The District's engineer is still reviewing the adequacy of the proposed design along Timberline. The
District expects to have its technical comments soon.
Boxelder Sanitation District has the following comment about sewer service to the Liberty Farms
development. The District asks that its comments be incorporated into the Development Agreement
that the City of Ft. Collins and Liberty Farms agrees to.
The proposed sewer line routing along Timberline that will connect Liberty Farms to the District's
existing sanitary sewer collection system within the Water Field development is an interim connection.
The District Is currently planning the construction of a sanitary sewer interceptor line (North Mulberry
Interceptor) that will serve a large basin that will include the Liberty Farms development. Until the
North Mulberry Interceptor is installed, the District will allow this interim connection to Its existing
collection system through the Water Field development.
The signature of Boxelder Sanitation District (District) on the final plat will be contingent upon an
Agreement Concerning Sanitary Sewer Service between the District and Liberty Farms being executed
prior thereto.
&:ADMINrSrRATIONwlasteralT'(�inplates4 dministr--,3tionV'nx\otigr'au.Uuc
9. Service connections to structures require an elder valve (sewer shut-off valve)
and a cleanout. Elder valves must be installed upstream of the cleanout and a
minimum 3-feet from any wall, overhang or other structure that might limit
access to the valve. Elder valves may be purchased from vendors in Fort
Collins, Colorado.
10. All construction shall be inspected by District inspector prior to backfill.
11. For off -site sewer line manholes: Manhole rims shall be set flush with the
surface when within an all-weather access roadway, rims shall be set 6-inches
above grade if they are not within an all-weather access roadway.
S:\DEVELOPMENT\Basins\West_Basin\Cooper_Slough_lnterceptor Subbasin\Liberty-Farms\Design Review\2008-9-4-
2nd-rev iew-co m me nts. d oc
Enclosure 4
Notes
To:
From:
Date:
Subject:
O
co
File
Engineering
05 September 2008
Sanitary Sewer Notes for Plan and Profile Sheets
3201 E. Mulberry Street,
Unit Q
P.O. Box 1518
Fort Collins, CO 80522
Ph: 970 498-
0604
Fax: 970 498-0701
1. All sanitary sewer line construction shall conform to the latest Boxelder
Sanitation District "Standards and Specifications for Sanitary Sewer Pipeline
Construction and Improvements."
2. All sewer services shall be minimum 4-inch diameter constructed at a slope of
2% from the building to the sewer main, unless otherwise specified and
approved by the District.
3. All 6-inch diameter sewer services shall be constructed at a slope of 1% from
the building to the sewer main.
4. When groundwater is encountered clay cut off walls shall be installed on the
upstream side of all manholes, in the mid -section of each main line run at
intervals not to exceed 300-feet, or as required by the District. See detail
sheets for clay cut-off wall detail.
5. Field verify invert elevation of sanitary sewer and basement finished floor
elevation for gravity flow prior to constructing foundations.
6. The Contractor shall schedule a pre -construction meeting with Boxelder
Sanitation District a minimum of one week before construction to coordinate
schedules and clarify any additional District requirements. Contact number is
970-498-0604.
7. Contractor shall notify the District's inspector forty-eight hours prior to start of
construction.
8. Contractor shall be responsible for coordinating field locates of all existing
utilities prior to any construction.
S:\DEVELOPMENT\Basins\West_Basin\Cooper_Slough_lnterceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2 n d-review-com m ents. doc
Enclosure 3
To be on all plan sheets with Boxelder Sanitation District lines/facilities/easements
Boxelder Sanitation District
Reviewed By:
General Manager Date
Review does not constitute "approval' of plans. Plan Engineer is
responsible for accuracy and completeness of plans.
S:\DEVELOPMEN-RBasins\West_Basin\Cooper_Slough_lnterceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2 nd-review-com m ents. doc
13. Concrete: All concrete construction shall be completed utilizing 3,000 psi at twenty-eight
(28) days or equal concrete.
14. Pavement or Other Repairs: In event that asphalt or concrete pavement, sidewalks,
storm sewers, waterline or any other public or privately owned property is damaged or
requires reconstruction due to the work, repairs or replacement will be made in
accordance with the requirements of the appropriate governing authority. Private property
will be returned to its original condition or as close to original condition as reasonably
possible, unless otherwise noted on the drawings.
