HomeMy WebLinkAbout3214 Anika Dr - Disclosures/Mechanical - 04/15/2016City of Fort Collins Residential Mechanical Systems Performance Report This form is a record of testing targets and results, with Pass/Fail outcomes. For lnforma!!on on measurement tools and testing techniques, see the "Residential New Construction Mechanical Systems Testing Guide." The guide and this form may be periodically updated; check the Building Services web site for the current version. Th!s form must be completed and signed by an "Approved Agency," and submitted to Building Services as a requirement for receiving a C.O. Color key Target orllmlt Measured value to compare with target or limit d. House Data Addr ess 3214 Anika Dr Bui Ider Meritage Homes HVAC contra ct or Four Seasons Heating Inc. As-built ch mech design anges vs submittal Testing date(s) 1417116 Cauticin 2. I.local Exhaust (Spot Ventilation) Bath exhaust Flow :L Flow box too! - Passive flow hood - Pilot tube duct traverse Other (note below) Design Airflow Exhaust Pickup Location (CFM 5000'1 Powder 50 Testing notes Other data ADCF =Air Density Correction Factor, based on too!, ADCF altitude (5000'), air temperature through tool Volumetric now (CFM 5000') = ADCF x Indicated flow (CFM) Date of "Residential Mechanical Systems Design Submittal" information referenced by testing technicians Testing tech {initials)~ Air tempi through tool {F) 7o Minimum Airflow Requirement (CFM 5000') + Type of Operation .:L 50 lntermiUent - 20 Continuous - 50 Intermittent - 20 Continuous _ 50 Intermittent - 20 Continuous - 50 Intermittent - 20 Continuous - 50 Intermittent - 20 Continuous - 50 lntermltlent - 20 Continuous - 50 Intermittent - 20 Continuous • Systems other than sub-structural floor exhaust Testing tech (initials)~ Code-minimum ventilation airflowl69 ICFM 5000 , Design ventil.ationl 69 J (based on CFA and #of B;:.R::_I::· ====-· --------, airflow~. ___ _,cFM SOOO' 59 Target ventilation airflow range (code-minimum) to 79 CFM 5000' (12-0% of design flow) System type _Exhaust-only .:f_ Supply-only Balanced Measured Airflow Air Temp Indicated Volumetric Measurement Method Tool Location Through ADCF Flow Flow Pass Fall Tool (F) (CFM) (CFM 5000') Total N/A _ Passive flow hood ... - exhaust - I~< F!owbox :f_ Pilot tube traverse ARD 70 1.098 78 IZl airflow - Flow collar _Other (note below) Total - NIA - supply - Flow box - Passive now hood 1{~ P1tot tube traverse 0 airflow - Flow collar _Other (note below) When supply airflow ts circulated by air handler fan, fan speed for measurementl ....... -__ H_e_at_in_g __ £_C_o_o_lln_g ___ c_o_n_u_n_uo_u_s_f_a_n~ Balanced airflow In balanced systems Average of measured' supply+ exhaust flows Testing notes ICFM 5000' Target flow range! {average+/- 15°/o} to ICFM 5000' 0Pass bFail Sub-structural floor exhaust lll N/A -- no sub-structural floor exhaust system Design exhaust airflow (based onl ____ ~ICFM 5000 , approved design)_ . Testing tech (Initials}~ Target airflow llmitsJr -------t-o-------,JcFM 5000 , (design +/-15o/o)"· -------------~- Measured airflow Flow _ Flow box tool _ Passive flow hood _ Powered flow hood For multiple systems, attach one page per system System #LJ Which parts of house does it serve?IL.M_a_in_i_B_a_se_m_e_n_t _____________________ _, Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech (inilials)EJ Furnace or Boller AC or Heat Pump Condenser AC or Heat Pump Coll Manufacturer Goodman Model# GMSS920402BN :~~~r olumbus I Static pressures Setup Type _ Basic fiberglass .:L Basic pleated High-effic pleated Speed: _ Heatlng !