HomeMy WebLinkAbout605 Buckingham St - Special Inspections/Field Verification - 11/08/2016Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 11/8/16 PROJECT New Belgium Brewing Medical Clinic 602 Buckingham Street Fort Collins, CO 80524 ARCHITECT Open Studio Architecture 141 S. Broadway, Suite 202 Denver, CO 80209 ENGINEER A.E. Associates 5587 W. 19 th Street Greeley, CO 80634 CONTRACTOR Air Comfort, Inc. 150 Rome Ct. Fort Collins, CO 80524 605 Buckingham St Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: New Belgium Brewing Medical Clinic ADDRESS: 602 Buckingham Street, Fort Collins, CO 80524 The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:11/8/16 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:11/8/16 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 11/8/16 CERTIFICATION EXPIRATION DATE: 3/31/2018 Table Of Contents PROJECT: LOCATION: New Belgium Brewing Medical Clinic Fort Collins, CO DATE: CONTACT: AUTHOR: 11/8/2016 Emerson Moore Emerson Moore Table Of Contents 1 Instrument Calibration Report.pdf................................................................................................................................. 1 2 Abbreviation Report.pdf................................................................................................................................................ 2 3 Fan Coil........................................................................................................................................................................ 3 3.1 FCU-01................................................................................................................................................................... 3 4 Fan Unit........................................................................................................................................................................ 5 4.1 EF-01...................................................................................................................................................................... 5 4.2 EF-02...................................................................................................................................................................... 5 5 Mech Prints.pdf............................................................................................................................................................. 6 5.1 LG001..................................................................................................................................................................... 5.2 LD101..................................................................................................................................................................... 5.3 LS100...................................................................................................................................................................... 