15. Service Taps on Existing Lines: All taps made on existing lines shall be completed at
developer's expense by District personnel or the District's authorized contractor with no
exception.
16. Inspection: Construction shall conform to District Standards and Specifications or project
specific specifications at all times. The District shall inspect the construction as necessary
and shall observe all line testing. The District shall have the authority to ascertain that all
construction of facilities is equal to or better than minimum construction requirements as
set forth in these Specifications. The District shall also have the authority to assign an
inspector to check any and all work, including all materials to be incorporated in the work,
excavation, bedding, backfill, testing and all construction methods and practices. The
contractor shall contact the District a minimum of 48 hours in advance when they intend
to work weekends for scheduling of weekend inspections.
17. Testing: All lines shall be pressure tested and flushed by the Contractor in accordance
with District Standards and Specifications and under the District's supervision. Upon
passing, copies of all passing test results including soils compaction in the area of sewer
main construction shall be provided to the District.
18. Acceptance: Upon completion of all utility construction (sewer and other) and fulfillment of
all District requirements, preliminary acceptance of new sewer system improvements will
occur in accordance with District's acceptance procedure.
19. Warranty: The Contractor shall warrant the materials, installation, workmanship and
surface restoration for a period of two years from date of preliminary acceptance. During
this warranty period the Developer shall promptly repair any defects in the work and
maintain the work area. At the close of the two-year warranty period the District will
make a field inspection. Upon satisfactory correction of any deficiencies noted the
District will grant final acceptance of the lines and work. The lines and the
appurtenances shall then become the sole property and responsibility of Boxelder
Sanitation District.
20. Drawings of Record and Total Costs: Within 90 days of preliminary acceptance of the
new facilities, the District shall be provided with acceptable Drawings of Record of the
complete system consisting of two sets of fill size reproduced prints, two sets of/2-size
reproduced prints, one set of 6 mil double matted reproducible mylars and one complete
digital file equivalent (software and version to be confirmed at time of delivery). Written
confirmation of the total cost of all sewer system improvements shall also be submitted
with the Drawings of Record.
S:\DEVELOPMENT\Basins\West_Basin\Cooper_Slough_Interceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2nd-review-comme nts. d oc
4. Safety: All sewer main installation within the District shall be subject to current
(Occupational Safety and Heath Association (OSHA) and the Colorado Safety
Association, (CSA) safety requirements. Contractor shall also comply with any and all
requirements and regulations as set forth by City, County, State and Federal agencies
having applicable authority.
5. Start of Construction: No construction shall begin without prior design review of the
District. The District shall be notified 48 hours in advance of starting construction or
testing to allow for scheduling.
6. Road Excavation Permits: In event that State, County or City road excavation permit(s)
are required, the Contractor is responsible for obtaining all road permits which may be
required.
7. Other Permits: The Contractor shall be responsible for obtaining all permits required for
construction.
8. Revisions: No verbal authorization for field revision shall be given. All requests for field
revision shall be made in writing accompanied by proposed change indicated on copy of
the approved design drawings. Any field revision approved and installed shall also be
accurately documented on the Drawings of Record.
9. Materials: Plastic Pipe —All gravity sanitary sewer piping shall be Polyvinyl Chloride
(PVC) unless otherwise noted on the approved drawings. Pipe 15" and smaller shall
conform to ASTM D3034, Type PSM, and SDR 35. Pipe 18" and larger shall conform to
ASTM F679. All fittings shall be (PVC) unless otherwise noted.
10. Pipe Cover: A minimum cover of 3-1/2 feet of cover shall be maintained throughout the
sewer line and service line installation.
11. Bedding: All sewer main installation shall include bedding. Bedding shall be W washed
rock uniformly graded and compacted. Refer to force main design for force main bedding
requirements. Trench shall be excavated to a depth below established grade equal to Y4
of pipe diameter (min. 4"). Bell depressions shall be provided for all joints. In event that
unstable trench conditions are encountered at pipeline grade 1-1/2" uniformly graded
washed rock shall be used for stabilization. Bedding material shall be placed and
compacted under and around sides of the pipe. Place bedding in such a manner as to
provide solid, uniform bearing surface for full length of barrel. Minimum 30" initial lift
above pipe before other than hand compaction equipment is to be used. Note maximum
trench width detail.
