HomeMy WebLinkAbout602 Buckingham St - Special Inspections/Field Verification - 11/08/2016Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave., Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
11/8/16
PROJECT
New Belgium Brewing Medical Clinic
602 Buckingham Street
Fort Collins, CO 80524
ARCHITECT
Open Studio Architecture
141 S. Broadway, Suite 202
Denver, CO 80209
ENGINEER
A.E. Associates
5587 W. 19
th
Street
Greeley, CO 80634
CONTRACTOR
Air Comfort, Inc.
150 Rome Ct.
Fort Collins, CO 80524
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
PROJECT: New Belgium Brewing Medical Clinic
ADDRESS: 602 Buckingham Street, Fort Collins, CO 80524
The data presented in this report is an exact record of the system performance
and was obtained in accordance with NEBB Standard Procedures. Any
variances from design quantities which exceed NEBB tolerances are noted
throughout the report.
The air distribution systems have been tested & balanced and final adjustments
have been made in accordance with NEBB “Procedural Standards for Testing,
Adjusting & Balancing of Environmental Systems” and the project specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:11/8/16
The hydronic distribution systems have been tested & balanced and final
adjustments have been made in accordance with NEBB “Procedural Standards
for Testing, Adjusting & Balancing of Environmental Systems” and the project
specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:11/8/16
SUBMITTED & CERTIFIED BY
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
TAB SUPERVISOR: David C. Reichel
REG. NO.: 2389 SIGNATURE:
DATE: 11/8/16 CERTIFICATION EXPIRATION DATE: 3/31/2018
Table Of Contents
PROJECT:
LOCATION:
New Belgium Brewing Medical Clinic
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
11/8/2016
Emerson Moore
Emerson Moore
Table Of Contents
1 Instrument Calibration Report.pdf................................................................................................................................. 1
2 Abbreviation Report.pdf................................................................................................................................................ 2
3 Fan Coil........................................................................................................................................................................ 3
3.1 FCU-01................................................................................................................................................................... 3
4 Fan Unit........................................................................................................................................................................ 5
4.1 EF-01...................................................................................................................................................................... 5
4.2 EF-02...................................................................................................................................................................... 5
5 Mech Prints.pdf............................................................................................................................................................. 6
5.1 LG001.....................................................................................................................................................................
5.2 LD101.....................................................................................................................................................................
5.3 LS100......................................................................................................................................................................
5.4 LS101......................................................................................................................................................................
5.5 LS501......................................................................................................................................................................
5.6 LP001......................................................................................................................................................................
5.7 LP100......................................................................................................................................................................
5.8 LP501......................................................................................................................................................................
L.H. Finn and Associates
Final Report
Project: New Belgium Brewing Medical Clinic
Manufacturer Model Serial Application Cal. Date
Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014
Alnor HM-680 70750150 Hydronic Press. & Diff. Press. 12/14/2015
Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015
Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016
Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 6/10/2015
Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 4/10/2015
Cooper SH66A 92711016 Temperature 4/10/2015
Extech 461895 Q394479 Rotation Measurement 10/12/2015
Extech 461895 Q083481 Rotation Measurement 1/9/2014
Extech 461895 Q247569 Rotation Measurement 3/8/2016
Extech 461895 L268576 Rotation Measurement 3/8/2016
Extech 461895 Q331990 Rotation Measurement 11/4/2014
Extech 461895 Q477125 Rotation Measurement 9/25/2015
Extech 461895 Q477126 Rotation Measurement 4/5/2016
Extech 461895 Q527632 Rotation Measurement 4/8/2015
Extech 461895 Q590099 Rotation Measurement 10/12/2015
Extech RH390 9099221 Temperature / Humidity 4/9/2015
Fluke 335 96960004 Electrical Measurement 11/5/2015
Fluke 336 97110539R Electrical Measurement 4/5/2016
Fluke 336 97110538R Electrical Measurement 9/29/2015
Fluke 335 92008180 Electrical Measurement 11/4/2014
Fluke 335 12990071 Electrical Measurement 3/4/2016
Fluke 374 15460133 Electrical Measurement 4/18/2014
Fluke 374 20030351 Electrical Measurement 4/8/2015
Fluke 374 20030354 Electrical Measurement 10/23/2015
Shortridge ADM-860C M05789 Digital Manometer 11/25/2015
Shortridge ADM-860C M06821 Digital Manometer 10/12/2015
Shortridge ADM-860C M07352 Digital Manometer 6/6/2016
Shortridge ADM-860C M09123 Digital Manometer 4/18/2016
Shortridge ADM-860C M09347 Digital Manometer 9/26/2015
Shortridge ADM-860C M10144 Digital Manometer 11/18/2014
Shortridge ADM-860C M10371 Digital Manometer 11/5/2015
Shortridge ADM-860C M11448 Digital Manometer 4/15/2016
Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015
Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 10/12/2015
Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015
REMARKS: Not all equipment shown was used on this project.