5.4 LS101...................................................................................................................................................................... 5.5 LS501...................................................................................................................................................................... 5.6 LP001...................................................................................................................................................................... 5.7 LP100...................................................................................................................................................................... 5.8 LP501...................................................................................................................................................................... L.H. Finn and Associates Final Report Project: New Belgium Brewing Medical Clinic Manufacturer Model Serial Application Cal. Date Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014 Alnor HM-680 70750150 Hydronic Press. & Diff. Press. 12/14/2015 Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015 Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016 Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 6/10/2015 Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 4/10/2015 Cooper SH66A 92711016 Temperature 4/10/2015 Extech 461895 Q394479 Rotation Measurement 10/12/2015 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 3/8/2016 Extech 461895 Q331990 Rotation Measurement 11/4/2014 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 4/8/2015 Extech 461895 Q590099 Rotation Measurement 10/12/2015 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 11/5/2015 Fluke 336 97110539R Electrical Measurement 4/5/2016 Fluke 336 97110538R Electrical Measurement 9/29/2015 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 335 12990071 Electrical Measurement 3/4/2016 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 4/8/2015 Fluke 374 20030354 Electrical Measurement 10/23/2015 Shortridge ADM-860C M05789 Digital Manometer 11/25/2015 Shortridge ADM-860C M06821 Digital Manometer 10/12/2015 Shortridge ADM-860C M07352 Digital Manometer 6/6/2016 Shortridge ADM-860C M09123 Digital Manometer 4/18/2016 Shortridge ADM-860C M09347 Digital Manometer 9/26/2015 Shortridge ADM-860C M10144 Digital Manometer 11/18/2014 Shortridge ADM-860C M10371 Digital Manometer 11/5/2015 Shortridge ADM-860C M11448 Digital Manometer 4/15/2016 Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015 Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 10/12/2015 Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 1 of 9 Project: New Belgium Brewing Medical Clinic Symbol Description Symbol Description A Airflow (L/S) NS Not Shown AF Air Foil NT No Information Tag ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceiling Diffuser SD Supply Diffuser CFM Airflow (Cubic Feet / Minute) SNKL Snorkel DD Direct Drive SP Static Pressure Des Design SPD Static Pressure Drop DWDI