HomeMy WebLinkAbout055 - 10/17/1974 - RELATING TO THE REGULATION AND CONTROL OF THE DESIGN, CONSTRUCTION, INSTALLATION, QUALITY OF MATERIA ORDINANCE NO 55 , 1974
BEING AN ORDINANCE RELATING TO THE REGULATION
AND CONTROL OF THE DESIGN, CONSTRUCTION,
INSTALLATION, QUALITY OF MATERIALS, LOCATION,
OPERATION AND MAINTENANCE OF HEATING, VENTILATING,
COOLING, REFRIGERATION SYSTEMS, INCINERATORS,
AND OTHER MISCELLANEOUS HEAT PRODUCING APPLIANCES
IN THE CITY OF FORT COLLINS ADOPTING BY REFERENCE
THERETO THE UNIFORM MECHANICAL CODE, 1973 EDITION
OF THE INTERNATIONAL ASSOCIATION OF PLUMBING AND
MECHANICAL OFFICIALS AND THE INTERNATIONAL CON-
FERENCE OF BUILDING OFFICIALS, REPEALING ALL ORDI-
NANCES IN CONFLICT OR INCONSISTENT HEREWITH AND
PROVIDING A PENALTY FOR VIOLATION OF THE
PROVISIONS OF S4ID MECHANICAL CODE
BE IT ORDAINED BY THE COUNCIL OF THE CITY OF FORT COLLINS
Section 1 Pursuant to the power and authority conferred on the
City Council of the City of Fort Collins by Chapter 139, Article 34, Colorado
Revised Statutes, 1963, as amended, and Article II, Section 7 of the Charter
of the City of Fort Collins, Colorado, there is nereby adopted as the
Mechanical Code of the City of Fort Collins, by reference thereto, the Uniform
Mechanical Code, 1973 Edition, including specifically appendix B thereof, published
by the International Association of Plumbing and Mechanical Officials, 5032 Alhambra
Avenue, Los Angeles, California, 90032, and the International Conference of Buildirg
Officials, 5360 South Workman Mill Road, Whittier, California, 90601, all
to have the same force and effect as though set forth herein in every
particular The subject matter of said Code includes comprehensive
provisions and standards regulating and controlling the design, construction,
installation, quality of materials, location, operation and maintenance
of heating, ventilating, cooling, refrigeration systems, incinerators and
other miscellaneous heat producing appliances for the purpose of protecting
public health, safety and general welfare
Section 2 Said code is hereby amended and changed in the following
respects
a Section 304 is hereby amended by adding thereto additional
subsections 22 and 23 as follows
1122 Reinspection Fee $10 00
a
1123 For each gas piping permit 7 50"
b. An additional Section 307 is hereby added to said code as
follows
"Sec 307 Reinspections A reinspection fee may be
assessed for each inspection or reinspection when a
portion of work for which inspection is called is not
complete or when corrections called for are not made
"This section is not to be interpreted as requiring
reinspection fees the first time a job is rejected
for failure to comply with the requirements of this
Code, but as controlling the practice of calling for
inspections before the job is ready for such inspection
or reinspection
"Reinspection fees may be assessed when the permit
card is not properly posted on the work site, the
approved plans are not readily available to the
inspector, for failure to provide access on the date
for which inspection is requested, or for deviating
from plans requiring the approval of the Building
Official
"To obtain a reinspection the applicant shall file an
application therefor in writing upon a form furnished
for that purpose, and pay the reinspection fee estab-
lished by this ordinance In instances where rein-
spection fees have been assessed no additional in-
spection of the work will be performed until the
required fees have been paid "
c Section 409 is hereby amended by deleting therefrom the definitions
of "Hood", "Hood-Commercial Cooking", and "Hood-Grease"
d Section 706(d) is amended by deleting therefrom the words and
figures "two square inches" and by substituting therefor "one and one-half
square inches"
e All of Chapter 11 of said Code is deleted and the following
is substituted therefor
"CHAPTER 11
"VENTILATION AND EXHAUST SYSTEMS
"SCOPE
"Sec 1101 Every Type III ventilation system which is attached
to or is a part of a building shall conform to the requirements
of this Chapter and applicable standards
"DEFINITIONS
"Sec 1102 For the purpose of this Chapter, the following defini-
tions shall apply
-2-
"HOOD is any air intake device excluding ceiling or wall
louvers and register grills connected to a mechanical
exhaust system
"TYPE I HOOD is a kitchen grease hood
"TYPE II HOOD is a general kitchen hood for collection
of steam, vapor, smoke, heat or odors
"TYPE III HOOD is a ventilation hood for the removal of
flammable vapors, corrosive fumes, dust, stock and refuse
i
"FAN (EXHAUSTER) is a fan used to withdraw air, gas or
solid materials from a space
"DUCTS are a pipe, tube channels or other enclosures used
for the purpose of conveying air, gas, dust, refuse or other
materials
"GENERAL
"Sec 1103 Required ducts shall be designed and installed
so as to provide the required capacity
"Dampers provided to balance air flow in duct systems shall
be securely fixed in position so as to prevent operation of
the damper in such a manner as to restrict the flow of air