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
INSTRUMENT CALIBRATION REPORT
Page 1 of 9
Project: New Belgium Brewing Medical Clinic
Symbol Description Symbol Description
A Airflow (L/S) NS Not Shown
AF Air Foil NT No Information Tag
ANA Access Not Available OD Outside Diameter
BI Backward Incline RPM Revolution Per Minute
CD Ceiling Diffuser SD Supply Diffuser
CFM Airflow (Cubic Feet / Minute) SNKL Snorkel
DD Direct Drive SP Static Pressure
Des Design SPD Static Pressure Drop
DWDI Double Width Double Inlet SR Supply Register
EF Exhaust Fan SWSI Single Width Single Inlet
EG Exhaust Grille T Temperature ( C )
ER Exhaust Register T Temperature ( F )
ESP External Static Pressure TSP Total Static Pressure
FC Forward Curve VFD Variable Frequency Drive
GPM Waterflow (Gallons / Minute) VS Variable Speed
HC Heat Coil W Waterflow (L/S)
HER Heat Exchanger
HRC Heat Recovery
Hz Hertz
ID Inside Diameter
In. WC Inches of Water Column
NA Not Applicable
NI Not Installed
NIC Not In Contract
NM Not Measurable
NPT No Pressure Tap
NR Not Readable
REMARKS:
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
ABBREVIATION REPORT
Page 2 of 9
Fan Coil
PROJECT:
LOCATION:
New Belgium Brewing Medical Clinic
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
11/8/2016
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 11/7/2016
SYSTEM/UNIT: FCU-01
Unit Data
Unit Manufacturer Carrier
Unit Model Number FX4DNB061
Unit Serial Number 4016A85188
Filter Type MERV-8
Filter Qty 1
Filter Size 23x20x4
Test Data
Total CFM Design 1850 CFM
Total CFM Actual 1837 CFM
Outside Air CFM Design 150 CFM
Outside Air CFM Actual 162 CFM
Return Air CFM Design 1700 CFM
Return Air CFM Actual 1675 CFM
Motor Volts T1-T2 212 Volts
Amps T1 5.4 Amps
Fan RPM Actual High Speed RPM
Fan SP In -0.75 In. wc.
Fan SP Out 0.14 In. wc.
Unit E.S.P. Actual 0.41 In. wc.
E.S.P. In -0.27 In. wc.
E.S.P. Out 0.14 In. wc.
Filter SP In -0.27 In. wc.
Filter SP Out ANA In. wc.
Coil SP In ANA In. wc.
Coil SP Out -0.75 In. wc.