12. Backfill: Backfilling of trench shall be performed as soon as practical, subsequent to
inspection and approval. Backfilling of acceptable material shall not be placed in lifts of
greater than one (1) foot. Backfill shall be compacted to 95% of optimum density in
roadway and residential areas and 90% in all off -site easement areas unless otherwise
noted. Compaction testing of bedding and back fill shall be at least five tests per 1,000
feet and at varying depths and locations in accordance with the requirements of the
applicable authority or as required in project specific specifications.
S:\DEVELOPMENT\Basins\West_Basin\Cooper_Slough_lnterceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2 nd-review-com m e nts. d oc
Enclosure 2
Sgn��9
To: File
From: Engineering
Date: 05 September 2008
3201 E. Mulberry Street, Unit Q
P.O. Box 1518
Fort Collins, CO 80522
Ph: 970 498-
0604
Fax: 970 498-0701
Subject: Boxelder Sanitation District Construction Notes (to be included on the general
notes sheet of any set of construction plans)
The following information is condensed from the current "Standard Construction Specification
for Sewer Mains" as adopted by the Boxelder Sanitation District (District) and is to be
considered as such. In the event of any question the full document shall take precedence.
Existing Utility Locates: It shall be the responsibility of the Contractor to coordinate field
locates of all existing utilities prior to commencement of any construction. Contractor
shall also notify all affected utility companies prior to commencing construction. In the
event of damage to any existing utility, the contractor shall immediately notify the owner
of the utility involved and unless authorized in writing by the owner of the subject utility,
shall not attempt to make repairs. The cost of repairs shall be the responsibility of the
Contractor.
2. Preconstruction Easement Pictures: Contractor to provide sequential digital pictures
spaced at no more than 300 feet detailing conditions of the off -site easement conditions
and any structures that could be affected, to the District and the property owner prior to
the start of any off -site work. These pictures shall include all existing fence, ditches,
structures, buildings, water troughs, trees and all landscaping. Pictures are to be placed
at no more than four (4) pictures on a 11x8 sheet of photo paper inserted into transparent
sleeves and delivered with the drawings of record in a three (3) ring binder.
3. Protection of Property: Contractor shall continuously maintain adequate protection from
damage of all public and private property through which the work is done. Contractor is
solely responsible for working within the easements granted for the project.
S:\DEVELOPMENT\Basins\West Basin\Cooper_Slough_lnterceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2 nd-review-com m ents. d oc
Enclosure 1
Boxelder Sanitation District Easement Use Language for Platted Easements
Where Sanitary Sewer Will be Installed - to be Included on all Plats
1. There shall be no erection or construction of any building or other structure, or any
permanent obstruction, or decrease or substantial increase in ground level, from the
finished elevations on this set of plans, in a manner that will interfere with use of the
utility easement or impede access over and across the easement.
2. Landscaping in the area of the easement shall not create impediments to ingress and
egress, nor shall landscaping material be installed or any trees or shrubs whose
height is greater than 2-feet be planted in the easement area that may impinge on the
overall operation and maintenance of the infrastructure placed in the easement.
3. No fence, which may impede access to and across the easement, shall be installed
without prior approval from Boxelder Sanitation District. Any such fence, installed
with the Boxelder Sanitation District's approval, must have gates to allow access to
and across the easement of Boxelder Sanitation District's maintenance vehicles, and
must be paid for by the developer or property owner.
4. Boxelder Sanitation District, which owns infrastructure installed in the utility
easement, has the right from time to time to enlarge, improve, reconstruct, relocate
and replace any underground utility lines, improvements or other appurtenances
constructed hereunder with any other number or type of underground utilities and
pipelines, or other structures either in the original location or at any alternate location
or locations within said utility easement.
5. Boxelder Sanitation District shall have the right to mark the location of its
infrastructure by suitable markers set in or on the ground; provided that permanent
markers shall be placed in locations which will not interfere with any reasonable use
of said utility easement.
6. Boxelder Sanitation District shall have the right to install and maintain a gravel access
road within the utility easement for use by District personnel, equipment and vehicles.