through the duct below the required volume or velocity
"Every ventilation system regulated by this Code, and
designed to replace required ventilation, shall be arranged
to discharge into the conditioned space not less than the
amount of outside air specified in the Uniform Building
Code
"A separate and individual system, which shall not be part
of any other system shall be provided for ventilating each
room containing any of the following materials
"1 Noxious gases
2. Flammable vapors
3 Flammable dusts
4 Corrosive vapors (non-flammable)
"Any ventilation use involving materials incompatible with
each other shall have separate ventilation systems for each
of the incompatible materials
"The design of any air moving equipment shall include adequate
consideration of the material to be handled, its physical and
chemical properties and its hazard classification The Fire
-3-
Services may prescribe additional fire suppression systems
for any system conveying hazardous mixtures
"MOTORS, FANS AND FILTERS
"Sec 1104 Motors and fans shall be of sufficient capacity
to provide the required air capture velocities and movement
as specified in applicable standards Electrical equipment
shall be approved for the class of use as provided in the
Electrical Code Every motor and fan shall be so installed as
to afford access for servicing or maintenance
"Fan motors shall not be installed inside the ducts or under
hoods in any ventilation system conveying flammable vapors or
combustible dusts, nor shall any belt or chain-driven apparatus
be inside any such duct or under any such hood unless the
belt or chain and any pulley connection therewith is entirely
enclosed and grounded
"Every fan blade located in any duct shall be of rigid in-
combustible construction
"In any ventilation system conveying flammable vapors or
combustible dusts, the fan blade, shaft and casing shall be
of a non-sparking material Bearings for fans shall be self-
lubricating or shall be lubricated from outside the duct
"Air filters shall be of a type that, in a clean state,
will not burn freely Liquid adhesive coatings used on filters
shall have a flash point of 3500 F , Cleveland open cup tester
or higher
"SAFETY DEVICES
"Sec 1105 Whenever a fire damper is installed, it shall be
constructed and installed to comply with Chapter 43 and U B C
Standard 43-7 (See Appendix A)
"Ducts discharging combustible material directly into any
combustion chamber shall be equipped with a device designed
to prevent fire flashback into other portions of the system
"Where duct gas temperature exceeds 250° F, special protective
measures may be required by the Building Official
"In systems used for the removal of flammable vapor or gases
an approved fixed pipe fire extinguishing system may be
required by the Building Official
"DUCTS
"Sec 1106 (a) General Ducts serving a Type III hood or used
-4-
in a ventilating system shall be substantially airtight
throughout and have no openings other than those required
for proper operation and maintenance of the system Ducts
exposed to the outside atmosphere and subject to corrosion
shall be protected against corrosion in a manner acceptable
to the Building Official Galvanization of metal parts,
protection with noncorrosive paints, and waterproof insula-
tion are considered acceptable methods of protection
i "Metal ducts shall be constructed in accordance with the
ispecifications in tables 10-A and 10-B
"Every duct shall be securely attached to the building as
set forth in Table No 10-E Nails, screws and similar
attachments shall not be driven through the duct walls into
the building construction
"Ducts used for the ventilation of flammable vapors, corrosive
vapors, noxious gases or combustible dusts shall be supported
by incombustible straps or hangers without penetration of
the duct wall
"(b) Materials and Construction
"1 Ducts for noxious gases shall be constructed
of metal as set forth in Table No 10-A or Table No 10-B or
be approved material and construction
112 Ducts for flammable vapors and residue shall
be constructed of metal as set forth in Table No 11-A
TABLE NO 11-A
Up to 8 in. incl No 24 U S Gauge
Over 8 in to 18 in incl No 22 U S Gauge
Over 18 in to 30 in incl No 20 U S Gauge
Over 30 in No 18 U S Gauge
"Ducts used for the ventilation of flammable vapors shall have
all joints and connections made tight by crimping or other
equally effective means, without the use of solder All
sections of such ducts shall be securely joined
113 Ducts for abrasive dusts or solid materials
shall be constructed of metal as set forth in Table No 11-B
-5-
TABLE NO 11-B
Diameter of U S Standard Gaugge for Steel Ductl
Straight Ducts Class I Class II. Class III2
Up to 8" 24 22 20
Over 8" to 18" 22 20 18
Over 18" to 30" 20 18 16
Over 30" 18 16 14
"Class I. Includes nonabrasive applications such as paint spray, wood-
working, pharmaceutical and food products, discharge ducts from dust collectors
"Class II Includes nonabrasive materials in high concentrations (Low