Double Width Double Inlet SR Supply Register EF Exhaust Fan SWSI Single Width Single Inlet EG Exhaust Grille T Temperature ( C ) ER Exhaust Register T Temperature ( F ) ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Frequency Drive GPM Waterflow (Gallons / Minute) VS Variable Speed HC Heat Coil W Waterflow (L/S) HER Heat Exchanger HRC Heat Recovery Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 2 of 9 Fan Coil PROJECT: LOCATION: New Belgium Brewing Medical Clinic Fort Collins, CO DATE: CONTACT: AUTHOR: 11/8/2016 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 11/7/2016 SYSTEM/UNIT: FCU-01 Unit Data Unit Manufacturer Carrier Unit Model Number FX4DNB061 Unit Serial Number 4016A85188 Filter Type MERV-8 Filter Qty 1 Filter Size 23x20x4 Test Data Total CFM Design 1850 CFM Total CFM Actual 1837 CFM Outside Air CFM Design 150 CFM Outside Air CFM Actual 162 CFM Return Air CFM Design 1700 CFM Return Air CFM Actual 1675 CFM Motor Volts T1-T2 212 Volts Amps T1 5.4 Amps Fan RPM Actual High Speed RPM Fan SP In -0.75 In. wc. Fan SP Out 0.14 In. wc. Unit E.S.P. Actual 0.41 In. wc. E.S.P. In -0.27 In. wc. E.S.P. Out 0.14 In. wc. Filter SP In -0.27 In. wc. Filter SP Out ANA In. wc. Coil SP In ANA In. wc. Coil SP Out -0.75 In. wc. Motor Data Motor Manufacturer Genteq Motor Frame NS Motor HP 3/4 Motor RPM 1050 (3 spd) RPM Motor Phase 1 Motor Hertz 60 Hz Motor Service Factor NS Motor Rated Volts 208-230 Motor FL Amps 6.0 Amps Sheave Data Motor Sheave Make Direct Drive FCU-01 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Fan Coil PROJECT: LOCATION: New Belgium Brewing Medical Clinic Fort Collins, CO DATE: CONTACT: AUTHOR: 11/8/2016 Emerson Moore Emerson Moore FCU-01 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 110 B 24x24 200 126 206 63 103 Inlet-B 111 B 24x24 70 83 74 119 106 Inlet-C 107 D 14x6 320 339 330 106 103 Inlet-D 112 B 24x24 65 98 69 151 106 Inlet-E 102 D 14x6 295 475 298 161 101 Inlet-F 100 D 12x12 500 103 492 21 98 Inlet-G 109 B 24x24 100 74 102 74 102 Inlet-H 108 B 24x24 100 143 104 143 104 Totals: - - - 1650 1441 1675 87 102 L.H. Finn and Associates Final Report Page 4 of 9 Fan Unit PROJECT: LOCATION: New Belgium Brewing Medical Clinic Fort Collins, CO DATE: CONTACT: AUTHOR: 11/8/2016 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 11/7/2016 SYSTEM/UNIT: EF-01 Unit Data Fan Manufacturer Twin City Fan Fan Model Number T100 Fan Type Forward Curve Fan Size 6"ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 75 CFM Total CFM Actual 79 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 0.4 Amps SP In Actual 0.0 in. wc SP Out Actual 0.04 in. wc Total SP Actual 0.04 in. wc Motor Data Motor Manufacturer ANA Motor HP NS HP Motor RPM NS RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.1 Amps Sheave Data Motor Sheave Make Direct Drive Tested By: Emerson Moore Date: 11/7/2016 SYSTEM/UNIT: EF-02 Unit Data Fan Manufacturer Twin City Fan Fan Model Number T100 Fan Type Forward Curve Fan Size 6"ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 75 CFM Total CFM Actual 82 CFM Fan RPM Actual Direct Drive RPM T H AAV, MAV B F M S FS 24x18 SD TT AQ 1 DUCTWORK LEGEND - CONSTANT VOLUME SYSTEMS LEGEND DRAWING INDEX MECHANICAL GENERAL NOTES CODE INFORMATION DUCT SYSTEM NOTES (NOT ALL ITEMS WILL BE USED) 1. RESOLVE ALL QUESTIONS OR CONFLICTS WITH ENGINEER BEFORE ANY EQUIPMENT IS ORDERED, MATERIALS FABRICATED OR SYSTEMS INSTALLED. 