RESOLUTION 89- 179
OF THE COUNCIL OF THE CITY OF FORT COLLINS
APPROVING A REVISION OF ATTACHMENT C OF THE
POWER CONTRACT AND EXHIBIT A OF THE TRANSMISSION
FACILITIES AGREEMENT BETWEEN THE CITY OF FORT COLLINS
AND PLATTE RIVER POWER AUTHORITY
WHEREAS, the City of Fort Collins has heretofore executed an "Amended
Contract for the Supply of Electric Power and Energy" and a "Transmission
Agreement" with Platte River Power Authority (PRPA) ; and
WHEREAS, changes in operational conditions since the execution of said
agreements has required the addition of the Richards Lake and Linden Tecn
substation delivery points and has shown a need for further definition of
the maintenance responsibilities of the City and PRPA; and
WHEREAS, revisions to Attachment C of the Power Contract and Exhibit A
of the Transmission Facilities Agreement have been prepared, which
revisions have been recommended by the Utilities Director and approved by
the City Manager and City Attorney;
WHEREAS, said revisions would add the Richards Lake and Linden Tech
delivery points to the transmission system; would delete the 2% adder
presently included in the metering section of the Agreement; and would
clarify the division of maintenance responsibility between the City and
Platte River Power Authority.
NOW, THEREFORE, BE IT RESOLVED BY THE CITY OF FORT COLLINS as follows:
Section 1 . That the proposed revisions to Attachment C of the Power
Contract and Exhibit A of the Transmission Facilities Agreement between the
City of Fort Collins and Platte River Power Authority be, and the same are
hereby, approved; and
Section 2. That the Mayor and City Clerk be, and they hereby are,
authorized and directed to execute the same for and on behalf of the City
of Fort Collins.
Passed and adopted at a regular meeting of the Council of the City of
Fort Collins held this 17th day of October, A. . 1989.
Mayor
A T ST:
City Clerk
Exhibit "A"
The following properties comprise the Licensed Facilities to be
operated and maintained by Platte River Power Authority from and
after March 1 , 1980 pursuant to the provisions of Article ( 1 ) ( a)
of the Transmission Facilities Agreement to which this exhibit is
annexed .
Category Property Description FERC Account
( 1 ) Land and Land Rights 350
All land, land rights and easements
on which the following facilities
are erected :
( a) Poudre Tap to Power Plant Sub-
station 115 kV line
(b) WAPA Line to Drake Substation
115 kv line
(c) Timberline Park Substation
(Station 300 )
( 2 ) Station Equipment I 353
All foundations, control buildings , and
structural steel, 115 kV circuit
breakers, buses , switches and insulators ,
115 kV control equipment and devices , D-C
supply, fences, general station equipment,
switchboards , meters, relays, wiring and
other electrical facilities in service at:
Timberline Park Substation (Station 300 )
( 3 ) Station Equipment II 362
Til 115 kV breakers, buses , switches ,
insulators, control equipment & devices ,
switchboards , meters , relays , structural
steel and foundations in service at:
(a) Drake Road Sub (Station 200 ) and
(b) Overland Trail Sub (Station 400 )
(c) Power Plant Sub (Station 100 )
( 4 ) Poles and Fixtures--115 kV Lines 355
All anchors , head arm and other guys ,
including guy guards, guy clamps , pole
plates, etc; brackets; cross arms and
braces; gaining, roofing, stenciling
and tagging; insulator pins and suspension
bolts; pole steps; poles , wood & steel;
racks complete with insulators; reinforcing
and stubbing; settings; shaving and paint-
ing for the following facilities :
( a) Poudre Tap to Power Plant Sub
(b) WAPA Line to Drake Substation
(c ) Drake Sub to Platte River 230 kV
Line
(d ) 115 kV on double circuit south of
Station 300
Category Property Description FERC Account
( 5 ) All conductor, ground wires and ground 356
clamps, insulators , switches and
other devices for the following
facilities :
( a) Poudre Tap to Power Plant Sub
(b) WAPA Line to Drake Sub
(c) Drake Sub to Platte River 230
kV Line
(d ) Double circuit south of Station
300
The land and land rights licensed at Timberline Park Substation shall be that
enclosed by and shall include the existing substation fence, as shown on the
attached diagram. Said fence shall not be moved or expanded, and no permanent
facilities shall be constructed in the cross-hatched area shown on the diagram
as reserved for Fort Collins' future distribution facilities, without the per-
mission of the City of Fort Collins, which permission shall not be unreasonably
withheld. Maintenance of the grounds outside the substation fence and main-
tenance of the access road to the substation shall remain the reponsibility of
the City of Fort Collins.
Platte River agrees that (i ) it will not construct or permit construction of any
circuits under 115 kV to exit Timberline Park Substation overhead, (ii ) it will
not construct or permit construction of any 13 kV class circuits to exit said
substation except to supply electric loads of Fort Collins or Platte River, and
(iii ) it will provide at least two year' s notice of any expansion that would
impact nursery stock in locations presently utilized for this purpose.