pressure pneumatic conveying) moderately abrasive materials, and highly
abrasive materials in light concentrations Typical examples are conveying
of chemicals and wood dusts, exhaust of foundry shakeouts and sand-handling
systems, grain dusts, coal crushing and screening and grinding, buffing and
polishing
"Class III Includes all highly abrasive materials in moderate to heavy
concentration and moderately abrasive materials in heavy concentrations such
as low pressure conveying of tobacco, exhaust systems from sand and grit
blasting, abrasive cleaning operation, rock and ore screening, crushing
dryers and kilns, fly ash from boiler stacks
"Footnotes to Table 11-B
"1 Where the use of aluminum duct is indicated the B & S gauge
number corresponding to U S Standard gauge steel may be used
as follows
U S Standard
Gauge for Steel 26 24 22 20 18
Brown & Sharpe
Gauge for Aluminum 24 22 20 18 16
112 Elbows, wyes and bends shall be a minimum of two gauge
numbers heavier than straight duct work of the same diameter
except that for 14 gauge and heavier the elbows and ducts may
be the same gauge
"Every duct or plenum which is a portion of a ventilation system
used for exhausting any solid particles shall be constructed so
-6-
as to permit thorough cleaning of the entire duct system
Such duct or plenum, having sections inaccessible from the
duct entry or discharge shall be provided without cleanout
openings
"All cleanout openings shall be equipped with tight-fitting
sliding or hinged doors constructed of metal, equal or greater
in thickness than the ducts Such doors shall be equipped
with a substantial method of latching, sufficient to hold
the door tightly closed These doors shall be so designed
that they can be opened easily without the use of a tool
114 Corrosive Vapors (non-flammable) Duct systems
of plastic material may be used to handle non-flammable cor-
rosive fumes and vapors when convential metal duct systems
will not be adequate
"The system shall be designed with consideration for flame-
spread, minimum fire hazard, heat limitations and applicable
national standards
"Cc) Clearances
"All ducts shall have a minimum clearance of one inch
(111) from any combustible material, except where otherwise
provided
"Ducts used for the ventilation of flammable vapors shall be
located at least twelve inches (1211) from any unprotected com-
bustible materials EXCEPTION Clearance may be reduced to not
less than three inches (311) where the combustible materials are
protected with materials as approved for one-hour fire-resistive
construction on the duct side.
"Duct systems operating at elevated temperatures shall have
clearance from combustible construction as set forth in Table
No 11-C
TABLE NO 11-C
Clearance from Combustibles for Ducts
Operating at Elevated Temperatures
Duct Gas Temperature Largest Duct Dimension Clearance*
(In Inches) (In Inches)
Up to 600° F incl 8 8
over 8 12
Over 600' F -900° F incl 8 18
over 8 24
Over 9000 F Lined with
refractories
*Clearance may be reduced in accordance with Table No S-B
-7-
"(d) Exhaust Outlets
"Exhaust outlets for ducts that convey noxious gases,
flammable vapors or corrosive vapors shall terminate outside of
the building and at least ten feet (101) from any adjacent
building, adjacent property line, or air intake opening into
any building, and shall be located at least ten feet (101)
above the adjoining grade level Every such exhaust outlet
which is located above the roof shall extend at least two feet
i
(21) above the roof surface
"TYPE II - EXHAUST HOODS
"Section 1107 (a) Make Up Air Provisions shall be made for
air to enter the room in which the hood is located at a rate not
less than that at which the room air is exhausted by the hood
"(b) Tempered Air Hood and duct systems
exhausting more than 2,500 cfm shall be provided with tempered
make up air For this purpose tempered air means air heated
to at least 600 F at the inlet diffuser to the room or area
in which the hood is located
"Cc) Material and Installation All Type III
hoods shall comply with the following requirements
"1 Every hood shall be constructed of
galvanized steel, stainless steel, copper, or other material
approved for the use intended Hoods constructed of galvanized
steel shall be not less than No 18 Manufacturers Standard
Gauge Hoods of stainless steel shall have an equivalent
thickness of not less than 0 030 inch Hoods constructed of
copper shall be of copper sheets weighing not less than 24
ounces per square foot
112 Every hood shall be securely fastened
in place by incombustible supports
113 Every joint and seam shall be sub-
stantially tight No solder shall be used, except for sealing
a joint or seam
r
114 Every hood shall be so designed and
installed to provide for thorough cleaning
115 Every portion of a hood shall have
clearance from combustible construction of not less than eighteen
inches C1811) This clearance may be reduced to not less than
three inches (311) provided the combustible material is protected
with materials as specified for one-hour construction.
