Loading...
HomeMy WebLinkAbout4803 Boardwalk Dr - Disclosures/Blower Door Test - 03/20/2017BUILDING LEAKAGE TEST Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE Technician: Zach Kimbrough - EnergyLogic Project Number: 44984 Customer: Elder Construction Building Address: 4803 Boardwalk Dr Ft Collins , CO 80525 Test Results 1. Airflow at 50 Pascals: 1735 CFM50 ( +/- 2.9 %) (50 Pa = 0.2 w.c.) 1.98 ACH50 2. Leakage Area: 95.4 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 67.9 ( +/- 22.5 %) Exponent (n) = 0.829 ( +/- 0.062 ) Correlation Coefficient = 0.99720 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Winter: 158.1 CFM 0.18 ACH Summer: 104.9 CFM 0.12 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE Building Information Volume 52474.5 Surface Area Floor Area Height 13 # of Bedrooms # of Occupants Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 73.0 77.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -6.0 n/a n/a -66.6 -61.0 104.3 1832 1979 -3.2 Ring A -58.3 -52.7 90.6 1711 1849 2.0 Ring A -54.2 -48.7 75.4 1564 1690 -0.4 Ring A -47.1 -41.5 58.0 1377 1487 0.1 Ring A -39.9 -34.3 44.9 1215 1313 3.5 Ring A -36.0 -30.5 34.0 1060 1145 -0.5 Ring A -30.9 -25.4 26.0 931 1006 1.7 Ring A -25.8 -20.2 153.6 735 794 -3.0 Ring B -5.2 n/a n/a Time Averaging Period: 0 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE Comments Garage: -50 PA Mech: -50 PA