Motor Data
Motor Manufacturer Genteq
Motor Frame NS
Motor HP 3/4
Motor RPM 1050 (3 spd) RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Service Factor NS
Motor Rated Volts 208-230
Motor FL Amps 6.0 Amps
Sheave Data
Motor Sheave Make Direct Drive
FCU-01 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Fan Coil
PROJECT:
LOCATION:
New Belgium Brewing Medical Clinic
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
11/8/2016
Emerson Moore
Emerson Moore
FCU-01 Return Inlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 110 B 24x24 200 126 206 63 103
Inlet-B 111 B 24x24 70 83 74 119 106
Inlet-C 107 D 14x6 320 339 330 106 103
Inlet-D 112 B 24x24 65 98 69 151 106
Inlet-E 102 D 14x6 295 475 298 161 101
Inlet-F 100 D 12x12 500 103 492 21 98
Inlet-G 109 B 24x24 100 74 102 74 102
Inlet-H 108 B 24x24 100 143 104 143 104
Totals: - - - 1650 1441 1675 87 102
L.H. Finn and Associates
Final Report Page 4 of 9
Fan Unit
PROJECT:
LOCATION:
New Belgium Brewing Medical Clinic
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
11/8/2016
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 11/7/2016
SYSTEM/UNIT: EF-01
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number T100
Fan Type Forward Curve
Fan Size 6"ID
Fan Class 1
Fan Arrangement DWDI
Fan Discharge Horizontal
Starter Data
Installed Thermal Internal
Test Data
Total CFM Design 75 CFM
Total CFM Actual 79 CFM
Fan RPM Actual Direct Drive RPM
Motor Volts 1 121 Volts
Motor Amps 1 0.4 Amps
SP In Actual 0.0 in. wc
SP Out Actual 0.04 in. wc
Total SP Actual 0.04 in. wc
Motor Data
Motor Manufacturer ANA
Motor HP NS HP
Motor RPM NS RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 1.1 Amps
Sheave Data
Motor Sheave Make Direct Drive
Tested By: Emerson Moore
Date: 11/7/2016
SYSTEM/UNIT: EF-02
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number T100
Fan Type Forward Curve
Fan Size 6"ID
Fan Class 1
Fan Arrangement DWDI
Fan Discharge Horizontal
Starter Data
Installed Thermal Internal
Test Data
Total CFM Design 75 CFM
Total CFM Actual 82 CFM
Fan RPM Actual Direct Drive RPM
T H
AAV, MAV
B
F
M
S FS
24x18
SD TT AQ
1
DUCTWORK LEGEND -
CONSTANT VOLUME SYSTEMS
LEGEND DRAWING INDEX
MECHANICAL GENERAL NOTES
CODE INFORMATION
DUCT SYSTEM NOTES
(NOT ALL ITEMS WILL BE USED)
1. RESOLVE ALL QUESTIONS OR CONFLICTS WITH ENGINEER BEFORE ANY EQUIPMENT IS ORDERED, MATERIALS FABRICATED OR SYSTEMS INSTALLED.
2. COORDINATE THE INSTALLATION OF MECHANICAL SYSTEMS WITH OTHER TRADES. PROVIDE OFFSETS AS NECESSARY TO ACCOMMODATE STRUCTURE AND
4. COORDINATE AND VERIFY THAT ALL OPENINGS IN WALLS ABOVE CEILING / DOOR LOUVERS / DOOR UNDERCUTS ARE PROVIDED AS INDICATED ON THESE
DRAWINGS.
5. COORDINATE EXACT SIZE OF EQUIPMENT HOUSEKEEPING PAD WITH EQUIPMENT OVERALL FOOTPRINT DIMENSIONS.
6. LEVEL ALL EQUIPMENT CURBS / BASES PRIOR TO INSTALLATION OF ANY EQUIPMENT.
8. SEAL ALL ROOF PENETRATIONS IN ACCORDANCE WITH ROOF MANUFACTURER'S RECOMMENDATIONS. SEAL ALL WALL PENETRATIONS WATERTIGHT WITH
9. PROVIDE ACCESS PANELS (MIN. 24"x24") IN "HARD" CEILINGS PER CODE FOR ACCESS TO ALL MOTORS, CONTROLS, BALANCING DAMPERS, FIRE DAMPERS,
COMBINATION FIRE / SMOKE DAMPERS AND OTHER MECHANICAL EQUIPMENT.
10. LABEL ALL MECHANICAL DEVICES (VALVES, F/S DAMPERS, ETC.) ABOVE LAY-IN CEILING ON GRID BELOW DEVICE WITH PRINTED SELF ADHESIVE LABEL.
11. LOCATION OF ALL CEILING INLETS AND OUTLETS ARE APPROXIMATE. COORDINATE LOCATION WITH EXISTING LIGHT FIXTURES AND ARCHITECT, ETC.
12. INSTALL FLEXIBLE CONNECTORS AT ALL DUCT CONNECTIONS TO MECHANICAL EQUIPMENT, INCLUDING FAN COIL UNITS.
13. MAKE ALLOWANCES IN HARD CEILING AREAS FOR SPIN-IN FITTING WITH REMOTE DAMPER ACTUATOR.
14. VERIFY ALL DIMENSIONS AND JOB CONDITIONS. REPORT TO THE ENGINEER ANY DISCREPANCIES OR OMISSIONS WHICH WOULD INTERFERE WITH THE
SATISFACTORY COMPLETION OF WORK.
