HomeMy WebLinkAboutCENTRE AVE. RESIDENCES - PDP - 17-09 - CORRESPONDENCE - (3)Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 6 Created: 5/5/2009
[5/5/09] Fire hydrant coverage has been reviewed with PFA. Remove the proposed hydrant
near the east building, and abandon 6-in fire line stub at main in Centre.
Number: 7 Created: 5/5/2009
[5/5/09] A 1-inch water is not adequate for the 10 units included in Bldg 2.
Number: 8 Created: 5/5/2009
[5/5/09] Label sizes of water/sewer services to the proposed buildings.
Number: 9 Created: 5/5/2009
[5/5/09] At final, label all valves, fittings, connections, etc.
Number: 11
[5/5/09] See red -lined plans for other comments.
Department: Zoning
Topic: zoning
Number: 1
[4/20/09] No issues.
Created: 5/5/2009
Issue Contact: Gary Lopez
Created: 4/20/2009
Be sure and return all red -lined plans if/when you re -submit prior to a Planning & Zoning
Board public hearing on June 18`h, or with Final Plan submittal after the hearing.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at 221-6341.
Yours Truly,
A
K
Steve Olt
City Planner
cc: Andrew Carney
Everitt Companies/Stan Everitt
Northern Engineering
Current Planning file #17-09
Page 5
Number: 27 Created: 5/8/2009
[5/8/09] Please identify what exactly is going to be removed/relocated on the site and what
will remain. The drive offset on the access onto Worthington Circle, if modified, should not
be increased with the new design. If anything, the offset should be eliminated by sliding the
new access to align with the existing drive.
Number: 28 Created: 5/8/2009
[5/8/09] See red -lines for additional minor comments.
Number: 29 Created: 5/8/2009
[5/8/09] It appears that currently the existing walk is a 4-foot wide walk. This does not
currently meet our standards however it appears to be in good condition. If any sections of
the walk are to be removed it should be replaced in accordance with current standards.
Department: PFA
Topic: Fire
Number: 20
FIRE DEPARTMENT CONNECTION
location(s) for the FDC(s).
Issue Contact: Carie Dann
Created: 5/6/2009
Please contact me so we can determine optimal
Number: 21 Created: 5/6/2009
EAE signs: Please contact me to discuss how to sign the Emergency Access Easement (drive
aisles as well as walkways).
Number: 22 Created: 5/6/2009
FIRE LINE LOCATED UNDER BUILDINGS: According to NFPA 24 (8-3.1), fire line pipe
is NOT allowed to be run under buildings. Your utility plan shows fire lines being run under
buildings, between Building 1 and 2, and 1 and 3. Please contact me to discuss.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Stormwater .
Number: 23 Created: 5/8/2009
[5/8/09] The c-factor calculations are not correct with the amount of impervious area being
proposed. Basin B should be around .89 and C100 for this basin around 1.00. Please revise.
The c-factor I calculated for the entire site is .63, which is still less than the required .71.
Number: 24 Created: 5/8/2009
[5/8/09] The water quality volume will need to be recalculated. The impervious area for the
site is higher than the calculations show.
Number: 25 Created: 5/8/2009
[5/8/09] The project can go to a hearing based on the c-factor still less than .71.
Number: 26 Created: 5/8/2009
[5/8/09] At Final Plan review, the retaining wall needs to have a structural design. Also, the
ditch owner needs to be involved and any concerns the company has resolved.
Page 4
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Site Plan
Number: 13 Created: 5/6/2009
[5/6/09] Per the red -lined Site Plan, show the correct natural Feature Buffer line on the Site,
Landscape and Grading Plans and the plat.
Number: 14 Created: 5/6/2009
[5/6/09] Add the following note to the Plat, Site and Landscape Plans:
Refer to Section 3.4.1(E) of the Land Use Code for allowable uses within a buffer zone.
Number: 15 Created: 5/6/2009
[5/6/09] Label buffer line as "Natural Feature Buffer Line" on the Plat, Site, Landscape and
Grading Plans.
Department: Engineering Issue Contact: Andrew Carney
Topic: General
Number: 2 Created: 5/5/2009
[5/5/09] Engineering Inspection would like to see a more detailed plan of the proposed fire
line connection and master fire pump room.
Number: 3 Created: 5/5/2009
[5/5/09] Directional pedestrian ramps are required on any reconstructed drives - please
contact Transportation Planning for details.
Number: 4 Created: 5/5/2009
[5/5/09] Please provide more detail on the existing features surrounding the site such as
existing driveways and sidewalks on Centre Avenue and Worthington Circle and what
exactly is being proposed to be removed and/or reconstructed.