S:\DEVELOPMENT\Basins\West_Basin\Cooper_Slough_lnterceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2 n d-review-comme nts. d oc
12+81 needs to be shown more clearly, identified as to be
reconstructed, and need to see where access road will be in relation to
this ditch to insure the access road and manholes will not interfere with
the property owner's use of the ditch/piping.
■ Need to determine means of access road crossing ditch (culvert?) just
north of STA 22+01.
■ Future storm sewer needs to be shown on drawing to ensure there is
space for it and the sanitary sewer along the east side of the
development.
■ Move manhole O7A south 40-feet to allow room for the installation of the
future ditch crossing.
18 of 46
■ Need temporary construction easements in place for future use at the
ditch crossing. Also would like to discuss how future construction can
occur with the stormwater ponds in place.
■ Show the stormwater ponds in the vicinity of manhole O7A so we can
determine access road location, ensure manholes will not be in the pond
embankments and ensure the manholes will not be submerged during
runoff events.
43 of 46
■ Add cleanout detail (emailed to engineer)
■ Add cut-off wall detail (emailed to engineer)
■ Use updated District review block (Enclosure 3, also emailed to design
engineer).
■ Include sanitary sewer notes for plan and profile sheets on all plan and
All Sheets
profile dwgs (Enclosure 4, also emailed to engineer)
■ Temporary construction easements need to be shown on all plan and
profile drawings.
■ Renumber all manholes as redlined on drawings.
If there are questions, please contact me at 970-498-0604.
Thank you.
Sinc y,
Randy Sidden , P.E.
District Engineer
Enclosures:
1. Boxelder Sanitation District Easement Use Language for Platted Easements Where
Sanitary Sewer Will be Installed
2. Boxelder Sanitation District Construction Notes
3. Boxelder Sanitation District Review Block
4. Boxelder Sanitation District Sanitary Sewer Notes for Plan and Profile Sheets
EC: Jade Miller, DMV Engineers
Don Tiller
S:\DEVELOPMENT\Basins\West_Basin\Cooper_Slough_Interceptor_Subbasin\Liberty-Farms\Design Review\2008-9-4-
2 n d-review-com m ents. d oc
s jq'?--�
05 September 2008
Ms. Shelby Sommer
City of Ft. Collins, Planning and Zoning
P.O. Box 580
Ft. Collins, Colorado 80522-0580
Re: Liberty Farms Final Utility Plan Review Comments
Dear Shelby,
Boxelder Sanitation District (District) has received plans for the above referenced project.
District staff has completed its review of the submittal and has redlined the drawings. Below
are comments on the redlines in the plans. Please note that not all redlines are listed below.
Sheet #
�— Comment
■ Notes regarding surface use of the easements in which the sanitary
Plat, 1 of 2
sewer will be installed must be included on the plat. See Enclosure 1
(notes will be emailed to the design engineer).
■ Drainage easement on east side of the property needs to be designated
Plat, 2 of 2
as utility and drainage easement (U&DE).
■ Add Boxelder notes. see Enclosure 2 (notes will also be emailed to
2 of 46
design engineer).
_
■ Need another sheet showing the interim offsite sewer to the south and
its connection to the existing sanitary sewer.
■ Need a 12-ft wide gravel access road along the interim offsite sewer for
4 of 46
District service vehicle access.
■ Need to show future storm drain on the east side of the site to be sure it
and the sanitary sewer have adequate space to be installed. _
�T
Pond 12 and East Pond: Need to see where sanitary sewer is in relation
to these two stormwater ponds. A gravel access road to the map.holes
i will be needed and the manhole(s) cannot be located on the side slopes
16 of 46
of a pond nor can the manholes potentially be submerged during a storm
j runoff event.
1 ■ Easement along east side of site: Is the easement wide enough for the
sewer and future stormwater line? Or is it just intended for the sewer?
Eliminate Manhole: See redlines on drawings.
■ Maximum spacing between manholes should be 400 feet, adjust
17 of 46 I
MHs105 and 106, see redlines on dwg.