15. CLOSE ALL PIPE AND DUCT OPENINGS WITH CAPS OR PLUGS DURING INSTALLATION. PROTECT ALL FIXTURES AND EQUIPMENT AGAINST DIRT,
WATER, CHEMICAL, AND MECHANICAL DAMAGE.
16. ALL WORK AND MATERIALS TO CONFORM WITH THE REQUIREMENTS OF ALL APPLICABLE BUILDING AND FIRE CODES AND ALL AUTHORITIES
HAVING JURISDICTION.
OTHER TRADES. COORDINATE ANY PENETRATIONS THROUGH STRUCTURAL MEMBERS WITH STRUCTURAL ENGINEER.
ISSUED FOR CONSTRUCTION
ISSUED FOR REFERENCE ONLY, NOT FOR CONSTRUCTION
SILICONE CAULKING AND BACKER ROD.
2012 INTERNATIONAL BUILDING CODE
2012 INTERNATIONAL PLUMBING CODE
2012 INTERNATIONAL FUEL GAS CODE
2012 INTERNATIONAL FIRE CODE
2012 INTERNATIONAL ENERGY CONSERVATION CODE
INSULATION SCHEDULE
WITHIN 15 LINEAR FEET (OR AS NOTED) OF
FAN COIL UNITS
UNTREATED OUTSIDE AIR DUCT
ALL OTHER SUPPLY
ALL OTHER RETURN WITHIN A RETURN PLENUM
ALL EXHAUST
1. ALL DUCTWORK UNLESS SPECIFICALLY INDICATED SHALL BE GALVANIZED SHEET METAL INSTALLED AT A MINIMUM, IN ACCORDANCE WITH THE SMACNA DUCT
CONSTRUCTION STANDARDS.
2. CLASSIFICATION:
ALL DUCTWORK - PRESSURE CLASS +2" W.C., SEAL CLASS B.
2. ALL DUCTWORK JOINTS SHALL HAVE DUCTMATE "35", TDC, "HARDCAST" OR OTHER APPROVED SEALER.
3. DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS.
4. ROUND DUCTWORK
CONCEALED, 12" AND SMALLER, +2" W.C. TO -1" W.C. PRESSURE CLASS: GALVANIZED SHEET METAL SNAP-LOCK.
ALL OTHER: GALVANIZED SHEET METAL SPIRAL.
SCALE:
SCALE:
M
SPLIT SYSTEM PIPING
SCHEMATIC
FAN COIL UNIT
INSTALLATION DIAGRAM
MOTORIZED DAMPER
INTERLOCKED TO FAN COIL
UNIT OPERATION
FLEXIBLE
CONNECTION (TYP)
PROVIDE EXTERNAL FILTER RACK AND
FINAL TRANSITION TO FAN COIL UNIT.
EXHAUST FAN SCHEDULE
NOTES: A) INTERLOCK WITH LIGHT SWITCH, B) RUNS ON PROGRAMMABLE TIME CLOCK ACCESSORIES: 1) FAN SPEED CONTROLLER, 2) PLUG TYPE DISCONNECT, 3) VIBRATION ISOLATORS, 4)
ACCEPTABLE ALTERNATE MANUFACTURERS ARE COOK, GREENHECK, AND ACME.
TAG MANUF. MODEL LOCATION SERVICE
FAN DATA MOTOR DATA
OPER.
WEIGHT
(LBS)
AIR NOTES ACCESSORIES TAG
QTY.
(CFM)
ESP
("W.C.)
TYPE RPM MOUNT DRIVE BHP HP VOLTS/ø VFD
EF-1
TWIN
CITY
T-100 CEILING RESTROOM 75 0.25 CABINET 640 CEILING DIRECT 0.08 1/8 115/1 NO 30 A 1, 2, 3, 4 EF-1
EF-2
TWIN
CITY
T-100 CEILING MECH/WATER 75 0.25 CABINET 640 CEILING DIRECT 0.08 1/8 115/1 NO 30 B 1, 2, 3, 4 EF-2
GRILLE REGISTER AND DIFFUSER SCHEDULE
FINISH: 1) FACTORY FINISH TO BE SELECTED BY
ARCHITECT
A) SEE DRAWINGS FOR NECK SIZE AND AIR QUANTITY, B) PROVIDE FRAME COMPATIBLE WITH
MOUNTING LOCATION, C) ACCEPTABLE ALTERNATE MANUFACTURERS ARE PRICE, METALAIRE, AND
KREUGER.
