HomeMy WebLinkAbout021 - 02/04/2014 - AMENDING CHAPTER 5, ARTICLE IV OF THE CITY CODE FOR THE PURPOSE OF REPEALING THE 2009 INTERNATIONAL ORDINANCE NO. 021, 2014 OF THE COUNCIL OF THE CITY OF FORT COLLINS AMENDING CHAPTER 5, ARTICLE IV OF THE CODE OF THE CITY OF FORT rCOLLINS FOR THE PURPOSE OF REPEALING THE 2009 INTERNATIONAL MECHANICAL CODE(IMC), AND ADOPTING THE 2012 INTERNATIONAL MECHANICAL CODE, WITH AMENDMENTS WHEREAS, since 1924, the City has reviewed, amended and adopted the latest nationally recognized building standards available for the times; and WHEREAS, upon recommendation of City staff, the City Council has determined that it is in the best interests of the City to align the five interconnected basic construction codes under one publication year; and WHEREAS, the five interconnected basic construction codes are the International Building Code, International Residential Code, International Mechanical Code, International Fuel Gas Code, and International Energy Conservation Code; and WHEREAS, the City Council has determined that the 2012 publication year of the five interconnected basic construction codes ought to be adopted and that their counterpart,codes previously adopted should be repealed, both in order to align the publication years of the codes and also because the 2012 publications contain improvements in construction code regulation; and WHEREAS, City staff has conducted a significant public outreach program, working with the regulated construction industry and building professionals; and WHEREAS, the adoption of the fve interconnected basic construction codes has been presented to and recommended by the Affordable Housing Board, the Commission on Disability, the Air Quality Advisory Board, the Natural Resources Advisory Board, the Building Review Board, the Electric Board, the Landmark Preservation Commission and the Water Board; and WHEREAS, the City Council has determined that it is in the best interest of the health, safety and welfare of the City and its citizens that the 2009 International Mechanical Code, as amended be repealed and that in its place, the 2012 International Mechanical Code be adopted, with amendments. NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF FORT COLLINS as follows: Section 1. That Section 5-106 of the Code of the City of Fort Collins is hereby amended to read as follows: Sec. 5-106. Adoption of standards. Pursuant to the power and authority conferred on the City Council by Section 31-16-202, C.R.S, and Article 11, Section 7 of the Charter, the City Council hereby repeals the 2009 - 1 - International Mechanical Code (2009 IMC) and adopts, as the mechanical code of the City, the 2012 International Mechanical Code, (2012 IMC), published by the International Code Council, which shall have the same force and effect as though set forth in full herein. The subject matter of the 2012 International Mechanical Code, (2012 IMC) , adopted herein includes comprehensive provisions and standards regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance of heating, ventilating, cooling and refrigeration systems, incinerators, miscellaneous heat-producing appliances for the purposes of protecting public health, safety and general welfare. Section 2 . That Section 5 - 107 Code of the City of Fort Collins is hereby repealed and reenacted to read in its entirety as follows : Sec. 5407. Amendments and deletions to code. The 2012 INTERNATIONAL MECHANICAL CODE adopted herein is hereby amended in the following respects : ( 1 ) Section 101. 1 Title is hereby amended to read as follows : " 101 . 1 Title. These regulations shall be known as the Mechanical Code of the City of Fort Collins, hereinafter referred to as "this code. " (2) Section 102. 8 Referenced codes and standards, is amended to read as follows : "Section 102.8 reference codes and standards The codes and standards referenced herein shall be those that are listed in Section 101 .4 of the adopted International Building Code, entitled ` Referenced Codes '_and shall be considered part of the requirements of this code to the prescribed extent of each such reference. " Exception : Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing and the manufacturer' s installation instructions shall apply. (3 ) Section 103 Department of Mechanical Inspection is hereby amended in its entirety to read as follows : "SECTION 103 — CODE ADMINISTRATION 103 . 