_ Coollng _ Cont. fan _High-stage for multi-stage equipment Blower speed tap: _L_o_w _______ _ Humidifier damper:!_ NIA _Open (Heating) _Closed (Cool!ng) LAU registers open _ Zone dampers open SP11-138.4 \ Goodman GSX16018 - - Electrostatic Other: .6.P Filter I 28 1 I (SP1 - SP2) ~--·--~· -------------- SP21-110.3 t Goodman CAPF3636 ThicknessD MERV (optional) 8 (Inches) D Testing tech (lniliats)EJ \ \ I (Sama location for NSOP, TFSOP) Cooling: Measured air flow through indoor coil 0 N/A -- no AC Installed Testing tech (initials)~ Design cooling alrflowl756 ICFM 5000 , (high stage)L.. ----~· Target airflow Umlts1r5-4-3------to --869 ----~, CFM 5000' (design +/-15%) . Measured airflow Flow gridl !_ 141 plate size _ 20 AlrlempEJ through 70 tool (F) ADCFEJ NSOPEJ Indicated alrflo01wEJ CFM Measured AF x FRCF Measured airflow, no1EJ CFM Testing approach and targets 0 N/A: No complete AC system !lJ NIA: House completed November - April {installing contractor responsible for testing in warm weather) 0 TXV: Subcool!ng +SH check 0 Non-TXV: Superheat 0 OEM-specific: Approach 0 Other OEM-specific (documentation required) Temperatures Condenserf;I (F): entering air temp~ Non-TXV: Return D TargetD TargetD air wet-bulb temp superheat - , , subcooling , , approach TargetD , , , , _, , Subcoollng DischargeD pressure (PSI) Superheat SuctionD pressure (PSI) CondenserD saturation T F (5000' ctiart) EvaporatorD saturation T F (5000' chart) LiquldD line F temp SuctionD line F temp subcooling AclualD F (Cond T - lfq line T) superheat Aclua\D F (Suet line T • evap T) 0 TXV Pass: Actual SC Vlithin +/- 3 F of target SC, 2 F min 0TXVFai! D Non-TXV Pass: Actual SH within+/- 5 F of target SH 0 Non-TXV Fall TXV checks: D Pass: Field-installed TXV Installed in accordance with OEM instructions Q_ Caution: Actual SH outside mfgr range Approach Liquid lineDF temp Actual approachDF {Uq lme T • condensffEAT) D Approach Pass: Actual approach within+/- 1 F of target approach 0 Approach Fall Testing notes 'l. Room :Air Fi'low + Bressure Bi!Jance Register air flows All registers are cut through finish materials and moving a!r ~Pass QFai! (Remainder of register air flow section under development, not yet being enforced) Pressure balance Room Room-to-Core {match names on plans, include Pressure Drop basement if there is a door) Target Range (Pa) with system #1 ·3 to +3 -3 to +3 -3to +3 ·3 to +3 -3 to +3 [tJ Combustion safety testing N/A -- no natural-draft combustion appliances (Appllance Types table must be completed for every home) Appliance types Combustion Type Testing tech (initials)LJ Appliance N/A Draft-hood Induced-draft Power- Direct- Powered sealed- !Natural-draft) fNatura!-draft) vent vent combustion Electric Furnace #1 0 0 0 0 0 0 0 Furnace #2 0 0 0 0 0 0 0 Boiler #1 0 0 0 0 0 0 0 Boi!er#2 0 0 0 0 0 0 0 Water heater #1 0 0 0 0 0 0 0 Water heater #2 0 0 0 0 0 0 0 Fireplace #1 0 0 0 0 0 0 0 Fireplace #2 0 0 0 0 0 0 0 Other: 0 0 0 0 0 0 0 Worst-case depressurization performance H ouse setuo These doors are closed: -__ - Vented # of bath range fans hood on on __ Clothes dryer on -- Air handler on Other fans on: Other setup notes: Outdoor temperatureLJF I Tested appllances