! Existing irrigation ditch/piping on Holter property from STA 22+01 to
SADEVELOPMENT\Basins\West_Basin\Cpuper _Slough
_Interceptor _Subbasin\Liberty-Farms\m
Review\2008-9-4-2nd-review-comments.doc jHIO
3201 East Mulberry, Unit Q - P.O. Box 1518 • Fort Collins, Colorado 805
Phone (970) 498-0604 • Fax (970) 498-0701 • Email bsd@verinet.com
@ M 01 M
SEP 0 8 2008 D
Number: 160 Created: 2/22/2008
[2/22/08] Why are there no street trees along the western side of Lot 6? If this is an
issue related to the roundabout, let's discuss other solutions.
Acknowledged
Number: 161 Created: 2/22/2008
[2/22/08] General Note #6 on landscape plan says that final landscape plan shall
include the total area (in some square feet) for each landscape category. Please
add to plan.
Acknowledged
Number: 162 Created: 2/22/2008
[2/22/08] Trash enclosures need to be designed for walk-in service so that the main
gates do not need to be opened. This may be dimensioned on the enclosure detail,
but it is not clearly labeled. Also, please label swing gate material and color.
Acknowledged
Number:185 Creat /29/2
[2/29/08] Forestry (Tim Buchanan): These note ould be added to the dscape
plan:
"The soil in all landscape areas, including parkways and medians, shall be
thoroughly loosened to a depth of not less than 8 inches and soil amendment shall
be thoroughly incorporated intojhe soil of all landscape areas to a depth of at least 6
inches by tilling, disking or other suitable method, at a rate of at least 3 cubic yards
of soil amendment per 1,000 square feet of landscape area.
A permit must be obtained from the City forester before any trees or shrubs as noted
on this plan are planted, pruned or removed on the public right-of-way. This
includes zones between the sidewalk and curb, medians and other city property.
This permit shall approve the location and species to be planted. Failure to obtain
this permit may result in replacing or relocating trees and a hold on certificate of
occupancy.
The developer shall contact the City forester to inspect all street tree plantings at the
completion of each phase of the development. All trees need to have been installed
as shown on the landscape plan. Approval of street tree planting is required before
final approval of each phase. Failure to obtain approval by the City forester for
street trees in a phase shall result in a hold on certificate of occupancy for future
phases of the development."
Complete
Page 2
Comments on Liberty Farms
9-3-08
Tim Buchanan
Landscape notes need to be added to the plan.
Change PYUS Ussurian Pear used as a street tree to Chanticleer Pear.
English Oak QURO be changed to Skymaster English Oak Quercus robur `Skymaster'
!%! FINAL PLAN
Cityof_ and
Planning
REVISION COMMENT
Zoning
PO Box 580
Fort Collins. CO 80522-0580 SHEET
Fax: 970-416-2020
DATE: August 21, 2008
TO: Forestry
PROJECT PLANNER: Shelby Sommer
# 31-06B LIBERTY FARMS PDP
2nd Round of Review
Please return all comments to the project planner no later than the staff
review meeting:
September 3, 2008
Note - Please identify your redlines for future reference
❑ No Problems
Problems or Concerns (see below, attached, or DMS)
S'.e ,e k44ae._ L4Q q
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS _
_Plat _Site _DrainsS rt _Other /
_Utility _Redline Utility ClLadscape
City of Fort Colli
27. Check stationing/ location of fitting at site entrance.
Done
28. Show in the profile the water crossing at the ditch crossing. See redlines.
Ditch crossing has been added
29. Tie water line into existing water on west side of street after ditch crossing. Use 8" tee and cap line
continuing north.
30. Add steel casing detail provided in redlines. Also include Buried Casing Detail to detail sheet..
Detail has been added
Sheet 19
31. Verify service line locations in profile and label them as service lines.
Locations have been checked
32. Install Blue Board insulation to service line crossing —4+60 on storm line 5..
Note has been added
33. Add isolated water main detail to detail sheet.
Done
Sheet 20
34. Verify service line locations in profile and label them as service lines..
Locations have been checked
Sheet 31
35. Remove large meter vault detail (top and side view). Replace with Large water service detail- 1 %2" through
2".
Done
36. Add buried casing detail.
Done
Please return redlines with submittal.
