City of Fort Collins Water Conservation Standards for Landscapes
COMMENT SHEET
Project Name: TAVi urP
Date of Review: 12 -1 2 ^ o ::7
Reviewed By: Laurie D'Audney, Water Conservation Specialist, 221-6877
I have reviewed this landscape plan and it does not comply with the standards marked below.
Landscape Plan Requirements
1.. The landscape plan shall contain a general note calling for the review and approval by the City
of Fort Collins of any required landscape irrigation system, prior to the issuance of a Building
Permit.
2. The landscape plan shall include the total area (in square feet) for each landscape category.
Landscape categories are distinguished by their water requirements and intended maintenance
level. Examples of possible categories include, but are not limited to, high water turfgrass, low
water turfgrass, low water planting beds, moderate water planting beds, and non -plant areas
(paved areas, etc.).
❑ 3. Mulches shall be used for planting beds. The mulch can be either organic or inorganic, and
shall be applied to a minimum depth of 3 inches. In order to. prevent large expanses of barren
mulch, there shall be a minimum plant cover of 50 percent within 5 years of planting. .
(more)
700 Wood St. • PO. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6700 • FAX (970) 221-6619 • TDD (970) 224-6003
e-mail: utilities@fcgov.com . www.fcgov.com/utilities
COMMUNITY PLANNING AND ENVIRONMENTAL SERVICES
s a.
4 Fort Collins Neighborhood & Building Services
281 N. College Ave., P.O. Box 580; Fort Collins, CO 80522-0580; Voice: 970 2216760 FAX: 970 224 6LU
Ctn of Pori Collins
Codes and Standards
City of Fort Collins adopted codes applicable to all construction.
Residential - Includes single family, duplex and property -line townhomes
2003 International Residential Code with local Amendments
2005 Fort Collins Residential Energy Code (IRC chapter 11 amended entirely)
Accessibility -State Law CRS 9-5 (4 or more units in one building or more than 7 units in one
project) designed per ICC/ANSI Al17.1-1998
Wind Load: 100- MPH 3 Second Gust Exposure to be determined site specific
Roof Dead Load: 15 PSF min.
Snow Load Live Load: 30 PSF min.
Ground Snow Load 30 PSF
Frost Depth 30 inches
Seismic Design Category B
Commercial & Multi -family
1997 Uniform Building Code with local Amendments
2003 International Mechanical Code w/Amendments
2003 International Fuel Gas Code w/Amendments
2003 International Plumbing Code
2005 National Electrical Code
Fort Collins Nonresidential Energy Code, an amended version of ASHRAE/IES 90.1-1989
Fort Collins Multi -family residential energy code, 1995 Model Energy Code with amendments
Accessible and Usable Buildings and Facilities, ICC/ANSI Al17.1-1998, State Law CRS 9-5
Wind Load: 100-MPH Exposure B or 90-MPH Exposure. C
Roof Dead Load: 15 PSF min.
Snow Load Live Load: 30 PSF min.
Ground Snow Load 30 PSF
Frost Depth 30 inches
Seismic Zone 1
Pre -submittal Code Review Meeting Required
For All New Commercial & Multi -family prior to submitting for building permit
To schedule a Pre-submittial Code Review Meeting, call 416-2341 .
For questions regarding City of Fort Collins Zoning, call 416-2745.
For questions regarding Contractor Licensing rules call Delynn Coldiron at 221-6767.
,W
PROJECT
Cityaf_ COMMENT SHEET
Planning and Zoning
PO Box 580
Fort Collins. CO 80522-0580
Fox: 970-416-2020
DATE: December 3, 2007
TO: Building Inspection
PROJECT PLANNER: Steve Olt
# 37-07 Pavilion Place PDP — Type I
Associated with #6-96 (Harmony Center PUD)
Please return all comments to the project planner no later than the staff
review meeting:
December 19, 2007
Note - Please identify Your redlines for future reference
❑ No Problems
4J Problems or Concerns (see below, attached, or DMS)
FLEkt)E F 11.1D Pc -TT Fq:r,� WFLtCA-& , e'opeS `c ST+ANL&eAS
WE7 VJILl, E-,t.1POR-C,C
tAEETItl61 A-S NOT Et>
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_Plat _Site _Drainage Report _Other
_Utility _Redline Utility _Landscape
To: Steve Olt 12-19-07
From: Tim Buchanan
Re: Pavilion Place PDP
Street trees along Pavilion are labeled as Autumn Purple Ash which is not an approved
street tree. These need to be changed to Skyline Honeylocust or another species on the
approved city list. See comments on attached plant.