App!iancef----------t---------+----------1 Location CAZ. pressure BPI depressurization limit (Pa wrt outside) Measured net CAZ depressurization (Pa wrt outside) OK (less negative) I Caution (more negative) Splllage BPI maximum limit Measured spillage duration Pass= duration not exceeding limit Draft pressure BPlllm!t Measured (seconds (seconds I I {Pa wrt CAZ) {Pa wrt CAZ) Pass = pressure more negative than limit CO concentration in undiluted flue gas BPlm aximum limit Meas ured CO Pass = CO level not exceeding limit Cauli on= CO level 25 to 100 ppm Testing notes Residential Mechanical Design Submittal (ppm) (ppm) '---~~~~~~-'~~~~~~~--'-~~~~~~~-' 0 JoK I 0 I Caution D JoK J 0 I Caution D JoK I 0 I Caution 60 60 60 Testing tech (initials)~ System Testing Notes Controls Operating Per Design Intent local exhaust (all fans) D N/A eJ Pass D Fail Whole-house ventilation D N/A Iii Pass D. Fail Sub-structural floor exhaust IZl N/A D Pass D Fall To cold to test A/C Heating (all systems} D NIA "'1 Pass .D Fail Cool!ng (all systems) I?:] NIA D Pass '131. Fail Signatures . . Technician #1 performing inspection and testing documented on this report (Approved Agency) ~I certify that the tests referenced above, Jn sections bearing my !n!Ua!s, were performed in accordance with protocols specified by the _City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. Name (print) Ian Polman Tille Air Flow Tech Company Four Seasons Heating Inc. Signature and Date Ian Polman 417/16 Technician #2 performing inspection and testing documented on this report (Approved Agency) 'I certify that the tests referenced above, in sections bearing my initials, were performed !n accordance with protocols specified by the City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. Name (print) Tille Company Signature and Date HVAC Contractor {City of Fort Collins license holder) I certify that I have reviewed this report and that the test results are an accurate representation of the performance of the installed mechanical 'systems. Name {print) Lynn Cobb Title Project Manager Company Four Seasons Heating Inc. Signature and Date Lynn Cobb 4/15/16 Residential Mechanical Design Submittal V20140101 Page 6 City of Fort Collins Residential Mechanical Systems Performance Report This form is a record of testing targets and results, with Pass/Fall outcomes, For Information on measurement tools and testing techniques, see the "Residential New Construction Mechanical Systems Testing Gulde.ft The guide and this form may be periodically updated; check the Building Services web site for the current version. Thls form must be completed and signed by an ~Approved Agency,n and submitted to Bulldlng Services as a requirement for receiving a C.O. Color key Target orlimlt Measured value to compare with target or limit ~. House Data Addr ess 3214 Anika Dr Bui Ider Meritage Homes HVAC contra ct or Four Seasons Heating Inc. As·built ch mech design anges vs submittal Testing date(s) 1417116 2. I.local Exhaust (Spot Ventilation) Bath exhaust Flow :L Flow box tool - Passive flow hood - Pitot tube duct lraverse Other (note below) Design Airflow Exhaust Pickup Location (CFM 5000') Laundry 50 Bath 2 50 Master Bath 50 MasterW/C 50 Testing notes Other data ADCF ADCF =Air Density Correction Factor, based on tool, altitude {5000'), air temperature through tool Volumetric flow (CFM 5000') = ADCF x lndlcated flow (CFM) Date