2. COORDINATE THE INSTALLATION OF MECHANICAL SYSTEMS WITH OTHER TRADES. PROVIDE OFFSETS AS NECESSARY TO ACCOMMODATE STRUCTURE AND 4. COORDINATE AND VERIFY THAT ALL OPENINGS IN WALLS ABOVE CEILING / DOOR LOUVERS / DOOR UNDERCUTS ARE PROVIDED AS INDICATED ON THESE DRAWINGS. 5. COORDINATE EXACT SIZE OF EQUIPMENT HOUSEKEEPING PAD WITH EQUIPMENT OVERALL FOOTPRINT DIMENSIONS. 6. LEVEL ALL EQUIPMENT CURBS / BASES PRIOR TO INSTALLATION OF ANY EQUIPMENT. 8. SEAL ALL ROOF PENETRATIONS IN ACCORDANCE WITH ROOF MANUFACTURER'S RECOMMENDATIONS. SEAL ALL WALL PENETRATIONS WATERTIGHT WITH 9. PROVIDE ACCESS PANELS (MIN. 24"x24") IN "HARD" CEILINGS PER CODE FOR ACCESS TO ALL MOTORS, CONTROLS, BALANCING DAMPERS, FIRE DAMPERS, COMBINATION FIRE / SMOKE DAMPERS AND OTHER MECHANICAL EQUIPMENT. 10. LABEL ALL MECHANICAL DEVICES (VALVES, F/S DAMPERS, ETC.) ABOVE LAY-IN CEILING ON GRID BELOW DEVICE WITH PRINTED SELF ADHESIVE LABEL. 11. LOCATION OF ALL CEILING INLETS AND OUTLETS ARE APPROXIMATE. COORDINATE LOCATION WITH EXISTING LIGHT FIXTURES AND ARCHITECT, ETC. 12. INSTALL FLEXIBLE CONNECTORS AT ALL DUCT CONNECTIONS TO MECHANICAL EQUIPMENT, INCLUDING FAN COIL UNITS. 13. MAKE ALLOWANCES IN HARD CEILING AREAS FOR SPIN-IN FITTING WITH REMOTE DAMPER ACTUATOR. 14. VERIFY ALL DIMENSIONS AND JOB CONDITIONS. REPORT TO THE ENGINEER ANY DISCREPANCIES OR OMISSIONS WHICH WOULD INTERFERE WITH THE SATISFACTORY COMPLETION OF WORK. 15. CLOSE ALL PIPE AND DUCT OPENINGS WITH CAPS OR PLUGS DURING INSTALLATION. PROTECT ALL FIXTURES AND EQUIPMENT AGAINST DIRT, WATER, CHEMICAL, AND MECHANICAL DAMAGE. 16. ALL WORK AND MATERIALS TO CONFORM WITH THE REQUIREMENTS OF ALL APPLICABLE BUILDING AND FIRE CODES AND ALL AUTHORITIES HAVING JURISDICTION. OTHER TRADES. COORDINATE ANY PENETRATIONS THROUGH STRUCTURAL MEMBERS WITH STRUCTURAL ENGINEER. ISSUED FOR CONSTRUCTION ISSUED FOR REFERENCE ONLY, NOT FOR CONSTRUCTION SILICONE CAULKING AND BACKER ROD. 2012 INTERNATIONAL BUILDING CODE 2012 INTERNATIONAL PLUMBING CODE 2012 INTERNATIONAL FUEL GAS CODE 2012 INTERNATIONAL FIRE CODE 2012 INTERNATIONAL ENERGY CONSERVATION CODE INSULATION SCHEDULE WITHIN 15 LINEAR FEET (OR AS NOTED) OF FAN COIL UNITS UNTREATED OUTSIDE AIR DUCT ALL OTHER SUPPLY ALL OTHER RETURN WITHIN A RETURN PLENUM ALL EXHAUST 1. ALL DUCTWORK UNLESS SPECIFICALLY INDICATED SHALL BE GALVANIZED SHEET METAL INSTALLED AT A MINIMUM, IN ACCORDANCE WITH THE SMACNA DUCT CONSTRUCTION STANDARDS. 2. CLASSIFICATION: ALL DUCTWORK - PRESSURE CLASS +2" W.C., SEAL CLASS B. 2. ALL DUCTWORK JOINTS SHALL HAVE DUCTMATE "35", TDC, "HARDCAST" OR OTHER APPROVED SEALER. 3. DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. 4. ROUND DUCTWORK CONCEALED, 12" AND SMALLER, +2" W.C. TO -1" W.C. PRESSURE CLASS: GALVANIZED SHEET METAL SNAP-LOCK. ALL OTHER: GALVANIZED SHEET METAL SPIRAL. SCALE: SCALE: M SPLIT SYSTEM PIPING SCHEMATIC FAN COIL UNIT INSTALLATION DIAGRAM MOTORIZED DAMPER INTERLOCKED TO FAN COIL UNIT OPERATION FLEXIBLE CONNECTION (TYP) PROVIDE EXTERNAL FILTER RACK AND FINAL TRANSITION TO FAN COIL UNIT. EXHAUST FAN SCHEDULE NOTES: A) INTERLOCK WITH LIGHT SWITCH, B) RUNS ON PROGRAMMABLE TIME CLOCK ACCESSORIES: 1) FAN SPEED CONTROLLER, 2) PLUG TYPE DISCONNECT, 3) VIBRATION ISOLATORS, 4) ACCEPTABLE ALTERNATE MANUFACTURERS ARE COOK, GREENHECK, AND ACME. TAG MANUF. MODEL LOCATION SERVICE FAN DATA MOTOR DATA OPER. WEIGHT (LBS) AIR NOTES ACCESSORIES TAG QTY. (CFM) ESP ("W.C.) TYPE RPM MOUNT DRIVE BHP HP VOLTS/ø VFD EF-1 TWIN CITY T-100 CEILING RESTROOM 75 0.25 CABINET 640 CEILING DIRECT 0.08 1/8 115/1 NO 30 A 1, 2, 3, 4 EF-1 EF-2 TWIN CITY T-100 CEILING MECH/WATER 75 0.25 CABINET 640 CEILING DIRECT 0.08 1/8 115/1 NO 30 B 1, 2, 3, 4 EF-2 GRILLE REGISTER AND DIFFUSER SCHEDULE FINISH: 1) FACTORY FINISH TO BE SELECTED BY ARCHITECT A) SEE DRAWINGS FOR NECK SIZE AND AIR QUANTITY, B) PROVIDE FRAME COMPATIBLE WITH MOUNTING LOCATION, C) ACCEPTABLE ALTERNATE MANUFACTURERS ARE PRICE, METALAIRE, AND KREUGER. TAG MANUF MODEL SYSTEM DESCRIPTION CONSTRUCTION OBD FINISH NOTES A TITUS TDC SUPPLY 18x18 FLUSH LOUVERED FACE, 24x24 MODULE, ROUND NECK ADAPTER STEEL NO 1 A, B, C B TITUS PAR RETURN 24x24 FLUSH PERFORATED FACE, STEEL YES 1 A, B, C C TITUS 272RS SUPPLY 3/4" BLADE SPACING, DOUBLE DEFLECTION, ADJUSTABLE BLADES STEEL YES 1 A, B, C D TITUS 350RL RETURN RETURN GRILLE, 3/4" SPACING, 35° DEFLECTION, STEEL CONSTRUCTION. STEEL YES 1 A, B, C FAN COIL UNIT ACCESSORIES: 1) VERTICAL FAN COIL UNIT CONFIGURATION, 2) ROUTE CONDENSATE DRAIN TO DRAIN IN MECHANICAL ROOM, 3) 7-DAY PROGRAMMABLE ACO THERMOSTAT, 4) PROVIDE STAND-OFF FILTER RACK KIT WITH 1" THROWAWAY FILTER, 5) FACTORY INSTALLED HEATER PACKAGE: PART NUMBER KFCEH2001318, 6) MICROMETL GENERAL PURPOSE MIXING BOX AND CONTROLS FOR OUTSIDE AIR ECONOMIZER, MODEL NUMBER MB-GP-2000, 69 LBS. INCLUDES DRY BULB SENSOR, HONEYWELL CONTROLLER, 7) ACCEPTABLE ALTERNATE MANUFACTURERS ARE TRANE, YORK, AND DAIKEN. TAG MANUF MODEL HEATING COIL (KW) AIRFLOW ELEC. DATA OFFICE 110 EXAM 111 EXAM 112 CORRIDOR 102 PRE-EXAM 107 EXAM 109 EXAM 108 4 3 2 1 A B C MAIN ENTRY 100 ELEC/DATA 104 LAB 105 RR 106 A 65 6"ø A 70 6"ø C 200 8x6 D 200 10x6 12"x10" 10"x8" B 70 6x6 C 320 D 12x6 320 14x6 C 200 8x6 C 185 8x6 A 40 6"ø A 50 6"ø 4 3 C MECH/WATER 103 24"x20" (2" LNR) 22"x16" (2" LNR) C 150 8x6 2 EF 2 1 C 30 6x6 1 FCU 141 S. Broadway, Suite 202 Denver, Colorado 80209 303 640 3173 open studio | architecture scale: checked by: OSA project no.: copyright: 2015 open studio | architecture architect: project: sheet title: original issue date: FOR CONSTRUCTION original issue description: 1" = 1'-0" 12/18/2015 11:40:31 AM M3.01 ENLARGED MECHANICAL New Belgium Brewing Medical Clinic Checker 2015-004 PRICING AND PERMIT 602 Buckingham St. Fort Collins, CO 80524 DEC. 18, 2015 New Belgium Brewing Medical Clinic Rev. Description Date 1" = 1'-0" 1 ENLARGED FLOOR PLAN - MECHANICAL WORK NOTES (THIS SHEET ONLY) 1 TERMINATION THROUGH WALL. PROVIDE WALL CAP, BIRDSCREEN, AND BACKDRAFT DAMPER. 