"(d) Special Requirements for Type III Canopy
Style Hoods Canopy Style hoods shall comply with the following
-8-
requirements in addition to all other requirements for hoods
specified in this Chapter
"1 The inside edge of the hood shall
overhang or extend beyond the edge of the equipment surface
112 The hood ventilation system shall
exhaust through the hood a minimum quantity of air as determined
by the Building Official or applicable standards
"(e) Exhaust Air for Noncanopy Type Hoods
In addition to all other requirements for hoods specified in
this Chapter, the volume of air exhausting through a noncanopy
type hood to the duct system shall be not less than 300 cubic
feet per minute per lineal foot of equipment, unless otherwise
approved by the Building Official "
f Said Code is amended by adding thereto a new Chapter 20 as
follows
"CHAPTER 20
"COMMERCIAL HOODS AND KITCHEN VENTILATION
"DEFINITIONS
"Sec 2001 For the purpose of this Chapter the following
definitions shall apply
"COMMERCIAL FOOD HEAT-PROCESSING EQUIPMENT is equipment used
in a food establishment for heat-processing food or utensils
and which produces steam, vapors, smoke or odors which are
required to be removed through a local exhaust ventilation
system
"GREASE COLLECTOR is a device other than a filter used to
remove grease and other contaminants from the air before it
enters the duct system
"GREASE FILTER is a device used to capture by entrapment,
impingement, adhesion, or similar means, grease and similar
contaminants before they enter a duct system
"HOOD is any air intake device connected to a mechanical
exhaust system for collecting grease vapors, fumes, smoke,
steam, heat or odors from commercial food heat-processing
equipment
"TYPE I is a kitchen grease hood
"TYPE II is a general kitchen hood for collection of steam,
vapor, smoke, heat or odors
-9-
"KITCHEN VENTILATION SYSTEMS
"Sec 2002 (a) Materials Ducts and plenums, serving a
Type I hood, having an area of 4 square feet or less shall
be constructed of not less than No 16 Manufacturers Standard
Gauge steel, and ducts and plenums having an area greater than
4 square feet shall be constructed of not less than No 14
Manufacturers Standard Gage steel
i
"All joints and seams, except the vibration isolation connector,
i shall be made with a continuous grease tight weld or braze
made on the external surface of the duct system Vibration
isolution connector shall not be used unless it consists of
a metal sleeve joint packed with asbestos rope and its design
is acceptable to the Building Official
"Ducts and plenums serving Type II hoods shall be constructed
as set forth in Tables Nos 10-A, 10-B and 10-E
"Ducts exposed to the outside atmosphere and subject to
corrosion shall be protected in a manner acceptable to the
Building Official against such corrosion Galvanization of
metal parts, protection by noncorrosive paints, and waterproof
insulation are considered acceptable methods of protection
"(b) Prevention of Grease Accumulation Duct
systems serving a Type I hood shall be so constructed and
installed that grease cannot become pocketed in any portion
thereof, and the system shall slope not less than 1/4 inch
per lineal foot toward the hood or toward an approved grease
reservoir Where ducts exceed 75 feet in length the slope
shall be not less than one inch per lineal foot When a cen-
trifugal fan is used it shall be positioned so the discharge
outlet is in a bottom horizontal position and the air shall be
so diverted that there will be no impingement on the roof, other
equipment or parts of the structure
"(c) Cleanouts and Other Openings Duct systems
shall not have openings therein, other than those required for
proper operation and maintenance of the system Any portion of
such system having sections inaccessible from the duct entry or
discharge shall be provided with adequate cleanout openings
Cleanout openings shall be equipped with tight-fitting doors,
constructed of steel which is equal to or greater in thickness
than the ducts, and such doors shall be equipped with a sub-
stantial method of latching, sufficient to hold the door
tightly closed These doors shall be so designed that they can
be opened without the use of a tool
"(d) Duct Enclosure Ducts serving a Type I hood
which penetrates a ceiling, wall or floor shall be enclosed from
-10-
the point of penetration to the outside air as required for
vertical openings in the Building Code The shaft or enclosure
