HomeMy WebLinkAbout4803 Boardwalk Dr - Disclosures/Blower Door Test - 03/20/2017BUILDING LEAKAGE TEST
Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE
Technician: Zach Kimbrough - EnergyLogic
Project Number: 44984
Customer: Elder Construction
Building Address: 4803 Boardwalk Dr
Ft Collins , CO 80525
Test Results
1. Airflow at 50 Pascals: 1735 CFM50 ( +/- 2.9 %)
(50 Pa = 0.2 w.c.) 1.98 ACH50
2. Leakage Area: 95.4 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 67.9 ( +/- 22.5 %)
Exponent (n) = 0.829 ( +/- 0.062 )
Correlation Coefficient = 0.99720
4. Test Settings: Test Standard: RESNET Multi-Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate: Winter: 158.1 CFM
0.18 ACH
Summer: 104.9 CFM
0.12 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE
Building Information
Volume 52474.5
Surface Area
Floor Area
Height 13
# of Bedrooms
# of Occupants
Year of Construction 2017
Wind Shield M
Location Climate Information
Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) Default
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
73.0 77.0 5000.0
Data Points
Nominal
Building Pressure
(Pa)
Baseline Adjusted
Building Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-6.0 n/a n/a
-66.6 -61.0 104.3 1832 1979 -3.2 Ring A
-58.3 -52.7 90.6 1711 1849 2.0 Ring A
-54.2 -48.7 75.4 1564 1690 -0.4 Ring A
-47.1 -41.5 58.0 1377 1487 0.1 Ring A
-39.9 -34.3 44.9 1215 1313 3.5 Ring A
-36.0 -30.5 34.0 1060 1145 -0.5 Ring A
-30.9 -25.4 26.0 931 1006 1.7 Ring A
-25.8 -20.2 153.6 735 794 -3.0 Ring B
-5.2 n/a n/a
Time Averaging Period: 0
Deviations from Standard RESNET Multi-Point Test - Test Parameters
None
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 3/20/2017 Test File: 4803 Boardwalk Dr Elder TECTITE
Comments
Garage: -50 PA
Mech: -50 PA