These plant notes should be added to the landscape plan.
The soil in all landscape areas, including parkways and medians, shall be
thoroughly loosened to a depth of not less than eight (8) inches and soil
amendment shall be thoroughly incorporated into the soil of all landscape areas to
a depth of a least six (6) inches by tilling, discing or other suitable method, at a
rate of at least three (3) cubic yards of soil amendment per one thousand (1,000)
square feet of landscape area.
A permit must be obtained from the City Forester before any trees or shrubs as
noted on this plan are planted, pruned or removed on the public right-of-way.
This includes zones between the sidewalk and curb, medians and other city
property. This permit shall approve the location and species to be planted.
Failure to obtain this permit may result in replacing or relocating trees and a hold
on certificate of occupancy.
The developer shall contact the City Forester to inspect all street tree plantings at
the completion of each phase of the development. All tres need to have been
installed as shown on the landscape plan. Approval of street tree planting is
required before final approval of each phase. Failure to obtain approval by the
City Forester for street trees in a phase shall result in a hold on certificate of
occupancy for future phases of the development.
Swamp White Oak is used on this project as a landscape tree. This species does not
survive in Fort Collins soils. Chinkapin Oak Quercus muehlenbergii looks similar to
Swamp White Oak. This species or another adapted species should be substituted for
Swamp White Oak.
cc: Marc Virata, City Engineering
Dana Leavitt, City Environmental Planner
Spirit Hospitality LLC
Shear Engineering Corp.
The Frederickson Group LLC
Intermill Land surveying, Inc.
Planning & Zoning file #37-07
Page 17
Number: 5 Created: 12/ 13/2007
[12/ 13/07] I don't see any bicycle parking noted for Buildings 1, 2 or 4.
Please note bicycle parking and locate close to main entrances of buildings.
Number: 6 Created: 12 / 13 / 2007
[12/ 13/07] There are no ramps shown next to the handicap parking spaces
- please show ramps on the Site Plan.
Number: 7 Created: 12 / 13 / 2007
[12/ 13/07] Please show building envelopes, footprints and setbacks on the
Site Plan.
Number: 8 Created: 12 / 13 / 2007
[12/ 13/07] Please show ramps at crosswalks.
Number: 9 Created: 12/ 13/2007
[12/ 13/07] The height of building 4 - the hotel - is not noted on the
Building Data table. Please add that.
Number: 10 Created: 12/ 13/2007
[12/ 13/07] A color key was provided on the elevations, but the shading
looks pretty much the same for most of the colors on the key as well as the
elevation drawings themselves. Please note the colors on the elevations with
the corresponding color code.
Number: 11 Created: 12/ 13/2007
[12/ 13/07] Please remove topography lines from the Landscape Plan.
After discussion at staff review on December 19th it was determined that
the plans with this development proposal are in a condition to be able
to be scheduled for a Planning & Zoning Board public hearing.
Therefore, the item has been placed on the January 17, 2008 P&Z
Board agenda. However, several departments need to see some revised
plans prior to the hearing. Please contact City staff directly for information
on what they need and by when to enable the item to stay on the agenda
(see comment #81, page 4, of this comment letter). Be sure and return all
red -lined plans when you re -submit documentation.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at 221-6341.
Yours Trully,
ARah-1-St
Olt
City Planner
Page 16
All storm sewers construction shall have water tight joints in compliance
with ASTM C-443 standards.
Please provide a detail for the proposed water quality plate showing number
of holes, size, elevations, etc... and for the grate (openings, type of materials,
etc...)
Please provide a construction level detail of the pond outlet structure. The
provided detail lacks reinforcement information and dimensions.
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/Wastewater
Number: 64 Created: 12/ 19/2007
[12/ 19/07] Sheet 2 refers to DIP for water main and Sheet 3 indicates PVC.
If the intent is to use PVC, include Standard Details 25 and 30 on the detail
sheets.
Number: 65 Created: 12/ 19/2007
[12/ 19/07] Revise fire hydrant, fire line and water service layouts as noted
on the red -lined Utility Plans.
Number: 66 Created: 12/ 19/2007
[12/ 19/07] Extend sanitary sewer west of drive entrance as shown to get
service more perpendicular to main and get service out from beneath thrust
block on 45-degree bend.
Number: 67 Created: 12/ 19/2007
[12/ 19/07] Add water main lowerings table with detailed information with
lengths, elevations, etc.
Number: 68 Created: 12/ 19/2007
[12/ 19/07] See red -lined plans for other comments.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: Zoning
Number: 3 Created: 12/ 13/2007
[12/ 13/07] Please remove the landscaping and grade lines from the Site
Plan. A separate Landscape Plan should be provided.