shall be separated from the duct by a minimum of 3 inches and
a maximum of 12 inches and this area shall be ventilated to
the outside air Such enclosure shall be used exclusively to
enclose a single grease exhaust duct system
"(e) Fire-resistive Access Opening Where cleanout
openings are located in ducts within a fire-resistive shaft or
enclosure, access openings shall be provided in the shaft or
enclosure at each cleanout point These access openings shall
be equipped with tight-fitting sliding or hinged doors which
are equal in fire-resistive protection to that of the shaft or
enclosure
"(f) Air Velocity Ducts systems service a Type I
hood shall be designed and installed in a manner to provide an
air velocity within the duct system of not less than 1500 feet
per minute and not to exceed 2,500 feet per minute
"(g) Separation of Duct Systems A separate duct
system shall be provided for each Type I hood, except that a
single duct system may serve more than one hood located in the
same story of the building provided that all hoods served by
the system shall be located in the same room or adjoining rooms,
portion of the interconnecting ducts shall not pass through any
construction which would require the opening to be fire protected
as specified in the Building Code
"(h) Clearances Duct systems serving a Type I
hood shall have a clearance from combustible construction of
not less than 18 inches This clearance may be reduced to not
less than 3 inches provided the combustible material is protected
with materials as approved by the Building Official for one-
hour resistive construction on the duct side
"(i) Electrical Motors, fans, and exhaust outlets
for grease hood duct systems shall comply with all applicable
requirements as specified in the Electrical Code
"(j) Exhaust Outlets Exhaust outlets for ducts
serving commercial food heat-processing equipment Type I hoods
shall extend through the roof unless otherwise approved by the
Building Official Such extension shall be at least 2 feet above
the roof surface, at least 10 feet from any adjacent building,
adjacent property line, or air intake opening into any building,
and shall be located at least 10 feet beyond the adjoining grade
"Exhaust outlets for ducts serving commercial food heat-processing
equipment, Type II hoods, shall terminate not less than 5 feet
from any adjacent building, adjacent property line or air intake
opening into a building if the air from the exhaust outlet is
discharged away from such location
-11-
"EXCEPTION Upon approval of the Building Official, the
exhaust from any hood serving commercial food heat-processing
equipment may terminate in a properly engineered air recovery
system for recirculation to the room in which the hood is
located
"(k) Fuel-burning Appliances When vented fuel-
burning appliances are located in the same room or space as the
hood, the vent shall be arranged to prevent the hood system
from interfering with normal operation of the appliance vent
"HOOD
"Sec 2003 (a) Where Required Hoods shall be installed at
or above all commercial type deep fat fryers, broilers, fry
grills, steam-jacketed kettles, hot-top ranges, ovens, barbecues,
rotisseries, dishwashing machines, and similar equipment which
produce comparable amounts of steam, smoke, grease or heat in
a food processing establishment For the purpose of this Section
a food processing establishment shall include any building or
portion thereof used for the processing of food but shall not
include a dwelling unit
"(b) Materials and Installation Every Type I or
II hood shall be constructed of galvanized steel, stainless steel,
co per or other material approved by the Building Official for
the use intended Type I hoods constructed of galvanized steel
shall be of not less than No 18 Manufacturers Standard gauge
Type II hoods used for the capture of steam, vapor, smoke, heat
or odors shall be constructed of not less than No 24 Manufacturers
Standard Gauge steel All hoods constructed of copper shall be
of copper sheets weighing not less than 24 ounces per square
foot All hoods constructed of stainless steel shall have an
equivalent thickness of not less than 0 030 inch
"Every hood shall be securely fastened in place by noncombustible
supports
"(c) Cleaning and Grease Gutters Every hood shall
be so designed when installed to provide for thorough cleaning
of the entire hood When grease gutters are provided, they shall
drain to a collecting receptacle, fabricated, designed, and