TAG MANUF MODEL SYSTEM DESCRIPTION CONSTRUCTION OBD FINISH NOTES
A TITUS TDC SUPPLY 18x18 FLUSH LOUVERED FACE, 24x24 MODULE, ROUND NECK ADAPTER STEEL NO 1 A, B, C
B TITUS PAR RETURN 24x24 FLUSH PERFORATED FACE, STEEL YES 1 A, B, C
C TITUS 272RS SUPPLY 3/4" BLADE SPACING, DOUBLE DEFLECTION, ADJUSTABLE BLADES STEEL YES 1 A, B, C
D TITUS 350RL RETURN
RETURN GRILLE, 3/4" SPACING, 35° DEFLECTION, STEEL
CONSTRUCTION.
STEEL YES 1 A, B, C
FAN COIL UNIT
ACCESSORIES: 1) VERTICAL FAN COIL UNIT CONFIGURATION, 2) ROUTE CONDENSATE DRAIN TO DRAIN IN MECHANICAL ROOM, 3) 7-DAY PROGRAMMABLE ACO THERMOSTAT, 4)
PROVIDE STAND-OFF FILTER RACK KIT WITH 1" THROWAWAY FILTER, 5) FACTORY INSTALLED HEATER PACKAGE: PART NUMBER KFCEH2001318, 6) MICROMETL GENERAL PURPOSE
MIXING BOX AND CONTROLS FOR OUTSIDE AIR ECONOMIZER, MODEL NUMBER MB-GP-2000, 69 LBS. INCLUDES DRY BULB SENSOR, HONEYWELL CONTROLLER, 7) ACCEPTABLE ALTERNATE
MANUFACTURERS ARE TRANE, YORK, AND DAIKEN.
TAG MANUF MODEL
HEATING
COIL
(KW)
AIRFLOW ELEC. DATA
OFFICE
110
EXAM
111
EXAM
112
CORRIDOR
102
PRE-EXAM
107
EXAM
109
EXAM
108
4 3 2 1
A
B
C
MAIN ENTRY
100
ELEC/DATA
104
LAB
105
RR
106
A
65
6"ø
A
70
6"ø
C
200
8x6
D
200
10x6
12"x10"
10"x8"
B
70
6x6
C
320
D 12x6
320
14x6
C
200
8x6
C
185
8x6
A
40
6"ø
A
50
6"ø
4 3
C
MECH/WATER
103
24"x20" (2" LNR)
22"x16" (2" LNR)
C
150
8x6
2
EF
2
1
C
30
6x6
1
FCU
141 S. Broadway, Suite 202
Denver, Colorado 80209
303 640 3173
open studio | architecture
scale:
checked by:
OSA project no.:
copyright: 2015 open studio | architecture
architect:
project:
sheet title:
original issue date:
FOR
CONSTRUCTION
original issue description:
1" = 1'-0"
12/18/2015 11:40:31 AM
M3.01
ENLARGED MECHANICAL
New Belgium Brewing
Medical Clinic
Checker
2015-004
PRICING AND PERMIT
602 Buckingham St.
Fort Collins, CO 80524
DEC. 18, 2015
New Belgium
Brewing Medical
Clinic
Rev. Description Date
1" = 1'-0"
1
ENLARGED FLOOR PLAN - MECHANICAL
WORK NOTES (THIS SHEET ONLY)
1 TERMINATION THROUGH WALL. PROVIDE WALL CAP,
BIRDSCREEN, AND BACKDRAFT DAMPER.
2 18x18 OUTSIDE AIR LOUVER. PROVIDE BIRDSCREEN,
BALANCING DAMPER, AND MOTORIZED DAMPER.
0' 1' 2' 3'
N
3 PROVIDE FINAL TRANSITIONS FROM RETURN AIR AND
OUTSIDE AIR DUCTS TO OUTSIDE AIR ECONOMIZER.