F:\Drawings\LIB\DOCS\Comment reponce for ELCO Water.wpd
12. Tie valve to fitting at round -about.
Acknowledged
13. Leaders need to be checked for where they are pointing..
Acknowledged
14. Add valve to end of water line (before plug) South end of Collamer Rd..
Valve has been added
15. Move water service for bldg 5 to come off of (new) 8" water line that goes on front of the building. See
redlines.
Service has been moved
Sheet 15
16. Change 12" proposed water to 8" (typ).
Done
17. Connect water to existing water north of ditch/ canal..
Acknowledged
Sheet 16
18. Move water service line for bld 5 as noted in comment 15.
Service has been moved
19. Verify service line locations in profile and label them as service lines..
Done
Sheet 17
20. Verify service line locations in profile and label them as service lines..
Done
21. Check profile vs plan view stationing. They do not match..
Checked and fixed
Sheet 18
22. Change Vine/ Timberline water connections per redlines..
Done
23. Change all references to a proposed 12" water line to 8".
References have been changed.
24. Change butterfly vales to gate valves.
Valves have been changed.
25. Replace 2" line with proposed 8".
Done
26. Change reference of DIP to C900
References have been changed.
Comments from ELCO Water
Sheet 2
l . Under general notes, note 5. Please change the note to state that the water needs to be to
ELCO Water standards.
Note has been changed
2. Under general notes, note 39. Please add ELCO to the end of the note.
Note has been changed
3. Under Water notes, note 4. Please change the city contact information to ELCO information.
Information has been changed
4. Under Water notes please add a note 6 stating " Prior to construction a ditch crossing easement agreement
shall be recorded with Larimer County and on file at ELCO offices."
Note has been added
5. Under Water notes please add a note 7 stating "16" water pipe shall be ductile iron. All other pipe shall be
C900, PVC."
Note has been added
Sheet 4
6. Change all references to proposed 12" water line to 8" water line.
References have been changed
7. Add valves to all fire service lines.
Valves have been added
8. Move building 2's water and fire service to attach to and to the tee of the fire hydrant. See redlines.
Fire line and service has been moves
9. Chance all reference of proposed DIP to PVC.
References have been changed
10. Move Meter and stop to south of storm. Insulate Service line.
Meter has been moved. Note has been added.
II. Change water line that goes through lots 5-7 from a 6" to a 8" line.
Water line has been changed to 8"
1W NW
FINAL PLAN
°`- REVISION COMMENT
Planning and Zoning
PO Box;so SHEET
Fort Collins. CO 30522-0580
Fur: 970-416-2020
DATE: August 21, 2008
TO: ELCO
PROJECT PLANNER: Shelby Sommer
# 31-06/13 LIBERTY FARMS PDP
2nd Round of Review
Please return all comments to the project planner no later than the staff
review meeting:
September 3, 2008
Note - Please identify your redlines for future reference
No Problems
® Problems or Concerns (see below, attached, or DMS)
0
-NARWIN WILLS
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_Plat _Site _Drainage Report _Other
_Utility _Redline Utility _Landscape
08-29-2008
rx�
9
pumping system will be required. The outfall for a pumping system would probably
have to be the irrigation canal, which would require there approval.
Number: 218 Created: 9/5/2008
[9/5/08] The 36-inch storm sewer that is located behind the sidewalk will be a public
storm sewer maintained by the City. Since this storm sewer is located on private
property, the City will not be responsible for replacing and landscaping due to any
maintenance or replacement activities. The City is only responsible for the
maintenance of the pipe and bring the ground surface back to grade as shown on
the plans.
Also, a 20-foot drainage easement is required with the pipe centered within the
easement.
Number: 219 Created: 9/5/2008
[9/5/08] The retention pond slopes need to be 4:1, not 3:1. The City has had
problems with 3:1 slopes and a variance for this requirement is highly unlikely.
Number: 220 Created: 9/5/2008
[9/5/08] Please add a note on the storm sewer profiles that all storm sewers are to
be inspected by the City.
Number: 221 Created: 9/5/2008
[9/5/08] The detention pond outlet pipe for the ultimate condition needs to be
plugged in the interim. This will allow only one pond bottom seeing water, which will
be better for maintenance. The spillway will need to carry the 100-year flow if the
second retention pond was ever needed.