installed to be accessible for cleaning
"(d) Clearances Every portion of a Type I hood
shall have clearance from combustible construction of not less
than 18 inches This clearance may be reduced to not less than
3 inches provided the combustible material is protected with
materials as specified for one-hour fire-resistive construction
on the hood side Hoods less than 12 inches from the ceiling
or wall shall be flashed solid with approved metal
-12-
"(e) Grease Filters Type I hoods shall be equipped
with approved grease filters or grease extractors designed for
the specific purpose All grease collecting equipment shall be
accessible for cleaning The height of the lowest edge of a
grease filter located above the cooking surface shall be not
less than that set forth in Table No 20-A
"Filters and grease extractors shall be of such size, type and
i arrangement as will permit the required quantity of air to pass
through such units at rates not exceeding those for which the
filter or unit was designed or approved Filter units shall be
installed in frames or holders with handles by which they may
be readily removed without the use of tools, unless designed and
installed to be cleaned in place and the system is equipped for
such cleaning-in-place They shall be sized and made removable
so they may be passed through a dishwashing machine or cleaned
in a pot sink and so arranged in place or so provided with drip
intercepting devices as to avoid grease or other condensate
from dripping into food or on food preparation surfaces
"(f) Canopy Size and Location For canopy type
commercial cooking hoods the inside edge thereof shall overhang
or extend a horizontal distance of not less than 6 inches beyond
the edge of the cooking surface on all open sides and the vertical
distance between the lip of the hood and the cooking surface shall
be not more than 4 feet
"EXCEPTION Listed grease extractors are to be
installed in accordance with the terms of their listing and the
manufacturer's instructions
"(g) Capacity of Hoods For canopy-type commercial
cooking hoods the ventilation system shall exhaust through the
hood a minimum quantity of air as determined by either of the
following formulas
"NUMBER OF EXPOSED SIDES FORMULA
114 (central hood) Q = 150 A
3 or less Q = 100 A
Formula Alternate Q = 50 PD
"WHERE
"A = The horizontal surface of the hood in square feet
"P = That part of the perimeter of the hood that is
open, in feet
"D = Distance, in feet, between the lower lip of
the hood and the cooking surface
-13-
"Q = Cubic feet per minute
"EXCEPTION Listed grease extractors are to be
installed in accordance with the terms of their listing and the
manufacturer's instructions
"(h) Velocity for Non-canopy Hoods In addition to
all other requirements for hoods specified in this Section, the
volume of air exhausting through a non-canopy type hood to the
duct system shall be not less than 300 cubic feet per minute per
lineal foot of cooking equipment Listed grease extractors are
to be installed in accordance with the terms of their listing
and the manufacturer's instructions In no case shall the
velocity of air at the cooking surface be less than 30 feet per
minute,
"(i) Makeup Air Each room provided with an exhaust
system shall have air supplied to the room equal to the amount
of air to be exhausted Makeup diffusers shall be located to
prevent a short-circuiting of air furnished to the exhaust system
Windows shall not be used for the purpose of providing makeup
air The exhaust and makeup air systems shall be connected by
an electrical interlocking switch
"MOTORS, FANS, SAFETY DEVICES AND TEMPERED AIR
"Sec 2004 (a) General Motors and fans shall be of sufficient
capacity to provide the required air movement as specified in
this Chapter Electrical equipment shall be approved for the
class of use as provided in the Electrical Code Every motor
and fan shall be so installed as to afford access for servicing
or maintenance Motors shall not be installed within ducts or
under hoods
"(b) Fire Extinguishers Approved automatic fire-
extinguishing systems shall be provided for the protection of duct
systems, grease removal devices, and hoods Cooking equipment
which may be a source of ignition of grease in the hood, grease
removal device, or duct (such as fat fryers, ranges, griddles
and broilers) , shall also be protected by approved estinguishing
equipment If acceptable to the Building Official that portion
of the fire-extinguishing system required for protection of the
duct may be omitted when all cooking equipment is served by
listed grease extractors The extinguishing equipment shall
include both of the following types
"1 Automatically operated fixed pipe systems,
or other automatic systems specifically listed for the hazard
Listed fire-extinguishing systems shall be installed in accord-
ance with the terms of their listing and the manufacturer's
instructions Other fire-extinguishing equipment shall be
installed in compliance with the applicable standards
-14-
112 Approved portable inert gas or dry chemical
extinguishers
"(c) Fire Dampers Fire dampers shall not be
installed in duct systems unless they are listed for such use or
are part of a listed grease extractor, fire-extinguishing
system, or an approved fan bypass
"(d) Tempered Air Kitchens with exhaust systems
in excess of 2500 c f m shall be provided with tempered makeup
air For this purpose, tempered air means a temperature of not
less than 600 Fahrenheit at the discharge diffuser in the room
I
"EXCEPTION Kitchen ventilation systems which
furnish their own makeup air independent of the air furnished
to the kitchen or other areas of the building are excluded
TABLE NO 20-A
MINIMUM DISTANCE BETWEEN THE LOWEST EDGE
OF A GREASE FILTER AND THE COOKING SURFACE
OR THE HEATING SURFACE
Duct System and Hood with
Fire-Extinguishing System
(In Feet)
No exposed Flame Grilles, French Fryers, Etc 2
Exposed Flame and Burners 2
Exposed Charcoal and Charbroil Type Fires 3-1/2
It
g Section 2211 is amended by adding a new subsection g thereto
as follows
"(g) Single gas meter locations shall be fifteen inches (1511)
plus or minus one inch (111) to the right or left of the supply
riser Multiple gas meters shall be located eighteen inches
(1811) plus or minus one inch (111) right or left of the supply
riser and spaced twenty-four inches (2411) vertically "
h Section 2213 (g) is amended by deleting therefrom the first
sentence thereof
1 Section 2213 (j) is amended to read as follows
"(j) Fireplace outlets All gas outlets located in a
barbecue or fireplace shall be controlled by an approved
-15- '
operating valve located in the same room and outside
the hearth but not more than four feet from such outlets
Wind piping on the discharge side of any such control
valve is standard weight brass, such piping shall be in
a steel sleeve which may be imbedded in or surrounded by
not less than two inches (211) on concrete or masonry "
j Section 2214 is amended by deleting therefrom Exception
numbered 5
k Section 2215 is amended by changing subparagraph 6 thereof
to read as follows
116 Liquefied petroleum gas piping shall not serve any
furnace, gas water heater, or other fuel burning appliance
located in a pit or basement where heavier than air gas
might collect to form a flammable or explosive mixture "
1 Section 2218 (a) is amended to read as follows
"(a) General Gas piping shall comply with the provisions
of this section and section 2219 All natural gas regulations
and tables except Table 22D are based on the use of a gas
having a specific gravity of 0 65, supplied at 6-8 inches
water column pressure at the outlet of the meter Table
22D is based on the use of natural gas having a specific
gravity of 0 68 and 6 inch water column as supplied in the
Fort Collins area For undiluted liquefied petroleum gas,
gas piping may be sized for 2,500 BTU's per cubic foot at
11 inches water column and specific gravity of 1 52 "
m Table 22-D entitled Size of Gas Piping is deleted and the
following table substituted therefor
-16-
IV " F-
rri ti7 F F h- W F- Ci I
\ \ \ \ \ W -4 r--I
f N N J` N N
l o �
N wrF- ON� oANrl
t N 11 00 O O rn w NJ F� I C
Ln ON
a Oo 000 �9. N
C C C C C O O a
N rt tD
m <
n
w 01N V "O CN W N F- V W In F-' 0 0 C, W F- CJ N
r cr oln "O wF- o ov, cov, o n
ON M
OGO00 oAsrn - GG0000O �c� '" w
r - b
w
O r
C0) w~ oN � � Ni C-) w `C
W 0n %.O In W N V, In 00 In N F--' �l r`Ell F- O C N 00 G O \,O In N Ul k-n t-n A s A
a £ O C 0 0 0 CD A N A 0 0 0 G O O O W
O n a'
rt m F+
to FJ N V W N F+ n
V m In C7 M
m O 00 00 W N F fD
O In In In N v W N (D
Fn+. C) C C O N rt
M n
W m O
n rA FA
N
rwt ON wphi
C `C V' Gi to
w .
G rJ � � Nrn n
� Nr-r o to
F� M In C C C W F--i CD C O 'd
rt C) ooG000000 - a �
O �
tr
O n z ON b
rn a ON w
00 1-6 w h o H w x
0000 `� o °�° � r
rn o r
h V M 0 -
t"� Fj F I O
m n
Ot o N F--' ' to b fN
O 00 00 tD In W F-+ ' C
M In In O �O W
O C O G G 0 0 0 'C1
M CL r
r7 O CD
rr V
Opp O In N C.
Ln iJ In W F+
In In O W J W C, co N-
0 0 C C O C O In O
OQ
03
rt
n C
O In N F- kD
O In O :A CN O Ul V - OO
.7000GOF- O Rt
O
M
O
InLn N I
F✓ 00
G CA W w 00 A N
O Vt G N W � V fA
JG :: 000 F- 4- '[7
fD
n
w
M
µ
n
C% n 00
o N F- Ln
N w
O
N O f J V W N F+ F<+
0 GIO�O O�C N OD t `<
Section 3 Definitions
a Wherever the word "municipality" or "city" is used in the
Uniform Mechanical Code, it shall be held to mean the City of Fort Collins
b Wherever the word "building official" is used in the
Uniform Mechanical Code, the term shall be held to mean the City Building
Inspector, which term shall be synonymous with the Chief Building Inspector
and shall include all his designated representatives
Section 4 Penalty Clause The following sections of the
Uniform Mechnnical Code contain a penalty clause which is herewith set
forth in full as required by Chapter 139, Article 34, Section 4 of the
Colorado Revised Statutes, 1963, as amended, and Article II, Section 7
of the Charter of the City of Fort Collins, to-wit
"Sec 202 It shall be unlawful for any person, firm, or
corporation to erect, install, alter, repair, relocate, add
to, replace, use or maintain heating, ventilating, cooling,
or refrigeration equipment in the jurisdiction, or cause the
same to be done, contrary to or in violation of any of the
provisions of this Code Maintenance of equipment which was
unlawful at the time it was installed and which would be
unlawful under this Code if installed after the effective
date of this Code, shall constitute a continuing violation
of this Code
"Any person, firm or corporation violating any of the
provisions of this Code shall be deemed guilty of a misdemeanor,
and each such person shall be deemed guilty of a separate
offense for each and every day or portion thereof during
which any violation of any of the provisions of this Code
is committed, continued, or permitted, and upon conviction
of any such violation such person shall be punishable by a
fine of not more than $500 00, or by imprisonment for not more
than six months, or by both such fine and imprisonment "
Section 5 A public hearing on the adoption, by reference thereto
of the Uniform Mechanical Code, 1973 Edition, Volume 1, of the International
Association of Plumbing and Mechanical Officials and the International
Conference of Building Officials be, and the same hereby is, scheduled
in the Council Chambers, City Hall, 300 LaPorte Avenue, Fort Collins,
Colorado, at 5 30 o'clock P M on the 17th day of October, A D 1974,
and the City Clerk is hereby directed to publish notice of said public
meeting in the manner and style pursuant to the requirements of Chapter 139,
Article 34, Section 3, Colorado Revised Statutes, 1963, as amended, and
Article II, Section 7 of the Charter of the City of Fort Collins
Section 6 At least three copies of the Uniform Mechanical Code,
1973 Edition, shall be on file in the office of the City Clerk of the City
of Fort Collins, Colorado, at least fifteen (15) days preceding the date
set herein and may be inspected by any interested persons during normal
-17-
business hours After the public hearing thereon and final reading and
adoption by reference, the Mechanical Code as finally adopted shall be
available for sale to the public through the office of the City Clerk
at a price not to exceed the City's actual costs
Section 7 If any part, section, subsection, sentence, clause
or phrase of this ordinance or of the Mechanical Code adopted hereby is
for any reason held to be invalid, such decision shall not affect the
validity of the remaining sections of this ordinance or of said Mechanical
Code, and the City Council hereby declares that it would have passed this
ordinance and adopted said Mechanical Code in each part, section, subsection,
sentence, clause or phrase thereof irrespective of the fact that any one
or more parts, sections, subsections, sentences, clauses or phrases be
declared invalid
Section 8 All ordinances or parts of ordinances in conflict
herewith are hereby repealed, including specifically the following
Section 56-1, 56-2, 56-3A, 56-3B, 56-4 through 56-28, inclusive, and
Section 62-1 and 62-5, of the Code of the City of Fort Collins, provided,
however, that the repeal of said ordinance shall not revive any other
section of any ordinance or ordinances heretofore repealed or superseded
and provided further that such repeal shall not make lawful any violation
of the ordinances hereby repealed and provided further that construction
under any building permit heretofore taken out under the ordinance herein
repealed may be continued in conformance with such repealed ordinance
or if the owner thereof elects in conformance with the ordinance herein
enacted
Introduced, considered favorably on first reading and ordered
published this 19th day of September, A D 1974, and to be presented for
final passage on the 17th day of October, A D 1974
ATTEST
C3.t5r C erk
Passed and adopted on final reading this 17th day of October,
A.D 1974
ATTEST May
Ci y Clark
I
-18-