Number: 4 Created: 12/ 13/2007.
[12/ 13/07] There needs to be at least one Van Accessible handicap space
which needs to be an overall width of 16 feet and signed as "Van
Accessible". Please note it on the Site Plan.
Page 15
Please clarify the grading at the west end of the south entrance, what
elevation will the storm line be at? If possible provide an inlet at that
location rather then just a flared end section.
Topic: Hearing items
Number: 71 Created: 12 / 20 / 2007
[12/20/07] Items needed prior to hearing (by January 3, 2008):
* Letter of intent from the ditch company for approval of grading along
ditch right of way.
* Letter of intent from the Parkway Townhomes HOA for construction of
north retaining wall.
* Revised pond grading providing maintenance access and softening the
overall look of the pond with some landscaping.
Topic: Site and Landscape Plans
Number: 70 Created: 12 / 20 / 2007
[ 12 / 20/ 07] Please clearly label proposed retaining walls on both the Site
and Landscape Plans. It would help if storm lines shown on the Landscape
Plan are faded back and please make sure that the lines are consistent
between Site and Landscape Plans, and Utility Plans.
Topic: Storm line
Number: 20 Created: 12/ 18/2007
[ 12 / 18/ 07] The plans call for a 3'x6' box culvert to provide needed
detention. It is suggested that the 0.05 Acre-feet of detention be provided by
seeking a variance to the ponding depth in the parking lot if possible. This
variance would be approved as long as ponding does not exceed 18 inches
at any point. If not please consider the use of underground detention
systems in the parking area that will have better access for maintenance
purposes.
Topic: Utility Plans
Number: 22 Created: 12/ 18/2007
[12/ 18/07] Please call out the type and size of all existing and proposed
storm drainage facilities on the master Utility Plan (Sheet 3).
Please show 100 year HGL on all storm profiles.
Please add notes specifying that:
Maintenance of storm sewers outside the right of way shall be the
responsibility of the owner.
Page 14
Number: 17 Created: 12/ 18/2007
[12/ 18/07] ADDRESS NUMERALS: (NOTE: The lots shall be addressed off
Pavilion Place.) Address numerals shall be visible from the street fronting
the property, and posted with a minimum of 6 inch numerals on a
contrasting background. (Bronze numerals on brown brick are not
acceptable) . 97UFC901.4.4
Number: 18 Created: 12/ 18/2007
[12/ 18/07] FIRE LANE SIGNS: Please contact me regarding a fire -lane sign
template, because one of the signs shown on the plans is no longer what we
are using.
Department: Transportation Planning Issue Contact: Denise Weston
Topic: Transportation Planning
Number: 73 Created: 12 / 21 / 2007
[ 12 / 21 / 07] Note sidewalk widths on Site Plan. Please consider a smoother
transition between existing sidewalk and new sidewalk in the southwest
section of the development.
Department: Stormwater-Water-Wastewater Issue
Contact: Basil Hamdan
Topic: Ditch company approval
Number: 69 Created: 12 / 20 / 2007
[12/20/07] A letter of intent agreeing in principle to the proposed
improvements is required from the ditch company prior to hearing. At final
full ditch company approval will be required.
Topic: Drainage Plan
Number: 21 Created: 12/ 18/2007
[12/ 18/07] Please provide a pond summary table.
Topic: Erosion Control Plan
Number: 72 Created: 12 / 20 / 2007
[12/20/071 Please provide a silt fence along ditch to help protect ditch from
sediments during construction activities.
Topic: Grading
Number: 19 Created: 12/ 18/2007
[12/ 18/07] Please provide a tier stepped wall on the north and west side of
the detention pond. This will help for maintenance access and for visual
esthetics. Clearly designate pond overflow elevation and compare to
proposed building minimum opening elevations.
The retaining wall shown along the north property line is right on the
property line. A construction easement may be needed from the Parkway
Townhomes HOA to build this wall.
Page 13
❑ Be designed as a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road
base shall be used only for temporary fire lanes or at construction sites.
❑ Have appropriate maintenance agreements that are legally binding and
enforceable.
❑ Be designated on the plat as an Emergency Access Easement.
❑ Maintain the required minimum width of 20 feet throughout the length
of the fire lane.
97UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1
Number: 13 Created: 12/ 18/2007
[12/ 18/07] WATER SUPPLY: (NOTE: Location for the two new hydrants
looks excellent.)