Number: 5 Created: 5/5/2009
[5/5/09] Please add the following note to the Utility and Grading sheets:
Limits of street cut are approximate. Final limits are to be determined in the field by the City
Engineering Inspector. All repairs to be in accordance with City street repair standards.
Number: 10 Created: 5/5/2009
[5/5/09] The following comments are from Technical Services:
1) Please add a legal description to the Site Plan.
2) There are scanning issues on the Site and Landscape Plans.
Number: 12 Created: 5/5/2009
[5/5/09] Please clearly label what exactly is existing and what is proposed. For instance, are
the existing drives changing or moving in any way?
Page 3
Department: Current Planning Issue Contact: Steve Olt
Topic: Landscape Plan
Number: 36 Created: 5/13/2009
[5/13/09] To satisfy the "full tree stocking " requirement set forth in Section 3.2.l(D)(1)(c)
of the Land Use Code, 3 - 4 more trees (probably ornamental) should be included on the west
side of Building One facing Worthington Circle.
Number: 37 Created: 5/13/2009
[5/13/09] Per Section 3.2.2(J) of the Land Use Code, the width of the landscaped area
between the Centre Avenue ROW and the tier of 7 parking spaces just to the west of the
driveway entrance from Centre Avenue must be 10' wide. The width scales to 7'.
Number: 38 Created: 5/13/2009
[5/13/09] With the Final Plan submittal please make sure that Section 3.2.1(D)(3) Minimum
Species Diversity of the Land Use Code is met.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Landscape Plan
Number: 16 Created: 5/6/2009
[5/6/09] Extensive native plantings are required within the buffer zone.
Topic: Photometric (lighting) Plan
Number: 17 Created: 5/6/2009
[5/6/09] Fixture CC next to the trash enclosure will have to include a house side shield.
Suggest numbering the CC fixtures so that the legend reflects the inclusion of the shield on
that fixture only.
Department: Current Planning Issue Contact: Steve Olt
Topic: Site Plan
Number: 32 Created: 5/13/2009
[5/13/09] The total number of on -site parking spaces required is 50, not 51 as shown.
Number: 33 Created: 5/13/2009
[5/13/09] Based on the subdivision plat there is no street right-of-way (ROW) within the
property boundary. Therefore, no ROW should be netted out of the land area, as shown under
GROSS AREA COVERAGE under LAND -USE STATISTICS.
Number: 34 Created: 5/13/2009
[5/13/09] The maximum building height is 61', per the Exterior Elevations Plans. The
additional height of the chimneys does not count towards the overall height. Please make this
change under BUILDING HEIGHT under LAND -USE STATISTICS.
Number: 35 Created: 5/13/2009
[5/13/09] Per Section 3.2.2(J) of the Land Use Code, the width of the landscaped area
between the Centre Avenue ROW and the tier of 7 parking spaces just to the west of the
driveway entrance from Centre Avenue must be 10' wide. The width scales to 7'.
Page 2
M2
STAFF PROJECT REVIEW
City of Fort Collins
VFR Design, Inc. Date: 5/13/2009
c/o Russell Lee
401 West Mountain Ave. Suite 200
Fort Collins, CO 80521
Staff has reviewed your submittal for CENTRE AVENUE RESIDENCES, PROJECT
DEVELOPMENT PLAN - TYPE 2, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Building Elevations
Number: 39 Created: 5/13/2009
[5/13/09] Since the 3 buildings have different orientations it would be more appropriate to
label the various elevations FRONT, REAR, and END rather than NORTH, SOUTH, EAST,
and WEST.
Topic: General
Number: 30 Created: 5/13/2009
[5/13/09] Rick Lee of the Building Department indicated that he is forwarding to the
applicant a copy of the 2008 Commercial/Multi-Family Codes & Standards that the City will
be enforcing. Also, the applicant is required to schedule a Pre -submittal Code Review
Meeting with the Building Department. Please call 416-2341 to schedule this meeting.
Number: 31 Created: 5/13/2009
[5/13/09] In general the plans are in very good shape and staff has determined that this
development proposal can be placed on the June 18th Planning & Zoning Board public
hearing agenda. However, it would be appropriate for the applicant to either submit revisions
based on these staff comments and go to a Wednesday morning staff review meeting before
June 18th or contact individual staff to ensure that their concerns expressed in this letter can
be addressed with Final Plan review and will not preclude the project from going before the
Board on June 18th.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: General
Number: 18 Created: 5/6/2009
[5/6/09] A Limit of Development (LOD) line will be added at the time of Final Plan review
to the Site, Landscape and Grading plans.
Number: 19 Created: 5/6/2009
[5/6/09] All comments can be addressed at Final Plan review.
Page 1