2 18x18 OUTSIDE AIR LOUVER. PROVIDE BIRDSCREEN, BALANCING DAMPER, AND MOTORIZED DAMPER. 0' 1' 2' 3' N 3 PROVIDE FINAL TRANSITIONS FROM RETURN AIR AND OUTSIDE AIR DUCTS TO OUTSIDE AIR ECONOMIZER. 3 Page 9 of 9 C 100 6x6 C 100 6x6 18"x12" 14"x12" 12"x10" 6"x8" 8"x8" 10"x8" D 500 12x12 8"x8" 20"x14" 1 HP B 100 6x6 16"x14" 20"x16" 22"x14" T 1 A 340 12"ø M3.01 1 D 295 14x6 B 100 6x6 B 0 6x6 65 TO FCU-1 2 EF 1 6"x6" 24"x16" D 1850 24x16 24"x16" 30"x16" 1/4" = 1'-0" 1 FLOOR PLAN - MECHANICAL 141 S. Broadway, Suite 202 Denver, Colorado 80209 303 640 3173 open studio | architecture scale: checked by: OSA project no.: copyright: 2015 open studio | architecture architect: project: sheet title: original issue date: FOR CONSTRUCTION original issue description: 1/4" = 1'-0" 12/18/2015 11:40:31 AM M2.01 FLOOR PLAN - MECHANICAL New Belgium Brewing Medical Clinic ABT 2015-004 PRICING AND PERMIT 602 Buckingham St. Fort Collins, CO 80524 DEC. 18, 2015 New Belgium Brewing Medical Clinic 0' 4' 8' 12' WORK NOTES (THIS SHEET ONLY) 1 30x16 LOUVER WITH PLENUM BOX AND 24x16 CONNECTION FOR OA ECONOMIZER PRESSURE RELIEF AND 6x6 EXHAUST AIR CONNECTION. PROVIDE COUNTER BALANCED BACKDRAFT DAMPER SET TO 0.05" W.C. WITH BIRDSCREEN. 2 PROVIDE 1" DOOR UNDERCUT. Rev. Description Date Page 8 of 9 INDOOR WEIGHT SUPPLY ACCESSORIES TAG AIR CFM OA CFM ESP ("W.C.) VOLTS/ø BLOWER HP MCA MOCP FCU-1 CARRIER FX4DNB061L00 18 1850 150 0.65 208/3 3/4 55.5 60 300 1 THRU 7 FCU-1 HEAT PUMP (CONDENSING UNIT) ACCESSORIES: 1) REFRIGERANT LINE SET KIT, 2) PROVIDE HARD-START COMPONENTS, 3) SIGHT GLASS, 4) FILTER/DRYER, 5) ISOLATION PAD, 6) TXV, 7) HAIL GUARD, 8) ACCEPTABLE ALTERNATE MANUFACTURERS ARE TRANE, YORK, AND DAIKEN. TAG MANUF. MODEL SERVICE COOLING NET TOTAL/SENSIBLE CAP. (MBH) HEATING CAP. (MBH) SEER EER HSPF HP ELEC. DATA WEIGHT ACCESSORIES TAG VOLTS/ø MCA MOCP HP-1 CARRIER 25HHA460A005 FCU-1 54.95/ 54.01 57.71 14.0 11.5 8.2 208/3 23 40 325 1 THRU 8 HP-1 FAN COIL UNIT TYPICAL GRADE FLOOR TYPICAL HOUSEKEEPING PAD, THERMAL EXPANSION VALVE SIGHT GLASS FILTER/DRYER SUCTION LIQUID REFRIGERANT PIPES SIZED PER MANUFACTURER'S RECOMMENDATIONS TRAP ONLY PER MANUFACTURER'S RECOMMENDATIONS CAULK AROUND INSULATION WITH SILICONE BASED CAULK CONCEALED IN WALL F X ADD ON COOLING COIL, TYPICAL CONDENSATE DRAIN VENT 3/4" D TO FLOOR DRAIN WITH CONDENSATE NEUTRALIZATION DEVICE CU X NONE TYPICAL OF ALL UNITS UNLESS NOTED OTHERWISE 2 M0.02 FLOOR BALANCE OA TO AIR QUANTITY IN FAN COIL UNIT SCHEDULE OA DUCT WITH 2" EXTERNAL INSULATION F X NONE TYPICAL OF ALL UNITS UNLESS NOTED OTHERWISE 1 M0.02 SA DUCT WITH EXTERNAL INSULATION AND/OR INTERNAL LINER PER DUCT SYSTEM NOTES HOUSEKEEPING