1 Entity charged with code administration shall be as determined in accordance with Section 103 of the adopted International Building Code, entitled ` Code Administration' . " (4) Section 106. 5 Fees is hereby amended in its entirety to read as follows : "SECTION 106.5 FEES - 2 - 106.5 Payment of fees. All items relating to fees shall be as specified in Section 109 of the adopted International Building Code," entitled `Fees'." (5) Section 107.3 Testing and verification is hereby amended to read as follows: "107.3 Testing and verification. Installed heating, cooling and ventilation systems shall be performance-tested by an approved agency and adjusted to operate within design specifications, in accordance with ANSUACCA QI 5-2010 HVAC Quality Installation Specification. Documentation of results shall be submitted to the building official prior to approval Exception: Buildings subject to commissioning requirements in Section 3604.1 of the 2012 International Building Code as amended." (6) Section 108.4 Violation Penalties, is hereby amended to read as follows: "108.4 Violation penalties. Persons who violate a provision of this code or fail to comply with any of the requirements thereof or who erect, install, alter or repair a mechanical work in violation of the approved construction documents or directive of the code official, or of a permit or certificate issued under the provisions of this code, shall be guilty of a misdemeanor and shall be subject to the penalties and fines specified in Section 1-15 of the City Code." "108.4.1 Work commencing before permit issuance. In addition to the penalties set forth in 108.4, any person or firm who, before obtaining the necessary permit(s), commences any construction of, or work on, a building, structure, electrical, gas, mechanical or plumbing system that is not otherwise exempted from obtaining a permit, shall be subject to a fine in addition to the standard prescribed permit fee. Said fine shall be equal in amount to the permit fee, except that it shall not be less than $50 nor more than $1,000 for the first such violation. A person or firm committing the same such violation repeatedly shall be subject to a fine equal to double the amount of the permit fee or double the amount of the fee imposed for the preceding violation, whichever is greater, for every such subsequent violation committed within 180 days of a previous violation. Said fines may be appealed to the City Manager pursuant to Chapter 2, Article VI of the City Code." (7) Section 109 Means of Appeal is hereby amended in its entirety to read as follows: "109.1 General. Appeals of decisions, determinations and interpretations of this code shall be made pursuant to the applicable provisions of Section 113 of the adopted International Building Code, entitled `Board of Appeals'." (8) Section 202 GENERAL DEFINITIONS, is hereby amended to add the following definitions in alphabetical sequence as follows: "Multifamily. Any building housing group R-1, R-2 or R-4 occupancies. - 3 - Whole-dwelling unit mechanical ventilation system. An exhaust system, supply system, or combination thereof that is designed to mechanically exchange indoor air for outdoor air when operating continuously or through a programmed intermittent schedule to satisfy the whole-dwelling ventilation rate ." (9) Section 304. 3 Elevation of ignition source is hereby amended to read as follows and by deleting the exception: "304.3 Elevation of ignition source. Electrical devices, equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel-dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457 mm) above the floor surface on which the equipment or appliance rests . For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be considered to be part of the private garage. ( 10) Section 312 Heating and Cooling load calculations is hereby amended to read as follows : "312. 1 Heating and cooling load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the adopted International Energy Conservation Code. " ( 11 ) Section 407 Whole-dwelling unit ventilation is hereby added to read as follows : Section 407 WHOLE DWELLING UNIT VENTILATION "407. 1 Whole-dwelling unit mechanical ventilation system . For new buildings, a mechanical exhaust system, supply system, or combination thereof shall be installed for each dwelling unit to provide whole-dwelling unit ventilation. Such system shall comply with Sections 407 . 