Fire hydrants, where required, must be the type approved by the water
district having jurisdiction and the Fire Department. Hydrant spacing and
water flow must meet minimum requirements based on type of occupancy.
Minimum flow and spacing requirements include: Commercial, 1,500 gpm
at 20 psi residual pressure, spaced not further than 300 feet to the building,
on 600-foot centers thereafter; residential within Urban Growth Area, 1,000
gpm at 20 psi residual pressure, spaced not further than 400 feet to the
building, on 800-foot centers thereafter; residential outside Urban Growth
Area, 500 gpm at 20 psi residual pressure, spaced not further than 400 feet
to the building, on 800-foot centers thereafter.
These requirements may be modified if buildings are equipped with
automatic fire sprinkler systems.
97UFC 901.2.2.2
Number: 14 Created: 12/ 18/2007
[12/ 18/07] FIRE LINE REQUIREMENT: Buildings that are required to be
fire sprinklered shall have a minimum 6-inch fire line unless hydraulic
calculations can support a smaller fire line. NOTE: The fire lane shown
servicing Lot 3 is not labeled on the Master Utility Plan, Sheet 3.
Number: 15 Created: 12/ 18/2007
[12/ 18/07] BUILDING AREA: The proposed building exceeds 5,000 square
feet for type V construction and shall be fire contained or fire sprinklered.
(H4 > 3,000 SF = AS) 97UBC Table9-B (City of Fort Collins Amendment)
Number: 16 Created: 12/ 18/2007
[12/ 18/07] KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox
Box" to be mounted on the front of every new building equipped with a
required fire sprinkler system or fire alarm system. 97UFC 902.4; PFA
BUREAU POLICY 88-20
Page 12
hereby dedicated to the City as an emergency access, drainage and utility
easement and also hereby dedicates a shared access easement for the
benefit of Lots 1 through 4. Maintenance and ownership of Tract A shall be
the responsibility of Lots 1 through 4."
Number: 50 Created: 12/ 18/2007
[12/ 18/07] Larimer County Canal No.2 Ditch Company appears to need to
be a signatory to the plat with existing easements apparently onsite.
Number: 51 Created: 12/ 18/2007
[12/ 18/07] Technical Services has the following comments:
1. Boundary doesn't close.
2. Title and subdivision name in statement of ownership do not match.
3. PDP is a process and should not be in the name of the plat.
4. Who owns and maintains Tract A?
5. Text over line/scanning issues. See red -lines.
Department: Light & Power Issue Contact: Doug Martine
Topic: Landscape plan
Number: 2 Created: 12 / 6/ 2007
[12/6/07] There is an existing streetlight on Pavilion Lane., near building
#3, and another on JFK Pkwy., at Pavilion Lane. The developer needs to
survey the location of these lights, show them on the Landscape Plan.
Street tree locations then need to be adjusted to provide a minimum of 40 ft.
clearance between the lights and the trees (15 ft. if the tree is an ornamental
type) .
Topic: Utilities
Number: 1 Created: 12 / 6 / 2007
[12/6/07] The developer will need to coordinate the power requirements for
each building, locations for electric transformers, and the electric
development charges with Light & Power Engineering (221-6700). The
available locations for electric transformers appear to be quite limited, so
prompt contact with Light & Power is encouraged.
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 12 Created: 12/ 18/2007
[12/ 18/07] REQUIRED ACCESS: We prefer not to have a blanket
Emergency Access Easement (EAE). We can discuss the EAE over Tract A of
the plat, but we normally prefer to designate only the drive aisles as an
EAE. A fire lane shall be visible by painting and signage, and maintained
unobstructed at all times. A fire lane plan shall be submitted for approval
prior to installation. In addition to the design criteria already contained in
relevant standards and policies, any new fire lane must meet the following
general requirements:
Page 11
Number: 43 Created: 12 / 18/ 2007
[12/ 18/07] The Site Plan appears to show excess (and at times conflicting)
information with other documents. The grading contours can be removed
and the landscape information can be removed, which conflicts with the
landscape information shown on the Landscape Plan.
Number: 75 Created: 12 / 20 / 2007
[12/20/07] The comments from Engineering that should be resolved before
a hearing on the project are the following: 37, 38, 39, 40, 41, 42, 48, 49, 50
& 74.
Number: 76 Created: 12 / 21 / 2007
[12/21/07] In checking with Engineering Inspection on two issues brought
up at staff review regarding the construction of the extension of Pavilion
Lane, the following was noted:
- On the driveway not being constructed for the ditch company access,
this is being looked at further to recount past history between the
inspector and the contractor. There is reason to believe that the ditch
company was consulted and had no objection to the lack of a driveway,
though if this is not the case, the inspector will have the contractor for
Goodwill perform this work.