Number: 222 Created: 9/5/2008
[9/5/08] An off -site drainage easement is required for the second retention pond
before signing of mylars.
Number: 223 Created: 9/5/2008
[9/5/08] The location of the off -site storm sewer is shown to be located on
neighboring property. Please remove the pipe on the plans, due to the City not
wanting any predetermined location for this storm sewer.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
Shelby Sommer
City Planner
Page 5
[9/3/08] A development agreement information sheet must be submitted before I
can begin drafting the DA.
Topic: Technical services
Number: 211 Created: 9/3/2008
[9/3/08] No problems.
Department: Light & Power Issue Contact: Doug Martine
Topic: Electric Utility
Number: 87 Created: 10/29/2007
[8/22/08]
[10/29/07] No comments for the second round of review.
Department: Stormwater-Water-Wastewaterlssue Contact: Wes Lamarque
Topic: Stormwater
Number: 213 Created: 9/5/2008
[9/5/08] The retention ponds are significantly lower than the Larimer-Weld ditch
bottom and ground water may be a problem with these ponds. Please submit data
showing what the ground water elevation is during the irrigation season.
Number: 214 Created: 9/5/2008
[9/5/08] The City has concerns with the slope off the irrigation ditch which will be
over 12 feet high from the top of the ditch to the bottom of the pond. This is basically
creating a levee. More engineering thought into the feasibility of this design needs
to take place. Is this slope stable? Will seepage occur? Benching the slope, cut-off
wall, subdrains may be some options to help mitigate concerns.
Please label the dimensions of the slope including the top width.
The Ditch Company would have to approve this design due to the slope
compromising the structural integrity of the canal. The City would also need
indemnification.
Number: 215 Created: 9/5/2008
[9/5/08] The City does not allow buried rip -rap anymore on side slopes. Rip -rap can
be used only at pipe outlets where the slope is relatively flat. The City suggests
having the storm sewers that enter the detention pond outlet at the toe -of -slope.
Concrete rundowns or grouted rip -rap is another option, although these may be
more expensive and not as attractive.
Number: 216 Created: 9/5/2008
[9/5/08] The north swale that has a slope of 1 % needs to be 2% or the swale needs
to include a pan or an underdrain system. If this creates a problem with slopes next
to the can, an alternative or a variance may be granted.
Number: 217 Created: 9/5/2008
[9/5/08] The retention ponds need to drain within 72 hours according to state law.
Unless a percolation test shows these ponds will infiltrate within this time frame, a
Page 4
forthcoming. The CDOT detail might be acceptable for Cherryhurst. Please check
with Rick. Insert the CDOT detail into the plan set if you will be using this.
Number: 202 Created: 9/3/2008
[9/3/08] Provide a typical detail for the bike access ramps at the R.A. I will check
with the City Engineer regarding angle of approach etc. and get back with you.
Number: 203 Created: 9/3/2008
[9/3/08] Some of the HC ramps on the plans do not appear to match the LCUASS
1606 standard. Please revise the ramps on the plan and call them out with the 1606
detail just for clarification.
Number: 204 Created: 9/3/2008
[9/3/08] There are still a number of line over text conflicts in the plan set. I have
circled some of them in the redlines. Please go through the plans one more time
and try to fix as many as possible before going to mylar.
Number: 205 Created: 9/3/2008
[9/3/08] Submit one deed of dedication and stamped legal & exhibit for the drainage
easement needed for the off -site pond. The review fee is $250.
Number: 206 Created: 9/3/2008
[9/3/08] Ultimate Timberline Design - Please show all 3 profiles for Timberline
independently for the entire frontage of the property. Off -site preliminary design
must also show all 3 profiles but you can show the off -site preim. portion as you
have with this submittal if you like. We detailed info in the profiles for the medians.
Show medians with respect to the crown of the road.
Number: 207 Created: 9/3/2008
[9/3/08] Road cross sections are not shown consistently. See sheet 26 and 27 of
the redlines.
Number: 208 Created: 9/3/2008
[9/3/08] Vertical curve standards are not being met on Collamer north of the R.A.
50 mph design speed, 2-lane arterial, 4 percent grade change. I will check with
Sheri to determine if a variance is appropriate for this stretch of roadway over the
box culvert. Off -site prelim. Design should be adjusted to meet standards
regardless.