1 . 1 through 407 . 5 . 407. 1 . 1 Whole-dwelling unit ventilation rate, The dwelling unit mechanical ventilation system shall provide outdoor air at a continuous rate of not less than that determined in accordance with Table M 1507 . 3 . 3 ( 1 ) . Exception . The whole-dwelling unit mechanical ventilation system is permitted to operate intermittently where the system has controls that enable operation for not less than 25 - percent of each 4-hour segment and the ventilation rate prescribed in IRC Table M1507 . 3 . 3 ( 1 ) is multiplied by the factor determined in accordance with IRC Table M1507 . 3 . 3 (2) . - 4 - TABLE M1507.3.3(1) CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS DWELLING UNIT NUMBER OF BEDROOMS FLOOR AREA 0-1 1 2-3 1 4-5 1 6-7 1 >7 (square feed Airflow in CFM < 1,500 30 45 60 75 90 1.501-3,000 45 60 75 90 105 3,001-4,500 60 75 90 105 120 4.501-6,000 75 90 105 120 135 61001-7,500 90 105 120 135 150 >7,500 105 120 135 150 165 For SI: 1 square foot=0-0929 mr,.1 cubic Pont per mute=0.0004719 mrh. TABLE M1507.3.3(2) INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORS" RUN-TAME PERCENTAGE IN EACH 4-HOUR 26% 33% SU% 66% 75% IW% SEGMENT Fant7e 1 4 1 3 1 2 1 1.5 1.3 1.0 a For verru a wn system mu Ilme values between those given,the facmts am Permlded to be determined by mmrPolahon. b. ExtmpolatIm beyond the table Is pmtablted. 407.2 System design. The design of the required whole dwelling unit ventilation system shall comply with the requirements of this Section. System design documents shall be submitted, as required by the building official, at the time of application for a building permit. 407.2.1 System type. The system shall consist of one or more supply or exhaust fans, or a combination thereof, and associated ducts and controls. Exhaust fans shall be permitted to be part of a mechanical exhaust system. Outdoor air ducts connected to the return duct of a forced air furnace shall be considered to provide supply ventilation and shall be sized to provide adequate mechanical ventilation in accordance with ASHRAE 62.2 and shall meet the manufacturer's requirements for minimum return air temperature to the furnace heat exchange. ' , 407.2.2 Outdoor air intakes. Outdoor air intakes shall have automatic dampers that close when the ventilation system is not operating. 407.2.3. Exhausts. Exhausts shall have gravity dampers that close when the ventilation system is not operating. 407.2.4 Air Circulation fan motors. Motors for air circulation fans used in the ventilation system, rated at one-quarter horsepower or greater, shall meet at least one of the following criteria: 1. Where the furnace serves as an air handler for the ventilation system, the furnace shall be certified as an "Electrically Efficient Furnace" by the Air-conditioning, Heating and Refrigeration Institute(AHRI). 2. The blower motor shall be specified as a `Brushless DC" (BL or BLDC) motor by the manufacturer. i - 5 - 3. The blower motor shall be specified as "Brushless Permanent Magnet" (BPM) motor. 4. The blower motor shall be specified as "Electronically Commutated Motor (ECM)". 5. The blower shall meet equivalent criteria acceptable to the building ol cial. 407.2.5 System controls. The mechanical ventilation system shall be provided with readily accessible and labeled controls that enable occupant override. 407.2.6 Sound ratings for fans. Whole-dwelling unit ventilation fans shall be rated for sound at a maximum of 1.5 sones, in accordance with the procedures of the Home Ventilating. Institute (HVI 915, Procedure for Loudness Rating of Residential Fan Products). Exception: Heating, ventilating and air conditioning air handlers and remote-mounted fans need not meet sound requirements. To be considered for this exception, a remote-mounted fan must be mounted outside the habitable spaces, bathrooms, toilets and hallways, and there must be at least 4 ft (1 m) of ductwork between the fan and the intake grille. 407.3 System installation. The installation of the whole-dwelling unit ventilation system and equipment shall be carried out in accordance with the manufacturers' design requirements and installation instructions. 407.4 Performance verification. Performance of installed mechanical ventilation systems shall be verified in accordance with Section 107.3. 