PAD, TYPICAL CONDENSING UNIT RA DUCT WITH LINER PER DUCT SYSTEM NOTES, TERMINATE IN ADJACENT PLENUM WITH BIRDSCREEN OVER OPENING NOTES: 1) SEE MECH PLANS FOR DUCT SIZES (TYP) ROUTE SA DUCT ABOVE ADJACENT CEILINGS, RE: FLOOR PLANS FOR ROUTING ROUTE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS UP TO CONCENTRIC VENT KIT AT ROOF. 141 S. Broadway, Suite 202 Denver, Colorado 80209 303 640 3173 open studio | architecture scale: checked by: OSA project no.: copyright: 2015 open studio | architecture architect: project: sheet title: original issue date: FOR CONSTRUCTION original issue description: 12" = 1'-0" 12/18/2015 11:40:30 AM M0.02 SCHEDULES New Belgium Brewing Medical Clinic ABT 2015-004 PRICING AND PERMIT 602 Buckingham St. Fort Collins, CO 80524 DEC. 18, 2015 New Belgium Brewing Medical Clinic Rev. Description Date Page 7 of 9 EXCEPTION: INSULATED FLEXIBLE DUCT MAY BE USED FOR CONCEALED CONNECTIONS TO THE AIR OUTLET PROVIDED THE LENGTH OF THE FLEXIBLE DUCT DOES NOT EXCEED 6 LINEAR FEET. 5. ALL BRANCH DUCT CONNECTIONS TO AIR OUTLETS AND AIR INLETS SHALL BE THE SAME SIZE AS THE DEVICE NECK UNLESS SHOWN OTHERWISE ON THE DRAWINGS. THICKNESS DENSITY (") LINER/ WRAP SYSTEM EXHAUST NONE N/A N/A N/A RETURN NONE N/A N/A N/A SUPPLY WRAP 2 3/4 R-5 FSK VAPOR BARRIER SUPPLY WRAP 2 3/4 R-6 RETURN LINER 2 1-1/2 R-5 SUPPLY LINER 2 1-1/2 R-5 MINIMUM R-VALUE NOTES FSK VAPOR BARRIER FORT COLLINS GREEN AMENDMENTS NOV 13, 2015 DESIGN DEVELOPMENT (LBS/FT ³) DEC 18, 2015 PRICING AND PERMIT SET 17. CONTRACTOR TO PROVIDE AS-BUILT DRAWINGS, OPERATION AND MAINTENANCE MANUALS, AND BALANCING REPORTS AT PROJECT COMPLETION. 16. PROVIDE METAL JACKETING ON OUTDOOR REFRIGERANT PIPING FOR PROTECTION FROM WEATHER DAMAGE. DRAWING INDEX, LEGENDS AND NOTES DRAWING NUMBER M0.01 DRAWING TITLE REVISIONS M2.01 FLOOR PLAN - MECHANICAL WORK NOTE 1, REVISION NO. 1, DEMOLITION NOTE 1, POINT OF CONNECTION SUPPLY, RETURN, EXHAUST, OUTSIDE, COMBUSTION AIR AND MAKE-UP AIR SUPPLY AIR, RETURN AIR/EXHAUST AIR/OUTSIDE AIR FLOW ARROWS THERMOSTAT, HUMIDISTAT, SMOKE DETECTOR, BAROMETRIC, MOTORIZED AND MANUAL DAMPERS FIRE, SMOKE AND COMBINATION FIRE AND SMOKE DAMPERS NORMALLY CLOSED, NORMALLY OPEN PIPING TO BE REMOVED ACCESS PANEL, ACCESS PANEL IN DUCT TEMPERATURE TRANSMITTER, AIR QUALITY SENSOR DOWN AND BACK UP UNDER BEAM OR OBSTACLE SUPPLY AIR, RETURN/OUTSIDE AIR AND EXHAUST AIR DUCTWORK UNLINED AND DUCTWORK LINED FLEXIBLE AND RIGID ROUND DUCT PIPE ANCHOR, PIPE GUIDE, PIPE SLEEVE AUTOMATIC AIR / MANUAL AIR VENT, HOSE END DRAIN VALVE PIPE ELBOW DOWN, PIPE TEE DOWN, PIPE TEE UP, PIPE ELBOW UP SQUARE DUCT ELBOW WITH TURNING VANES FLEX CONNECTION, PIPE EXPANSION JOINT ANGLE, RELIEF VALVE, GAUGE AND COCK, THERMOMETER ISOLATION VALVE (RE: SPECIFICATION FOR TYPE) BALANCING VALVE, CALIBRATED, DYNAMIC BALANCING VALVES LUBRICATED PLUG VALVE, PRESSURE REDUCING VALVE THREE WAY CONTROL VALVE, SOLENOID AND TWO-WAY / MOTORIZED CONTROL VALVE HEATING WATER SUPPLY AND RETURN PIPING DESCRIPTION HWS, HWR HWS HWR EQUIPMENT