On the termination of the access ramp, the design and construction
was agreed to by the inspector and the contractor, not knowing whether
the extension of the sidewalk would take place at any point. The
development should reconstruct the access ramp as needed to continue
it to the east.
Topic: Plat
Number: 48 Created: 12 / 18/ 2007
[12/ 18/07] The existing 20' slope easement proposed to be vacated with
this plat is of potential concern at the ditch crossing. Not knowing the
grading in this area I'd prefer that this portion of the slope easement remain
(and doesn't appear to adversely affect the development) around the culvert
structure.
Number: 49 Created: 12/ 18/2007
[12/ 18/07] Tract A is indicated as being dedicated as various easements for
the benefit of Lots 1 through 4. If this is intended then to not be dedicated
to the City, then the Certificate of Dedication language should specifically
state the exemption of Tract A as being dedicated to the City to avoid
confusion. This would be of concern though as the emergency access,
drainage, and utility easement uses should be dedicated to the City for the
public use and not solely to Lots 1 through 4. Overall, I'd prefer that Tract
A note be amended to read similar to as follows: "With this Plat Tract A is
Page 10
Number: 74 Created: 12/20/2007
[ 12 / 20/ 071 Stormwater brought up the retaining wall shown along the
north boundary of the site and its location adjacent to the property line. It
would appear to be difficult to have this wall constructed without
permission from the property owner to the north. A letter of intent should
be provided from the owner to the north or the design should be revised (or
demonstrated) not to encroach offsite.
Topic: General
Number: 37 Created: 12 / 18 / 2007
[12/ 18/07] Please remove PDP from all the document titles. The naming of
the project as "Pavilion Lane" would be awkward with sharing the same title
as the street. Pavilion Place (as apparently titled in our comment sheets) or
some other title would be preferred.
Number: 38 Created: 12/ 18/2007
[12/ 18/07] Per the Development Review Engineering Manager's review of
the Transportation Development Review Fee submittal, an additional
$7,957.50 in fees is required.
Number: 39 Created: 12/ 18/2007
[12/ 18/07] Figure 19-6 of LCUASS specifies parking stall setback
requirements from public streets. The commercial local street classification
of Pavilion Lane combined with the 1580 daily trips specifies a parking stall
setback of 50' when 30' is provided. The handicap parking stall should
ideally be moved to the adjacent stall with this parking stall removed. (See
next comment regarding the design of the stall.)
Number: 40 Created: 12/ 18/2007
[12/ 18/07] The handicap parking stall itself shown on the site plan does
not appear to be sufficient in width (12' instead of 131, while the
construction plan drawings show this parking stall to be a standard stall at
Win width. The horizontal control information does not appear to match.
Number: 41 Created: 12/ 18/2007
[12/ 18/07] In general, the on -site design information appears slightly
different between the civil and planning documents. Internal curbing
around parking stalls, sidewalk widths, and parking stall widths differ
between the documents. Please coordinate.
Number: 42 Created: 12/ 18/2007
[12/ 18/07] A letter of intent from the Larimer Canal No. 2 Ditch Company
appears to be needed prior to a hearing for the project.
Page 9
Number: 85 Created: 12 / 21 / 2007
[ 12 / 21 / 07] The trash enclosure in the northwest corner of the site
currently lies within the natural area buffer. If the enclosure lies within the
ultimate buffer zone, it shall be relocated outside of the buffer area.
Number: 86 Created: 12 / 21 / 2007
[ 12 / 21 / 07] The trash enclosure located adjacent to Pavilion Lane may be
more appropriately located on the north side of the parking lot. This would
put the enclosure an additional 40' north of the roadway.
Department: Current Planning Issue Contact: Steve Olt
Topic: Transportation Planning
Number: 77 Created: 12 / 21 / 2007
[ 12 / 21 / 07] Denise Weston of the Transportation Planning Department
offered the following comments:
a. Please denote all sidewalk widths on the development plans.
b. Please make smoother "curved" transition of the public sidewalk at the
southwest corner of the site.
Department: Engineering Issue Contact: Marc Virata
Topic: Construction Plans
Number: 44 Created: 12/ 18/2007
[12/ 18/07] The construction drawings do not need to have Landscape Plan
information shown.
Number: 45 Created: 12/ 18/2007
[ 12 / 18 / 07] On Sheet 3 for Note 1 add "Limits of street repair are
approximate. Final limits to be determined in the field by the City
Engineering Inspector. All repairs are to be in accordance with City
Standards.