of ~Residential Mechanical Systems Design Submittal" information referenced by testing technicians Testing tech (!nil!a!s)EJ Air lempl through tool (F) ?O Minimum Airflow Requirement (CFM 5000') +Type of Operation .:L 50 lntermlttent - 20 Continuous L 50 Intermittent - 20 Continuous L 50 lntermillent - 20 Continuous ..L 50 Intermittent - 20 Continuous - 50 Intermittent - 20 Continuous - 50 Intermittent - 20 Continuous Systems other than sub-structural floor exhaust Testing tech (initials)~ Code-minimum ventilation alrflowl ICFM 5000 , Design ventllat!onl icFM 5000 . (based on CFA and# of B~R:_l:;. ====·--------, alrflowL. ---~- Target ventilation airflow range to CFM 5000' (coda-.rninlmum) (120% of design flow) S stem _Exhaust-only Y ty e _ Supply-only P Balanced Measured Airflow Air Temp Indicated Volumetric Measurement Method Tool Location Through ADCF Flow Flow Pass Fail Toot (F) (CFM) (CFM 5000') Total - N/A - Passive flow hood .. exhaust - Flow box - Pilot tube traverse 0 0 airflow - Flow collar _Other (note below) Total - N/A - supply - Passive flow hood p Flow box - Pitot tube traverse 0 airflow Flow collar Other (note below) When supply airflow is circulated by air handler fan, fan speed for measurementcl __ H_e_a_tln_g ___ c_o_o_li_ng ___ c_o_n_t_ln_u_ou_s_f_a_n~ Balanced airflow In balanced systems Average of measured' supply + exhaust flows. Testing notes I with system #1 ICFM 5000' Target flow rangel (average+/- 15%) to ICFM 5000' 0Pass _OFail Sub-structural floor exhaust Iii N/A -- no sub-structural floor exhaust system Design exhaust airflow (based onl icFM 5000 , approved des!gn)L. ____ _,_ Testing tech (inltlals)~ Target airflow limlls~1-------to------~ICFM 5000' {design+/- 15°/o)L_ ------'---------~- Measured airflow Flow _Flow box Pitot tube traverse Tool I Air tempo Passive flow hood Flow collar through tool _ - Powered flow hood _ Other (note below) location . tool (F) =--;:::::====~--'--' '----;::====::::::_, Indicated flow CFM Volumetric flow CFM 5000' 0 Pass _O Fail Testing notes 4. Heating + Cooling Duct Uieakage NIA_ No ductwork _{_No ductwork outside conditioned space 0 1 k Testing tech (Initials): uct ea age - Energy rater (name, For multiple systems, attach one page per system System #D Which parts of house does it serve? Upstairs '--~~~~~~~~~~-;::::==: Installed equipment (Be clear about wh!ch AC components are fnstalled at time of testing) Testing tech (initials)llP Furnace or Boller Manufacturer Goodman Model# GMSS920402BN :,~~~f olumbus I Static pressures Setup Type _ Bas!c fiberglass :L Basic pleated Hlgh-effic pleated Speed:_ Healing :!._ Cooling _ Cont fan High-stage for mutu-stage equipment Blower speed tap: _L_o_w _______ _ Humldlfler damper::!_ NIA _Open (Healing) _Closed (Cooling) ..:!..._All registers open _ Zone dampers open SP11-101.7 \ AC or Heat Pump Condenser Goodman GSX16018 - - Electrostatic Other: t .6.P Filter 1-4 6 I (SP1 • SP2) ~-· --~-~ AC or Heat Pump Cotl Goodman CHPF2430 ThlcknessD (inches) (optional) MERVD 8 Testing tech (Initials)~ \ (SP3-SP4) 22.2 I (Same location for NSOP, TFSOP) .6.PColll ~/.,--~ \ Cooling: Measured air flow through indoor coil 0 NIA·· no AC installed Testing tech (!nlt!a!s)~ Design cooling airflow,447 icFM 5000 , (hlghstage)~. ----~- Target airflow !imitsrl 3_8_0 _____ 10_5_1_4----~ICFM 5000' {design +/-15"/o)_ . Measured airflow Flow gridl .f 141 plate size _ 20 AlrtempEJ through 70 tool (F) ADCFEJ NSOPEI Indicated airflow~CFM Testing tech (!nltia!s)EJ Testing approach and targets 0 N/A: No complete AC system 0 NIA: House completed November - April (installing contractor raspons;bfe for testing in warm weather) 0 TXV: Subcoollng + SH check 0 Non-TXV: Superheat D OEM-specific: Approach D Other OEM-specific (documentation required) Temperatures CondenserEJ (F): entering air temp 38 Non-TXV: Return D TargetD- TargetD air wet-bulb temp superheat , subcooling , , - , TargetD approach , Subcooling DischargeD pressure (PSI) Superheat SuctionD pressure (PSI) CondenserD saturation T F (5000' chart) EvaporatorD saturation T F {5000' chart) llqu!dD line F temp SucllonD line F temp subcooling ActualD F (Cond T ·liq line T) superheat ActualD F (Suet line T - avap T) 0 TXV Pass: Actual SC within+/- 3 F of target SC, 2 F min 0TXVFai! D Non-TXV Pass: Actual SH within+/- 5 F of target SH 0 Non-TXV Fail TXV checks: D Pass: Field-Installed TXV Installed in accordance 'Nith OEM instructions D Caution: Actual SH outside mfgr range Approach liquid llneDF temp Actual approachDF {Liq line T. condenser EAT) D Approach Pass: Actual approach 'Nithln +/- 1 F of target approach D Approach Fait Testing notes 'T:. Room 'Air F'low "" Rressure Bala,nce ' , ~ Register air flows All registers are cut through finish materials and moving air ~ Pass 0Fall (Remainder of register air flow section under development, not yet being enforced) Pressure balance Master Bedroom Bedroom 3 Bedroom 2 Room (match names on plans, Include ~ Combustion safety testing NIA -- no natural-draft combustion appliances {Appliance Types table must be completed for every home) Appliance types Combustion Type Appllance Draft-hood Induced-draft Power- Direct- Testing tech (initials)LJ N/A Powered sealed- rNaturaf-draft /Natural-draft vent vent combustion Electric Furnace #1 D D D D 0 D D Furnace #2 D D D D D D D Boiler #1 D D D D D D D Boiler #2 D D D D D D D Water heater #1 D D D D D D D Water heater #2 D D D D D D D Fireplace #1 D D D D D D D Fireplace #2 D D D D D D D Other: D D D D D D D Worst~case depressurlzatlon performance H ouse setun These doors are closed: -- # of bath fans on __ Vented range hood on __ Clothes dryer on -- Air handler on Other fans on: Other setup notes: Outdoor temperatureLJF I Tested appliances Appllancel--------_,f---------t---------1 Location CAZ pressure BPI depressurization limit {Pa wrt outside) Measured net CAZ. depressurizat!on {Pa wrt outside) OK {less negative) I Caution {more negative) Splllage BPI maximum limit Measured spillage duration {seconds {seconds ) ) Pass= duration not exceeding limit Draft pressure BP/limit Measured (Pa wrt C!\2. (Pa wrt C!\2. Pass= pressure more negative than l!mit CO concentration in undlluted flue gas BPI maximum limit Measured CO Pass= CO level not exceeding limit Caution = CO level 25 to 100 ppm Testing notes Residentlal Mechanical Design Submittal (ppm (ppm ) ) ) Testing tech {Initials)~ System Controls Operating Per Design Intent Testing Notes Local exhaust {all fans) D NIA Ill Pass D Fall Whole-house ventilation lil NIA D Pass p Fail Sub-structural floor exhaust IZl NIA D Pass .D Fail To cold to test NC Heating {all systems) D NIA [] Pass D Fail Cooling (al! systems) Ill NIA D Pass D Fall Signatures Technician #1 performing Inspection and testing documented on this report (Approved Agency) :.! I certify that the tests referenced above, in sections bearing my Initials, were performed Jn accordance with protocols specified by the :: City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. Name (print) Ian Pelman Title Air Flow Tech Company Four Seasons Heating Inc. Signature and Date Ian Pelman 417/16 Technician #2 performing Inspection and testing documented on this report (Approved Agency) 'I certify that the tests referenced above, in sections bearing my Initials, were performed In accordance with protocols specified by the i. City of Fort Colllns Building Services Department, and that the reported results are accurate to the best of my knowledge. Name {print) Tille Company Signature and Date HVAC Contractor (City of Fort Colllns llcense holder) certify that I have reviewed this report and that the test results are an accurate representation of the performance of the Installed mechanical ·'systems. Name {print) Lynn Cobb T!Ue Project Manager Company Four Seasons Heating Inc. Signature and Date Lynn Cobb 4/15/16 Residential Mechanlcal Design Submittal V20140101 Page6 ) '---------''--------'--------' D jOK I .O• I Caution D jOK I 0 I Caution D jOK I 0 I Caution 60 60 60 0 !Pass I JJc.IFail D !Pass !HJ• !Fait D !Pass 1;0.!Fait D !Pass l,O;jFail D jPass I o,JFait D !Pass ifD]Fail 100 100 100 D !Pass ID !Fall D !Pass j. O'!Fail D !Pass jJ;J jFail D.lcaullon 1' O': Jcaulion Dlcaulion V20140101 Page 5 basement if there Is a door) Residential Mechanical Design Submittal Room-to-Core Pressure Drop Target Range (Pa) -3 to +3 ·3 to +3 ·3 to +3 -3to +3 ·3 to +3 ·3 to +3 ·3 to +3 ·3 to +3 ·3 to +3 ·3 to +3 V20140101 Measured Pressure Drop (Pa) -.3 1.8 2.2 Testing tech (Initials)~ Testing tech (initials)~ Pass Fall 0 i; 0 r 0 l?J,., .... Page 4 Measured AF x FRCFL__j M_easured airflow, .no~CFM ad1ustmenUcorrect1onL__j Testing notes Heating: Gas manifold pressure Manifold pressure~IWC OEM spec@ 5ooo·L_J Heating: Temperature rise {high stage) Target manifold Pl; 3 to 3 .7 limits (spec+/- 5%)"-·------~ OEM temperature rise Hmitsl3_o ___ io_fi_O_~jF (high stage)_ • Flow ResistanceEJ Correction Factor ·79 Volumetric alrflowEJas CFM Ill Pass Indicated AF x ADCF 5000' lq Fail Testing tech (initials)~ IWC MeasuredEJ.4 4 IWC G?i Pass pressure :q Fail Testing tech (initials)~ Measured temps (F): Sup~l~EJ- Retua7r~ = Te~p~ Ill Pass nseL_J .0 Fail ··o'.caution: within 10F of top of range Residential Mechanical Design Submittal V20140101 Page 3 data source - company, testing date): House conditioned floor areal (1nciude full basement) Test Parameter and Conditions Leakage Type Timing Air Handler Total leakage Rough-in Excluded Total leakage Rough-in Included Total leakage Complete Included Leakage Complete Included to outdoors Residential Mechanical Design Submittal Testing notes (incl multlple sys) A!rtempJI through tool (F)L___j Maximum Allowed Duct Leakage Normallzed Absolute (CFM25 5000' / 100 s~ (CFM25 5000') 4 6 12 8 V20140101 Measured Duct Leakage System #1 System #2 Indicated Volumetric (CFM25) (CFM25 5000') Pass Fall Pass Fall 0 . i;; •• 0 'o 0 I" . 