Number: 209 Created: 9/3/2008
[9/3/08] 1 still need resolution on the clearance between the road design for
Collamer and the box culvert. Can the full road section be built as shown and
maintain adequate clearance to satisfy the box culvert owner ?
Number: 210
Created: 9/3/2008
Page 3
1. Sheet 25 shows a 64' wide interim street cross section on Timberline whereas the
plans on previous sheets show a 54' wide cross section.
Sheet 33
1. For the westbound left turn lane on Cherryhurst: delete the diagonal taper line and
the dotted line across the taper area. Extend the double yellow (on the
southernmost yellow line dividing the westbound left turn lane from the eastbound
through lane) from the intersection to where the taper area starts (approximately sta
12+94).
Number: 212 Created: 9/4/2008
[9/4/08] Tim Buchanan (Forestry):
1. Please change PYUS Ussurian Pear used as a street tree to Chanticleer Pear
2. English Oak QURO be changed to Skymaster english Oak Quercus robur
"Skymaster"
Department: Engineering Issue Contact: Randy Maizland
Topic: Engineering
Number: 197 Created: 9/3/2008
[9/3/08] Please add a new note to the Plat regarding resource conserving
equipment. I have attached the note to the redlines.
Number: 198 Created: 9/3/2008
[9/3/08] The Plat shows a 20 foot drainage easement along the east side of the
property. This should be a U.E. for the sewer. The 10 foot off -site portion of this
sewer easement will be dedicated to the District so please label it this way on the
sewer design plans and make sure all of the dimensioning is consistent and matches
the Plat. All easements to utility districts will need to be recorded prior to final plan
approval and reception numbers referenced on the plan. Only the drainage
easement for the pond will be dedicated to the City. Submit deeds of dedication and
stamped legal with exhibit + a $250 review fee.
Number: 199 Created: 9/3/2008
[9/3/08] Please use SHARKS TEETH striping at the R.A. approaches at the yield
line. Revise the detail accordingly. See LCUASS Figure 8-15 and sheet 7 of the
redlines.
Number: 200 Created: 9/3/2008
[9/3/08] Please provide details for the 6 foot pan and center island mountable curb
proposed for the R.A. See sheet 9 of the redlines for clarification.
Number: 201 Created: 9/3/2008
[9/3/08] Rick Richter in the Pavement Management Department will be reviewing
the concrete jointing pattern for the R.A. and the Cherryhurst street section (no
jointing pattern provided for Cherryhurst?). Comments from Rick will be
Page 2
r:
City of Fort Collins
STAFF PROJECT REVIEW
DON TILLER
2121 Midpoint Dr., Suite 302
FT COLLINS, CO 80525
Date: 09/04/2008
Staff has reviewed your submittal for LIBERTY FARMS PDP - TYPE II AND FINAL
PLANS, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Shelby Sommer
Topic: General
Number: 195 Created: 8/28/2008
[8/28/08] Great job addressing my last round of comments ... I'm ready for mylars!
Number: 196 Created: 9/3/2008
[9/3/08] Joe Olson (Traffic Operations):
Sheet 9
1. Remove the "YIELD" pavement marking word symbols shown on each approach
to the roundabout.
Sheet 23 and 24
1. The interim cross section for Timberline Road includes a 12' wide northbound bike
lane. It is likely that this will end up being used as a defacto right turn lane by
motorists. A more effective cross section would include a 12.5' northbound right turn
lane (measured from the flow line), a 5' bike lane, an 11' northbound through lane,
an 11' southbound left turn lane (shadowed by an 11' painted median on the south
side of the intersection), an 11' southbound through lane and a 5' southbound bike
lane/shoulder. A short northbound right turn bay taper should be included as part of
this cross section and the bike lane should be dotted (2' line + 2' space) across the
taper area.
2. Marking should be as per the latest edition of the Manual on Uniform Traffic
Control Devices (MUTCD). The MUTCD no longer includes diamond pavement
markings for bike lanes. Those should be removed from the plans.
3. The hatching pattern should be removed from the painted medians.
4. Remove the dotted line across the southbound left turn bay entering taper.
5. Remove the crosswalk and STOP bar shown across Cherryhurst.
Sheet 25