The following table shows the cost and maintenance responsibilities agreed to by
the Parties:
FURNISH MAINTAIN
Substation: A, B, C, D, E, F, G, H, I , J B. C. D, E, F, G, H, I , J
Overland Trail C C C C C C C C C C C C C C C C C C C
Drake C C C C C C C C C C C C C C C C C C C
Timberline C C C C C C C C C C PR C PR C PR PR PR PR PR
Legend: C - City of Fort Collins
PR - Platte River
Furnish and Maintain Items:
(A) Site Purchase and Ownership (F) Control Building
(B) Grading and Surfacing Within (G) Battery & DC System
Fenced Area
(C) Access Road (H) Station Service
(D) Fence (I) Station Lighting
(E) Landscaping and Grounds (J) Station Grounding
Outside Fenced Area
The foregoing Exhibit is approved by the parties as of 1989
PLATTE RIVER POWER AUTHORITY CITY OFF MCOLLINS
General Manager Mayor
ATTEST: AT ST:
ATTACHMENT TO EXHIBIT " A "
FENCE AREA OF TIMBERLINE PARK SUBSTATION
( SCALE 1 " = 100' )
NORTH
660'
Cross-hatched area reserved for City
of Fort Collins distribution equipment .
450'
Attachment C
Platte River Power Authority
SERVICE SPECIFICATIONS
(1) Applicability
These service specifications are applicable to the Agreement for
electric service dated March 31, 1980, and covering the supply
and delivery of electric power and energy by Platte River Power
Authority, ("Seller") to
CITY OF FORT COLLINS
COLORADO ("Participant")
(2) Points of Delivery
Seller is obligated to deliver electric power and energy contracted
for by Participant. Such delivery shall be made at the following
points and voltages and subject to the indicated conditions.
Delivery Point Delivery Metering pelivery
Identity and Location Voltage Voltage Conditions
Power Pla t Substation 115 kV 13.8 kV NA
�Sta. 000
orth Col ege Ave.
Drake Substation 115 kV 13.8 kV NA
6Sta. 00
rake Road & C&S Railroad
verland Trail Substation 115 kV 13.8 kV NA
Sta. 4001
verland Trail & Mulberry
Harmonyy S bstation 230 kV 13.8 kV NA
2ta. 500�
armony Road & Union Pacific
Railroad
Richard Lake Substation 115 kV 13.8 kV NA
Rta. 60 )
ast County Rd. 52
Htaen7TOgch Substation 115 kV 13.8 kV NA
Linden Center Drive
(3) Underfrequency Load Interruption
Participant shall at all times be obligated to maintain minimum percentages
of its load subject to interruption during periods of system under-
frequency. Such percentages of load shall be interrupted in successive
steps, subject to relay and circuit breaker time, before the frequency
decreases to the frequency established for each load step, all as specified
in the following table. Such interrupting capability shall be in operation
on Participant' s system on or before the effective date hereinafter specified.
Percent Effective
Step of Load Frequency Date
1. 10 59.0 Hz 1/1/80
2. 20 58.5 Hz 1/1/80
3. 20 58.0 Hz 1/1/80
The foregoing is subject to change in the event obligations of Seller to
provide under-frequency load interruption are changed under production,
pooling or exchange agreements to which Seller is a party.
(4) Cost and Maintenance Responsibility
The Seller and Participant agree to the cost and maintenance respon-
sibilities as shown in the following table. This table shall be updated as
new delivery points or stations are constructed.
FH A
Substation: A, B. C, D,U E,RNISF, G H, I , J B. C D,MA E,INT F, GIN, H, I , J
Power Plant P P P P P P P P P P P P P P P P P P P
Richard Lake P P P P P D D P P P P P P P D D P P P
Harmony P P P P P D D P P P P P P P D D P P P
Overland Trail P P P P P P P P P P P P P P P P P P P
Drake P P P P P P P P P P P P P P P P P P P
Linden Tech P P P P P D D P P P P P P P D D P P P
Timberline(Leased L L L L L L L L L L S P S P S S S S S
Facilities)
Timberline(TransmissiL - S - S - S S S S S S P S P S S S S S
Expansion)
Legend: D - Dual (Seller and Participant each responsible for their own)
L - Lease
P - Participant
S - Seller
Furnish and Maintain Items:
(A) Site Purchase and Ownership (F) Control Building
(B) Grading
gAand Surfacing Within (G) Battery & DC System
Fencedrea
(C) Access Road (H) Station Service
(D) Fence (I) Station Lighting
(E) Landscaping and
dAGrounds (J) Station Grounding
Outside Fencedrea
(5) Approvals
The foregoing Service Specifications are approved by the parties as of
1989 and shall continue in force until changed
by mutual agreement.
FOR SELLER FOE PARTICIP T
General Manager Mayor
ATTEST: Al: