HomeMy WebLinkAbout172 - 12/04/1984 - AMENDING PORTIONS OF CHAPTER 50 OF THE CITY CODE RELATING TO THE UNIFORM FIRE CODE ORDINANCE NO. 172, 1984
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING PORTIONS OF CHAPTER 50 OF THE CODE
OF "rHE CITY OF FORT COLLINS RELATING TO THE UNIFORM
FIRE CODE
BE IT ORDAINED BY THE COUNCIL OF THE CITY OF FORT COLLINS:
Section 1. The following sections of Chapter 50 of the Code of the
City of Fort Collins are hereby amended as follows:
Section 50-2 is amended by adding the following subsection:
(35) Appendix VII is added as follows:
APPENDIX VII
LIFE SAFETY REQUIREMENTS FOR
EXISTING HIGH-RISE BUILDINGS
SECTION 101. SCOPE
These provisions appply to existing high-rise buildings constructed prior
to the adoption of this appendix and which house Group B, Division 2
offices or Group R, Division 1 Occupancies, each having floors used for
human occupancy located more than 75 feet above the lowest level of fire
department vehicle access.
SECTION 102. GENERAL
Existing high-rise buildings as specified in Section 101, above, shall be
modified to conform with not less than the minimum provisions specified in
Table No. 1-A and as enumerated within this appendix.
The provisions of this appendix shall not be construed to allow the
elimination of fire protection systems or a reduction in the level of fire
safety provided in buildings constructed in conformance with previously
adopted codes.
SECTION 103. COMPLIANCE DATA
After adoption of this appendix, the fire marshal shall duly notify the
owners whose buildings are subject to the provisions of this appendix.
Upon receipt of such notice, the owner shall , subject to the following time
limits , take necessary actions to comply with the provisions of this
appendix.
Plans and specifications for the necessary alterations shall be filed
with the fire marshal within 18 months after the date of owner notifica-
1
tion. Work on the required alterations to the building shall commence
within 30 months of the date of owner notification and such work shall be
completed within five years from the date of owner notification.
The fire marshal shall grant necessary extensions of time when it can
be shown that the specified time periods are not physically practical or
pose an undue hardship. The granting of an extension of time for com-
pliance shall be based upon the showing of good cause and subject to the
filing of an acceptable systematic progressive plan of correction with the
fire marshal .
SECTION 104. AUTHORITY OF THE FIRE MARSHAL
For the purpose of applying the provisions of this appendix, the fire
marshal shall have the authority to consider alternative approaches and
grant necessary deviations from this appendix as follows:
A. Allow alternate materials or methods of compliance if such alter-
nate materials or methods of compliance will provide levels of
fire and life safety equal to or greater than those specifically
set forth in this appendix.
B . Waive specific individual requirements if it can be shown that
such requirements are not physically possible or practical and
that a practical alternative cannot be provided.
SECTION 105. APPEALS BOARD
Appeals of the determinations of the fire marshal in applying the pro-
visions of this code may be made by an appeal directed to the Board of
Appeals as established by Section 2.302 of this code.
SECTION 106. SPECIFIC PROVISIONS AND ALTERNATES
(a) Specific Provisions . The following provisions shall apply when
required by Table No. 1-A.
1. Type of construction. Buildings classified in the Uniform Buil -
ding Code as Type II-N, III-N or V-N construction shall be equipped with an
approved automatic sprinkler system installed in accordance with U.B.C.
Standard No. 38-1.
EXCEPTION: Installation of meters or backflow preventers for the
connection to the water works system need not be provided unless
required by other regulations of the authority having jurisdiction.
2. Fire department communication system. When it is determined by
test that the portable fire department communication equipment is ineffec-
tive, a communication system acceptable to the fire department shall be
installed within the existing high-rise building to permit emergency
communication between fire-suppression personnel .
-2-
3. Single-station smoke detectors. Single-station smoke detectors
conforming to U.B.C. Standard No. 43-6, Part II, shall be installed within
all dwelling units or guest rooms in accordance with the manufacturer' s
installation instructions . In dwelling units , the detector shall be
mounted on the ceiling or wall at a point centrally located in the corridor
or area giving access to each separate sleeping area. When sleeping rooms
are located on an upper level , the detector shall be installed at the
center of the ceiling directly above the stairway within the unit. In
efficiency dwelling units , hotel suites and in hotel guest rooms, detectors
shall be located on the ceiling or wall of the main room or hotel sleeping
room. When actuated, the detector shall provide an audible alarm in the
sleeping area of the dwelling unit, hotel suite or guest room in which it
is located .
Such detectors may be battery operated.
4. Manual fire alarm system. An approved manual fire alarm system
connnected to a central , proprietary or remote station service, or an
approved manual fire alarm system which will provide an audible signal at a
constantly attended location, shall be provided. Such system shall include
a graphic annunciator panel in the main lobby or other location approved by
the fire department.
5. Occupant voice notification system. An approved occupant voice
notification system shall be provided. Such system shall provide communi -
cation from a location acceptable to the fire department and shall permit
voice notification to at least all normally occupied areas of the building.
The occupant voice notification system may be combined with a fire
alarm system, provided the combined system has been approved and listed for
such use. The sounding of a fire alarm signal in any given area or floor
shall not prohibit voice communication to other areas or floors. Combi -
nation systems shall be designed to permit voice transmission to override
the fire alarm signal , but the fire alarm shall not terminate in less than
3 minutes .
6. Vertical shaft enclosures. Openings through two or more floors
except mezzanine floors, which contain a stairway or elevator, shall be
provided with vertical shaft enclosure protection as specified herein.
Such floor openings, when not enclosed by existing shaft enclosure con-
struction , shall be protected by one-hour fire-resistive-rated shaft
enclosure construction. For floor openings which are enclosed by existing
shaft enclosure construction having fire-resistive capabilities similar to
wood lath and plaster in good condition, 1/2-inch gypsum wallboard or
approved 1/4-inch-thick wired glass is acceptable. Wired glass set in a
steel frame may be installed in existing shaft enclosure walls but shall be
rendered inoperative and be fixed in a closed position.
-3-
Openings through two or more floors for other than stairways or elevators,
such as openings provided for piping, ducts, gas vents , dumbwaiters, and
rubbish and linen chutes, shall be provided with vertical shaft enclosure
protection as specified for stairways and elevators.
EXCEPTIONS: Openings for piping, ducts, gas vents , dumbwaiters and
rubbish and linen chutes of copper or ferrous construction are per-
mitted without a shaft enclosure, provided the floor openings are
effectively fire-stopped at each floor level .
7. Shaft enclosure opening protection. Openings other than those
P 9 P .
provided for elevator doors in new vertical shaft enclosures constructed of
one-hour fire-resistive construction shall be equipped with approved fire
assemblies having a fire-protection rating of not less than one hour.
Openings other than those provided for elevator doors in existing vertical
shaft enclosures shall be equipped with approved 20-minute-rated fire
assemblies , 1 3/4-inch solid wood doors or the equivalent thereto .
Doors shall be either self-closing or automatic closing and automatic
latching.
8. Manual shutoff of HVAC systems. Heating, ventilating and air
conditioning systems shall be equipped with manual shutoff controls in-
stalled at an approved location when required by the fire department.
9. Automatic elevator recall system. Elevators shall be equipped
with an approved automatic recall system as required by Section 1807(h)2 of
the Uniform Building Code.
10. Unlocked stairway doors . Exit doors into exit stairway enclosures
shall be maintained unlocked from the stairway side on at least every
fifth floor level . All unlocked doors shall bear a sign stating ACCESS
ONTO FLOOR THIS LEVEL.
Stairway doors may be locked, subject to the following conditions:
A. Stairway doors which are to be locked from the stairway side shall
have the capability of being unlocked simultaneously without
unlatching upon a signal from an approved location.
B. A telephone or other two-way communications system connected to an
approved emergency service which operates continuously shall be
provided at not less than every fifth floor in each required
stairway.
11. Stair shaft ventilation. Stair shaft enclosures which extend to
the roof shall be provided with an approved manually openable hatch to the
exterior having an area not less than 16 square feet with a minimum dimen-
sion of 2 feet.
-4-
}
EXCEPTIONS: 1. Stair shaft enclosures complying with the require-
ments for smokeproof enclosures .
2. Stair shaft enclosures pressurized as required for mechanically
operated smokeproof enclosures to a minimum of 0.15- and a maximum of
0.50-inch water column.
12. Elevator shaft ventilation. Elevator shaft enclosures which
extend to the roof shall be vented to the outside with vents whose area
shall be not less than 3 1/2 percent of the area of the elevator shaft ,
with a minimum of 3 square feet per elevator.
EXCEPTION: Where energy conservation or hoistway pressurization
requires that the vents be normally closed, automatic venting by
actuation of an elevator lobby detector or power failure may be
accepted.
13. Posting of elevators . A permanent sign shall be installed
in each elevator cab adjacent to the floor status indicator and at each
elevator call station on each floor reading IN FIRE EMERGENCY, DO NOT USE
ELEVATOR -- USE EXIT STAIRS, or similar verbiage approved by the fire
marshal .
EXCEPTION: Sign may be omitted at the main entrance-floor level call
station.
14. Exits . A. General . Every floor from an existing high-rise
building shall have access to two separate means of egress, one of which
may be an existing exterior fire escape or an exterior stairway not less
than 30 inches in clear width. The stairway may be constructed with an
8-inch maximum rise and 9-inch minimum run, provided the greatest riser
height and largest tread run do not exceed the smallest by more than
3/8-inch . The adequacy of fire escapes shall be demonstrated to the
satisfacton of the fire marshal .
B . Fire escapes . Access to fire escapes may be any one of the
following :
(i ) Through a room between the corridor and the fire escape if the
door to the room is operable from the corridor side without the
use of any key, special knowledge or effort.
(ii ) By a door to a fire escape operable from the interior without the
use of any key, special knowledge or effort.
(iii ) By a window operable from the interior. Such window shall have a
minimum net clear dimension of 29 inches when open. The sill
shall be not more than 30 inches above the floor and landing.
-5-
C. Protection of exterior openings . When a fire escape is accepted
as one of the required means of egress, openings onto the fire escape
landing and openings within 10 feet horizontally of the landing shall be
protected in a manner acceptable to the fire marshal .
15. Exit corridor construction . Corridors serving as an exit for an
occupant load of 30 or more shall have walls and ceilings of not less than
one-hour fire-resistive construction as required by the Uniform Building
Code. Existing walls may be surfaced with wood lath and plaster in good
condition or 1/2-inch gypsum wallboard for corridor walls and ceilings and
occupancy separations when approved.
16. Exit corridor openings. Openings in corridor walls and ceilings
shall be protected by not less than 1 3/8-inch solid-bonded wood-core
doors , approved 1/4-inch-thick wired glass, approved fire dampers con-
forming to U.B.C. Standard No. 43-7, or by equivalent protection in lieu of
any of these items . Transoms shall be fixed closed and covered with
1/2-inch Type X gypsum wallboard or equivalent material installed on both
sides of the opening.
17. Exit corridor door closers. Exit doors into corridors shall be
equipped with self-closing devices or shall be automatic closing by actu-
ation of a smoke detector. When spring hinges are used as the closing
device, not less than two such hinges shall be installed on each door leaf.
18. Exit corridor dead ends . The length of dead end corridors serving
an occupant load of more than 30 shall not exceed 20 feet .
19. Interior finish. The interior finish in exit corridors, exit
stairways and extensions thereof shall conform to the provisions of Chapter
42 of the Uniform Building Code.
20. Exit stairway illumination. When the building is occupied, exit
stairways shall be illuminated with lights having an intensity of not less
than 1 footcandle at the floor level . Such lighting shall be equipped with
an independent alternate source of power such as a battery pack or on-site
generator.
21. Exit corridor illumination. When the building is occupied, exit
corridors shall be illuminated with lights having an intensity of not less
than 1 footcandle at the floor level . Such lighting shall be equipped with
an independent alternate source of power such as a battery pack or on-site
generator.
22. Exit stairway exit signs. The location of exit stairways shall be
clearly indicated by illuminated exit signs. Such exit signs shall be
equipped with an independent alternate source of power such as a battery
pack or on-site generator or shall be of an approved self-illuminating
type.
-6-
23. Exitway exit signs. Illuminated exit signs shall be provided in
all exitways and located in such a manner as to clearly indicate the
direction of egress. Such exit signs shall be equipped with an independent
alternate source of power such as a battery pack or on-site generator or
shall be of an approved self-illuminating type.
24. Standpipe systems . Standpipe systems shall be upgraded to
deliver 250 gallons per minute per outlet. Each floor shall have a minimum
of two outlets in order to provide a minimum flow of 500 gallons per
minute.
(b ) Sprinkler Alternatives . The requirements of Table No . 1-A may
be modified as specified by the following for existing high-rise buildings
classified in the Uniform Building Code as Type I, II-F.R. , II One-hour,
III One-hour, IV or V One-hour construction when an approved automatic
sprinkler system is installed throughout the building in accordance with
U.B.C. Standard No. 38-1:
Item 4 - Manual fire warning system shall not be required.
Item 5 - Occupant voice notification system shall not be required;
however, if the building is equipped with a public address system, the
public address system shall be available for use as an occupant voice
notification system.
Item 6 - Vertical shaft enclosures may be of nonrated construction for
required exit stairway enclosures . Vertical shaft enclosures of
openings in floors provided for elevators, escalators and supplemental
stairways shall not be required, provided such openings are protected
by an approved curtain board and water curtain system.
Item 7 - Protection of openings in vertical shaft enclosures may be
non-rated but shall be not less than 1 3/4-inch solid-wood door or the
equivalent thereto. Closing and latching hardware shall be provided.
Item 9 - An automatic elevator recall system shall not be required.
Item 11 - Stair shaft ventilation shall not be required.
Item 15 - Existing corridor construction need not be altered .
Item 16 - Door openings into exit corridors may be protected by
assemblies other than those specified in Section 106 (a) , provided an
effective smoke barrier is maintained. Closing and latching hardware
shall be provided. Protection of duct penetrations is not required.
Item 18 - The length of existing exit corridor dead ends shall not be
limited.
Item 19 - Interior finish in exitways may be reduced by one classifi-
cation but shall not be less than Class III , as described in the
Uniform Building Code.
-7-
Installation of meters or backflow preventers for the connection to
the water works system need not be provided unless required by other
regulations of the authority having jurisdiction.
Section 50-3 is repealed and readopted as follows:
50-3. Violations and penalties .
Any person who shall violate any of the provisions of the Uniform Fire
Code, as amended, or who shall fail to comply with any of said provisions
or who shall violate or fail to comply with any orders made thereunder or
who shall act in any way in violation of any permits issued thereunder
shall , severally and for each and every violation in noncompliance res-
pectively, be guilty of a misdemeanor punishable by a fine not to exceed
three hundred dollars ($300.) or by imprisonment not to exceed ninety (90)
days, or by both such fine and imprisonment, as provided in the Code of the
City of Fort Collins . The imposition of one (1) penalty for any violation
shall not excuse the violation or permit it to continue, and all persons
shall be required to correct or remedy the violations or defects within a
reasonable time, and when not otherwise specified, each ten (10) days that
prohibited conditions are maintained shall constitute a separate offense.
The application of any penalty pursuant thereto shall not be held to
prevent the enforced removal of prohibited conditions nor the suspension or
removal of a permit or license issued thereunder.
Section 50-4 is repealed and readopted as follows:
50-4. Appeals .
Whenever the Chief shall disapprove any application made pursuant to
the Uniform Fire Code, as amended, or refuse to grant a permit applied for
thereunder or when it is claimed that the provisions of said code do not
apply or that the true intent and meaning of said code have been miscon-
strued or wrongly interpreted or when any person requests a variance
from the literal terms of said code, the applicant or person affected may
appeal the decision of the Chief to the Board of Appeals established
pursuant to Section 2.302 of said code. Such Board shall have the power to
vary or modify any requirement made by the Chief thereunder, provided that
an appeal to the Board is made within thirty (30) days of the date of the
action complained of. Within fifteen (15) days after the date of final
action of the Board of Appeals, either the Chief or the person affected may
appeal to the City Council by filing a notice of such appeal with the
City Clerk.
Section 2. Severability
The City Council hereby declares that should any section, paragraph,
sentence, word or other portion of this Ordinance or the Appendix adopted
therein be declared invalid for any reason, such invalidity shall not
-8-
effect any other portion of this Ordinance or said Appendix, and the City
Council hereby declares that it would have passed all other portions
of this Ordinance and adopted all portions of the said Appendix, inde-
pendent of the elimination therefrom of any such portion which may be
declared invalid.
Introduced , considered favorably on first reading , and ordered
published this 20th day of November , A.D. 1984, and to be presented for
final passage on the 4th day of December , [A.DD. , 1984.
/O�IY�JI.tjl
Mayor
ATTEST:
City Clerk
Passed and adopted on final reading this 4th day of December A.D. ,
1984.
l
Mayor
ATTEST:
City C erk�
-9-