Number: 46 Created: 12/ 18/2007
[12/ 18/07] On the plan view of the construction drawings please show the
indication of truncated dome detectable warnings on either side of the
driveway out to Pavilion Lane just to sure it isn't assumed that scoring lines
are needed (realizing that the truncated dome warnings are accurately
reflected on the detail sheets).
Number: 47 Created: 12/ 18/2007
[12/ 18/07] Why is there grading information not shown north of the
culvert at the southwest corner of the site? (see ID #48)
Page 8
Number: 35 Created: 12/ 18/2007
[12/ 18/07] For the 3 pad sites, show the building setbacks from the
adjacent street rights -of -way.
Number: 36 Created: 12/ 18/2007
[12/ 18/07] Are the Typical (parking) Stalls dimensions the same
throughout the project?
Number: 79 Created: 12 / 21 / 2007
[12/21/071 In the BUILDING DATA table, there should be a height for
Building 4, the hotel.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Site Plan
Number: 53 Created: 12/ 19/2007
[12/ 19/07] Add the natural area buffer line. Measure from top of
embankment to edge of parking drive within property. Show the top of
embankment of the Site Plan. Refer to the redline plan for complete location
of buffer line.
Number: 54 Created: 12/ 19/2007
[12/19/07] The trash enclosure in the northwest corner of the property is
located within the buffer area. Locate this trash enclosure outside of the
buffer area.
Number: 55 Created: 12/ 19/2007
[12/ 19/07] Trash enclosure on the south side of the property and on the
Landscape Plan do not match. Resolve conflict. Consider moving this
enclosure to the north side of the parking lot as a means of reducing the
visual impacts from Pavilion Lane.
Number: 56 Created: 12/ 19/2007
[12/ 19/07] Remove landscape plants from Site Plan. Only show on the
Landscape Plan.
Number: 84 Created: 12 / 21 / 2007
[ 12 / 21 / 07] Add natural area buffer line to the plan. Show and label the
top of embankment of the Larimer County Canal Ditch #2 on the plan. This
line was identified in the field on a site visit between Don Ennis and Dana
Leavitt. If the buffer line extends into the property, align with the edge of
pavement on the parking lot and extend out to the maximum of 50' north
and south of the parking lot.
Page 7
Topic: Lighting Plan
Number: 58 Created: 12/ 19/2007
[12/ 19/07] Include a schedule of fixtures on Lighting Plan.
Number: 83 Created: 12 / 21 / 2007
[ 12 / 21 / 07] Add schedule of fixtures to plan. Will require all lights adjacent
to the natural area buffer be equipped with exterior house side shields.
Topic: Plat
Number: 52 Created: 12/ 19/2007
[12/ 19/07] Show buffer line on west property line. Add note to plat "Refer
to Section 3.4.1(E)(2) for allowable uses within a natural area buffer."
Number: 82 Created: 12 / 21 / 2007
[ 12 / 21 / 07] Add the buffer zone line to the plat based upon final location
derived from Site Plan. Label buffer zone as a natural area buffer. Add note
to Plat: "Refer to Section 3.4.1 (E) (2) of the City of Fort Collins Land Use
Code for allowable uses within a natural area buffer zone.
Department: Current Planning Issue Contact: Steve Olt
Topic: Site Plan
Number: 23 Created: 12/ 18/2007
[12/18/07] Please remove the landscaping from the Site Plan. There is a
separate Landscape Plan for that information. Also, the "conceptual"
landscaping on the Site Plan is not consistent with the actual Landscape
Plan. The drawing as submitted is cluttered and difficult to read.
Number: 24 Created: 12/ 18/2007
[12/18/07] Building 2 and the Hotel should have bicycle racks in
convenient locations next or near to them.
Number: 25 Created: 12/ 18/2007
[12/18/07] The "Sight" Triangles are misspelled on the Site Plan.
Number: 26 Created: 12/ 18/2007
[12/ 18/07] The street widths and right-of-way widths for both JFK
Parkway and Pavilion Lane should be shown on the Site Plan.
Number: 27 Created: 12/ 18/2007
[12/18/07] Show the setback distance for the parking areas from the west,
south, and north property lines on the Site Plan.
Number: 28 Created: 12/ 18/2007
[12/18/07] All sidewalk widths, internal to the site and along the streets,
must be shown on the Site Plan.
Page 6
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Grading
Number: 57 Created: 12/ 19/2007
[12/ 19/07] Show the top of embankment and buffer line on Grading Plan.
Coordinate with Site Plan.