407.5 Multifamily buildings. In multifamily buildings, all doors between dwelling units and common hallways shall be gasketed or otherwise substantially airtight with weather stripping, except when the ventilation system explicitly requires transfer of air from corridors into units." (12) Section 504.1 Installation is hereby amended to read as follows and by deleting the exception: "504.1 Installation. Clothes dryers shall be exhausted in accordance with the manufacturer's instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building. Dryer exhaust duct terminations shall not be located within 36 inches (914 mm) of exterior openings into conditioned spaces, crawl spaces, and attic spaces." (13) Section 504.6.4.2 Manufacturer's instructions, is amended by deleting in its entirety: (14) Section 505.2 Makeup air required is hereby amended to read as follows: "505.2 Makeup air required. Exhaust hood systems capable of exhausting in excess of 400 cfm (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to - 6 - the exhaust air rate. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system. Exhaust air rate required shall be calculated based on the total BTU's of the gas appliance beneath the hood at a ratio of 100 BTU's to 1 CFM." (15) Section 512.1 General is hereby amended to read as follows: "512.1 General. When a subslab soil exhaust system is provided, the duct for such system shall conform to the requirements of Section 1211 of the adopted International Building Code, entitled `Radon-Resistant Construction'." (16) Section 602.3 Stud cavity and joist space plenums, is hereby deleted in its entirety: (17) Section 602.3 Building cavities (Mandatory) is hereby added to read as follows: "Section 602.3 Building cavities (Mandatory) Building framing cavities shall not be used as ducts or plenums." (18) Section 602.3.1 Return air is hereby added to read as follows: "Section 602.3.1 Return air. Return air shall be taken from inside the dwelling. Dilution of return air with outdoor air shall be permitted. A return air path shall be provided in all habitable rooms by means of ducts or transfer grills." (19) Section 603.18.3 Construction debris and contamination is hereby added to read as follows: "603.18.3 Construction debris and contamination. Mechanical air-handling systems and their related ducts shall be protected from the entrance of dirt, debris, and dust during the construction and installation process. Prior to passing final inspection or issuance of a Certificate of Occupancy, such systems shall be substantially free of construction-related contaminants." (20) Section 60Z4 Access and identification is hereby amended to read as follows: "607.4. Access and identification Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its.operating parts. The access shall not affect the integrity of fire-resistance- rated assemblies. The access openings shall not reduce the fire-resistance-rating of the assembly. Access points shall be permanently identified on the exterior and readable without the removal of finish ceiling works by a label having letters not less than 0.5 inch (12.7 mm) in height reading: SMOKE DAMPER or FIRE DAMPER. Access doors in ducts shall be tight-fitting and suitable for the required duct construction." (21) Section 801.19 Multi-story prohibited is hereby amended to read as follows: - 7 - "801.19 Multi-story prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited, except engineered systems where all of the appliances served by the common vent are located in rooms or spaces that are accessed only from the outdoors. The appliance enclosures shall not communicate with the occupiable areas of the building." (22) Section 903.1.1 Solid fuel fireplaces and appliances is added to read as follows: "903.1.1 Solid fuel fireplaces and appliances. Solid fuel fireplaces, fireplace stoves and solid-fuel-type room heaters shall also comply with Section 5-110 of the City Code." (23) Section 903.3 Unvented gas logs heaters, is deleted in its entirety: Introduced, considered favorably on first reading, and ordered published this 21st day of January, A.D. 2014, and to be presented for final passage on the 4th day of February, A.D. 2014. [O R T C��C M2 �LP� �.Zf.CJuc eKA�C coC •ybr ATTEST: N SEAL PtORP City Clerk Passed and adopted on final reading on the 4th day of February, A.D. 2014. Ma r ATTEST: G`�y OF FO,4� :moo City Clerk o< ' 'ADO 8 -