NUMBER EQUIPMENT TYPE RTU X EQUIPMENT TAG R-RTU-ROOF TOP M-MAU-MAKE UP AIR UNIT UNIT 1 M-1 R-1 M-1 1 1 AP SA,RA,EA,OA,CA,MA NC, NO RE: VFD AP T, H, SD, TT, AQ AP AAV / MAV, HEV (R/D) X" ~ (R/D) TP HEV PRV S C M D SECTION A ON SHEET M-1 DIAGRAM 1 ON SHEET M-1 RISER R-1 ON SHEET M-1 VARIABLE FREQUENCY DRIVE REFERENCE DUCTWORK TO BE REMOVED TEST PLUG CHECK VALVE, STRAINER UNION, FLANGE, BLIND FLANGE HEAT TRACE TAPE ABBR. SYMBOL SPIN-IN WITH REMOTE DAMPER ACTUATOR SPIN-IN WITH QUADRANT DAMPER, SPIN-IN WITHOUT DAMPER, THROW DIFFUSER 1-WAY DIRECTIONAL THROW DIFFUSER 4-WAY DIRECTIONAL 3-WAY DIRECTIONAL THROW DIFFUSER 2-WAY DIRECTIONAL THROW DIFFUSER EXISTING DIFFUSER REBALANCE EXISTING DIFFUSER RELOCATE AND AIR QUANTITY DIFFUSER TYPE REB XXX AIR QUANTITY REBALANCE XXX COUNT ON PLANS) REL NECK SIZE QUANTITY (VERIFY EXACT X X"ø XXX (X) DIFFUSER TAG A M-1 CW, HW DOMESTIC COLD WATER AND HOT WATER SD, OSD SD OSD STORM DRAIN AND OVERFLOW STORM DRAIN PIPING AIR QUANTITY ROUND SHEET TRANSITION METAL DUCTWORK RETURN GRILLE SQUARE ELBOW WITH TURNING SAME SIZE AS DIFFUSER INLET UNLESS NOTED OTHERWISE WITH TAG VANES 10"ø B 8"ø 250 N FLEXIBLE DUCTWORK WITH EXTERNAL INSULATION (5' MAXIMUM LENGTH) CEILING DIFFUSER LINEAR DIFFUSER RECTANGULAR SHEET METAL DUCTWORK CONICAL SPIN-IN FITTING WITH QUADRANT DAMPER CONICAL SPIN-IN FITTING WITH REMOTE DAMPER ACTUATOR B 4 LF/8"ø 250 SUPPLY GRILLE WITH 45 DEGREE ENTRY BRANCH AND M.V.D. M0.02 SCHEDULES X EXISTING EQUIPMENT TAG EQUIPMENT NUMBER M3.01 ENLARGED MECHANICAL 141 S. Broadway, Suite 202 Denver, Colorado 80209 303 640 3173 open studio | architecture scale: checked by: OSA project no.: copyright: 2015 open studio | architecture architect: project: sheet title: original issue date: FOR CONSTRUCTION original issue description: 12" = 1'-0" 12/18/2015 11:40:29 AM M0.01 DRAWING INDEX, LEGENDS AND NOTES New Belgium Brewing Medical Clinic ABT 2015-004 PRICING AND PERMIT 602 Buckingham St. Fort Collins, CO 80524 DEC. 18, 2015 New Belgium Brewing Medical Clinic Rev. Description Date Page 6 of 9 Motor Volts 1 121 Volts Motor Amps 1 0.5 Amps SP In Actual 0.0 in. wc SP Out Actual 0.02 in. wc Total SP Actual 0.02 in. wc Motor Data Motor Manufacturer ANA Motor HP NS HP Motor RPM NS RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.1 Amps Sheave Data Motor Sheave Make Direct Drive L.H. Finn and Associates Final Report Page 5 of 9 Deviation % Final Deviation Outlet-01 107 C 12x6 320 294 318 92 99 Outlet-02 110 A 24x24 200 194 196 97 98 Outlet-03 111 A 24x24 70 79 69 113 99 Outlet-04 112 A 24x24 65 76 66 117 102 Outlet-05 102 C 8x6 200 159 197 80 99 Outlet-06 100 A 24x24 340 289 342 85 101 Outlet-07 100 C 8x6 185 230 184 124 99 Outlet-08 109 A 24x24 100 63 98 63 98 Outlet-09 108 A 24x24 100 47 100 47 100 Outlet-10 105 A 24x24 50 66 50 132 100 Outlet-11 106 A 24x24 40 58 39 145 98 Outlet-12 100 C 8x6 150 281 148 187 99 Outlet-13 104 C 8x6 30 56 30 187 100 Totals: - - - 1850 1892 1837 102 99 L.H. Finn and Associates Final Report Page 3 of 9