Topic: Utility Plans
Number: 87 Created: 12 / 21 / 2007
[12/21/07] Show natural area buffer on all plans as derived from the Site
Plan.
Department: Current Planning Issue Contact: Steve Olt
Topic: Landscape Plan
Number: 29 Created: 12/ 18/2007
[12/ 18/07] Laurie D'Audney, the City's Water Conservation Specialist,
indicated that she is forwarding a Water Conservation Standards for
Landscapes COMMENT SHEET and the City of Fort Collins Water
Conservation Standards for LANDSCAPING and IRRIGATIONS General
information to the Applicant. These items are attached to this comment
letter.
Number: 32 Created: 12/ 18/2007
[12/ 18/07] Please revise the 3 building pad site notes to say: FUTURE
LANDSCAPING TO BE PROVIDED BY DEVELOPER OF PAD SITE, TYPICAL,
THROUGH THE CITY'S MINOR AMENDMENT REVIEW PROCESS.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Landscape plan
Number: 59 Created: 12/ 19/2007
[12/ 19/07] Show buffer line on Landscape Plan. Coordinate with Site Plan.
Add a ground cover level of plants within the buffer area between the
parking lot and the property line. Additional plants are needed between the
edge of the ditch and Lot 3. Use all native plants within the buffer zone.
Number: 60 Created: 12/ 19/2007
[12/ 19/07] Use organic material within the buffer zone instead of cobble
mulch.
Number: 88 Created: 12 / 21 / 2007
[12/21/07] Add buffer line as derived from Site Plan.
Number: 89 Created: 12 / 21 / 2007
[12/21/07] Additional plant material is needed in the plant beds within and
adjacent to the buffer area. All plants are to be native species conducive to
improving wildlife habitat. Refer to the red -lines for location of additional
planting requirements.
Page 5
Number: 81 Created: 12 / 21 / 2007
[12/21/071 After discussion at staff review on December 19th it was
determined that the plans with this development proposal are in a
condition to be able to be scheduled for a Planning & Zoning Board
public hearing. Therefore, the item has been placed on the January 17,
2008 P&Z Board agenda. However, several departments need to see some
revised plans prior to the hearing. Please contact the following staff directly
for information on what they need and by when to enable the item to stay
on the agenda:
* Marc Virata/Engineering ... 221-6605
* Basil Hamdan/Stormwater ... 224-6035
* Roger Buffington/Water & Wastewater ... 221-6854
* Dana Leavitt/Environmental Planner ... 224-6143
Current Planning (Steve) needs the following information:
* Eight (8) full-size plans each of revised Site, Landscape, Building
Elevations, and Site Lighting Plans, addressing the comments in this
letter, by Friday, January 4th.
* Reduced copies, one (1) each to 8.5" x 11", of the Site, Landscape, and
Building Elevations Plans by Wednesday, January 2nd. Prefer to have
them sent electronically to rmichels(@fcgov.com.
* One (1) each of rendered (colored) Site and/or Landscape Plan, and
Building Elevations by Wednesday, January 9th. Prefer to have them
sent electronically to rmichelsafcgov.com.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: General
Number: 90 Created: 12 / 21 / 2007
[ 12 / 21 / 071 I will need to see revised plans no later than January 4th to
keep the project on the P&Z Board agenda. The following plans are required
for review:
- Plat
- Site Plan
- Landscape Plan
- Grading Plan
- Horizontal Control Plan
- Utility Plan
Page 4
c. Additional Transportation Development Review Fees are due. They must
be paid to the Development Review Center prior to this project going to
a Planning & Zoning Board public hearing, such as with the next
informal submittal.
d. The handicapped parking space and the next conventional space just to
the northwest of the entry into the site may have to be eliminated
because they do not meet the 50' setback distance requirement from the
street flowline. The setback distance is for safety reasons.
e. The Larimer County Canal No. 2 ditch company must be notified, with
plans provided to them. City staff needs some form of response from the
ditch company prior to the P&Z public hearing. The ditch company will
have to sign the Final construction documents.
f. There are numerous inconsistencies between plans. The construction
drawings must be coordinated, made consistent, with the Site Plan.
g. Please take the Landscape Plan out of the construction drawing set.
Water & Wastewater/Roger Buffington
a. Poudre Fire Authority and Water & Wastewater need to talk about the
proposed fire hydrant locations.
b. The department's comments are relatively minor.
Transportation Planning/Denise Weston
a. Please smooth out the sidewalk transition at the southwest corner of
the site.
b. All sidewalk widths must be shown on the development plans.
