HomeMy WebLinkAbout5815 Tilden St - Disclosures/Blower Door Test - 11/03/2016BUILDING LEAKAGE TEST Date of Test: 11/03/2016 Technician: Jay Bundy Test File: Meritage Blower Door Customer: Meritage Homes 7400 E Orchard Rd Greenwood Village, Colorado 80111 Phone Building Address: 5815 Tilden Street Fort Collins, Colorado 80528 Test Results 1. Airflow at 50 Pascals: 1015 CFM ( +/- 0.9 %) (50 Pa = 0.2 w.c.) 1.40 ACH 0.29 CFM per ft2 floor area 2. Leakage Areas: 99.1 in2 ( +/- 10.5 %) Canadian EqLA @ 10 Pa 51.0 in2 ( +/- 16.2 %) LBL ELA @ 4 Pa 3. Minneapolis Leakage Ratio: 0.12 CFM50 per ft2 surface area 4. Building Leakage Curve: Flow Coefficient (C) = 69.6 ( +/- 24.8 %) Exponent (n) = 0.685 ( +/- 0.062 ) Correlation Coefficient = 0.98784 5. Test Settings: Test Standard: = CGSB Test Mode: = Depressurization Equipment = Model 3 Minneapolis Blower Door Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 78.4 CFM 0.11 ACH 2. Estimated Design Infiltration Rate: Winter: 86.2 CFM 0.12 ACH Summer: 49.0 CFM 0.07 ACH 3. Recommended Whole Building Mechanical 60.9 CFM Ventilation Rate: (based on ASHRAE 62.2) Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 Date of Test: 11/03/2016 Test File: Meritage Blower Door Building Conditions Inside Temperature: 65 deg F Heating Fuel: Gas Outside Temperature: 58 deg F Heating Fuel Cost: # of Stories 2.0 Heating Efficiency: Heating Degree Days: 6020 Wind Shield: M Cooling Fuel Cost: # of Occupants Cooling SEER: Cooling Degree Days: 287 # of Bedrooms: 3.0 Volume: 43470 ft3 Ventilation Weather Factor: 0.87 Surface Area: 8401 ft2 Energy Climate Factor: 17.0 Floor Area: 3506 ft2 Design Winter Wind Speed: 9.0 mph Design Winter Temp Diff: 69 deg F Design Summer Wind Speed: 7.0 mph Design Summer Temp Diff: 16 deg F Comments BUILDING LEAKAGE TEST Page 3 Date of Test: 11/03/2016 Test File: Meritage Blower Door Data Points: Data Entered Manually Nominal Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow Temperature Adjusted Flow % Error Fan Configuration Baseline Std Dev (Pa) -2.0 n/a +/- 0.00 -65.0 413.0 1200 1192 0.3 Ring B -60.0 362.6 1125 1117 -0.5 Ring B -55.0 315.4 1050 1043 -1.2 Ring B -50.0 297.5 1020 1013 2.7 Ring B -45.0 234.7 907 901 -1.5 Ring B