0 0 0 0 iQ 0 I '•El 0 0 Page 2 - 50 Intermittent - 20 Continuous ADCF11.098 Measured Airflow Indicated Volumetric Flow Flow Pass Fall (CFM) (CFM 5000') 94 103 lZJ I 88 96 Ii! 86 94 Ii! ;;p 85 93 Ii! o D :Gr D Tl D .D. Kitchen exhaust NIA· hood does not vent to outside D Testing tech (initials)EJ Oven fuell _Gas _Electric J Measured airflow Minimum airflow requirement (CFM 5000') +operation! _ 100 Intermittent _ 25 Continuous I - Flow box 1 _ Passive flow hood _ Powered flow hood Flow too lndi caled flow! Test ing note s _-Flow P!tot grid tube traverse _Other (note below) ICFM Residential Mechanlcal Design Submittal Tool location _ Interior grille Air tempo ADCFD _ Exhaust duel through {Exterior termination not OK) tool (F) Volumetric f1owl lcFM 5000' D Pass {]Fail V20140101 Page 1 0 !Pass i;IJ>JFall 0 !Pass I IJ !Fail 0 !Pass i'.OIFait 0 !Pass FD.I Fail 0 !Pass l·OIFall 0 !Pass ID¥ ail 100 100 100 0 JPass I O!Fail 0 JPass IDIFait 0 JPass l.OIFail ··O'Jcaulion 0 :Jcaulion D Jcautlon V20140101 Page 5 -3 to +3 -3 to +3 -3to +3 -3to +3 ·3 to +3 Residential Mechanical Design Submittal V20140101 Testing tech (lniUals)~ Testing tech (initials)~ Measured Pressure Pass Fall Drop (Pa) 0 'Q. 0 fl 0 I 0 0 0 ~ 0 cg 0 0 0 21) 0 ,, ~ Page 4 adjustmenVcorrecUon Testing notes {high stage) to 3.7 Heating: Gas manifold pressure Manifold pressure~IWC OEM spec@ 5000'L_j Target manifold P,3 3 llmits (spec+/- 5%) ' ~------~ Heating: Temperature rise OEM temperature rise limitsJ, 3_o ___ t_o_e_o __ _,JF (high stage)_ . Measured temps (F}: Sup~ll~~ - Retu;~::::: Te~p4sl nsec:__j Resldentia! Mechanical Design Submittal V20140101 Flow ResistanceEJ Correction Factor ·91 Vo1.umetric alrflow~CFM -~-Pass !nd1cated AF x AOCF~5000' Jil Fail IWC Ill Pass Testing tech (initials)EJ Measuredr;,;llWC l.i.I Pass pressurec__j J::I Fail 0Fail Testing tech (initia!s)EJ d Caution: within 10F of lop of range Page 3 _Flow Pitot tube collar traverse Tooll Air through tempo _Other (note below) location . tool (F) ~-;::::=======;-~~ ~;======:::::'.-, Indicated flow CFM Volumetric flow C~M 5000' 0 Pass IJ. Fall Testing notes It. Heating + Cooling Duct t:eakage N/AI- No ductwori< I :!.... No ductwork outside conditioned space Testing notes! (incl multiple sys)I 0 t 1 k Testing tech (ln!Ua!s): uc ea age - Energy rater (name, data source - company, testing date): House conditioned floor areal (indude full basement) Test Parameter and Conditions Leakage Type Timing Air Handler Total leakage Rough-In Excluded Total leakage Rough-Jn Included Total leakage Complete Included Leakage Complete Included to outdoors Residential Mechanlcaf Design Submittal A!rtempr-1 through tool (F)L__j Maximum Allowed Duct Leakage Normalized Absolute (CFM25 5000' I 100 sn (CFM25 5000') 4 6 12 8 V20140101 Measured Duct Leakage System #1 System #2 Indicated Volumetric (CFM25) (CFM25 5000') Pass Fall Pass Fall 0 03 0 ;Q 0 J;;l 0 ;p 0 ;[ ••. 0 p 0 it; ,. 0 q Page 2 ADCF,1.098 Measured Airflow Indicated Volumetric Flow Flow Pass Fail (CFM) (CFM 5000') 71 78 Ill <r,. D ' D I; D ,,,- !,; D 1 ]\ D ,1 J1 D d Kitchen exhaust NIA~ hood does not vent to outside D Testing tech (JniUa!s)~ Oven fuetl ..:L. Gas _Electric j Measured airflow Minimum airflow requirement (CFM 5000') + operationj L 100 Intermittent _ 25 Continuous I - Flow box 1 _ Passive flow hood _ Powered flow hood Flow too Ind lcated flowl Test ing not es _!_ Pilot tube traverse _Flow grid _Other (note below} Jc FM Residential Mechanical Design Submittal Tool _ Interior grille AlrtempEJ location ADCFEJ .:!.... Exhaust duct through 70 (Exterior termination not OK) tool (F) Volumetric flowl 297 ICFM 5000' 0Pass 0Fail V20140101 Page 1