Light & Power/Alan Rutz
a. He has not further comments prior to public hearing.
Number: 80 Created: 12 / 21 / 2007
[ 12 / 21 / 071 Apparently there is a proposed retaining wall shown on the
construction drawings at the northeast corner of the site that is not shown
on the Site & Landscape Plans. Please show this wall on all plans. How is it
going to be built?
Page 3
Number: 34 Created: 12/ 18/2007
[12/ 18/07] A detail showing the style, height, material(s), and general
color(s) for the proposed fences on the west and north property lines is
needed.
Number: 78 Created: 12 / 21 / 2007
[12/21/07] The following comments were offered by City staff at the staff
review meeting on December 19, 2007:
Stormwater/Basil Hamdan
a. Generally, this is a very good set of development plans. They are
substantially complete.
Environmental Planner/Dana Leavitt
a. The required buffer line for the Larimer County Canal No. 2 ditch along
the west side of the property must be clearly shown on all plans. The
buffer line must be a minimum of 30' from the "top of bank", which is
reduced from the normally required 50'.
b. The proposed fence as shown along the west property line is not
consistent with the purpose of the wildlife corridor. If a fence is to be
installed in this location it should be something like an open, 3-rail
fence. One is not required.
c. The proposed landscaping along the west property line is insufficient to
mitigate the allowable reduced buffer distance. Also, native plants must
be used in this area.
d. A schedule of lighting fixture types is needed on the Site Lighting Plan,
or another plan added to include this information. Technically, a
Photometric Plan showing spot lighting levels is normally provided.
e. There appears to be a potential safety issue with the detention pond -
public sidewalk relationship at the southeast corner of the site,
adjacent to the 2 streets.
Engineering/Marc Virata
a. Please remove the reference to PDP from the plans. PDP really refers to
a particular phase in the City's development review process.
b. Pavilion Lane, being the adjacent street, may be confusing as the
project name. Possibly "The Plaza at Pavilion Lane", or something like
that, would be a better name.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Ennis Associates
c/o Don Ennis
13994 Turnberry Court
Broomfield, CO 80023
303-465-2983
Date: 12 / 21 / 2007
Staff has reviewed your submittal for PAVILION LANE PDP - TYPE 2, and
we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Building Plans
Number: 61 Created: 12/ 19/2007
[12/19/07] There is a legend with letter -designated colors for the buildings
on the plans. However, none of the elevations clearly differentiate what area
is what.
Number: 62 Created: 12/ 19/2007
[12/ 19/07] Identify the various materials on the building plans.
Number: 63 Created: 12/ 19/2007
[12/ 19/071 Several building bays on the north, south, and east elevations
exceed 30' in length and the plans do not clearly depict if these bays satisfy
the standards set forth in Section 3.5.3(D)(2) of the Land Use Code.
Topic: General
Number: 30 Created: 12/ 18/2007
[12/ 18/07] Rick Lee of the Building Department indicated that he is
forwarding a copy of the Codes and Standards that his department will
enforce. It is attached to this comment letter. Also, please note that a Pre -
submittal Code Review Meeting is required and should be scheduled with
him.
Number: 31 Created: 12/ 18/2007
[12/ 18/07] Bonnie Ham of the U.S. Postal Service indicated that the
Developer is responsible for providing mailbox(es) for businesses. The
preferred location is on Pavilion Lane close to the entrance to the site. Please
contact Bonnie at 214-3668 (cell).
Number: 33 Created: 12/ 18/2007
[12/ 18/07] A detail is needed for the Trash Enclosures. Materials and
colors must be consistent with the buildings.
Page 1
Steve Olt -Pavilion Lane PDP Page 1
From: Steve Olt
To: bshear@shearengineering.com; don.ennis@comcast.net;
mcole@shearengineering.com; tim@frederickson.us
Date: 12/21/2007 4:14:36 PM
Subject: Pavilion Lane PDP
Attached is the staff comment letter for the Pavilion Lane PDP. Attached to the hard -copy letter is a
Revision Routing Sheet telling you how many of what documents need to be submitted by when (January
3, 2008) for this item to be, and remain, on the January 17, 2008 Planning & Zoning Board public hearing
agenda.
The original letter, addressed to Don Ennis, and hard copies of the letter for Spirit Hospitality, Shear
Engineering, The Frederickson Group, and Intermill Land Surveying are with one stack of red -lined
drawings on our Development Review Center counter at 281 North College Avenue. Someone from your
development team should pick them up as soon as possible. Our building will be closed only on Christmas
day, December 25th, and New Year's day, January 1 st.
Steve