3
Page 9 of 9
C
100
6x6
C
100
6x6
18"x12"
14"x12"
12"x10"
6"x8"
8"x8"
10"x8"
D
500
12x12
8"x8"
20"x14"
1
HP
B
100
6x6
16"x14"
20"x16"
22"x14"
T
1
A
340
12"ø
M3.01
1
D
295
14x6
B
100
6x6
B
0
6x6
65
TO FCU-1
2
EF
1
6"x6"
24"x16"
D
1850
24x16
24"x16"
30"x16"
1/4" = 1'-0"
1
FLOOR PLAN - MECHANICAL
141 S. Broadway, Suite 202
Denver, Colorado 80209
303 640 3173
open studio | architecture
scale:
checked by:
OSA project no.:
copyright: 2015 open studio | architecture
architect:
project:
sheet title:
original issue date:
FOR
CONSTRUCTION
original issue description:
1/4" = 1'-0"
12/18/2015 11:40:31 AM
M2.01
FLOOR PLAN - MECHANICAL
New Belgium Brewing
Medical Clinic
ABT
2015-004
PRICING AND PERMIT
602 Buckingham St.
Fort Collins, CO 80524
DEC. 18, 2015
New Belgium
Brewing Medical
Clinic
0' 4' 8' 12'
WORK NOTES (THIS SHEET ONLY)
1 30x16 LOUVER WITH PLENUM BOX AND 24x16
CONNECTION FOR OA ECONOMIZER PRESSURE RELIEF
AND 6x6 EXHAUST AIR CONNECTION. PROVIDE
COUNTER BALANCED BACKDRAFT DAMPER SET TO 0.05"
W.C. WITH BIRDSCREEN.
2 PROVIDE 1" DOOR UNDERCUT.
Rev. Description Date
Page 8 of 9
INDOOR
WEIGHT
SUPPLY ACCESSORIES TAG
AIR CFM
OA CFM ESP ("W.C.) VOLTS/ø BLOWER HP MCA MOCP
FCU-1 CARRIER FX4DNB061L00 18 1850 150 0.65 208/3 3/4 55.5 60 300 1 THRU 7 FCU-1
HEAT PUMP (CONDENSING UNIT)
ACCESSORIES: 1) REFRIGERANT LINE SET KIT, 2) PROVIDE HARD-START COMPONENTS, 3) SIGHT GLASS, 4) FILTER/DRYER, 5) ISOLATION PAD, 6) TXV, 7) HAIL
GUARD, 8) ACCEPTABLE ALTERNATE MANUFACTURERS ARE TRANE, YORK, AND DAIKEN.
TAG MANUF. MODEL SERVICE
COOLING NET
TOTAL/SENSIBLE
CAP. (MBH)
HEATING
CAP. (MBH)
SEER EER HSPF HP
ELEC. DATA
WEIGHT ACCESSORIES TAG
VOLTS/ø MCA MOCP
HP-1 CARRIER 25HHA460A005 FCU-1 54.95/ 54.01 57.71 14.0 11.5 8.2 208/3 23 40 325 1 THRU 8 HP-1
FAN COIL UNIT
TYPICAL
GRADE FLOOR
TYPICAL
HOUSEKEEPING PAD,
THERMAL
EXPANSION
VALVE
SIGHT GLASS
FILTER/DRYER
SUCTION
LIQUID
REFRIGERANT PIPES SIZED PER MANUFACTURER'S RECOMMENDATIONS
TRAP ONLY PER MANUFACTURER'S
RECOMMENDATIONS
CAULK AROUND INSULATION
WITH SILICONE BASED CAULK
CONCEALED IN WALL
F
X
ADD ON COOLING
COIL, TYPICAL
CONDENSATE
DRAIN VENT
3/4" D TO FLOOR DRAIN
WITH CONDENSATE
NEUTRALIZATION DEVICE
CU
X
NONE TYPICAL OF ALL UNITS UNLESS NOTED OTHERWISE
2
M0.02
FLOOR
BALANCE OA TO AIR
QUANTITY IN
FAN COIL UNIT SCHEDULE
OA DUCT WITH
2" EXTERNAL
INSULATION
F
X
NONE TYPICAL OF ALL UNITS UNLESS NOTED OTHERWISE
1
M0.02
SA DUCT WITH EXTERNAL
INSULATION AND/OR
INTERNAL LINER PER DUCT
SYSTEM NOTES
HOUSEKEEPING PAD,
TYPICAL
CONDENSING UNIT
RA DUCT WITH LINER PER DUCT SYSTEM NOTES,
TERMINATE IN ADJACENT PLENUM WITH
BIRDSCREEN OVER OPENING
NOTES:
1) SEE MECH PLANS FOR DUCT SIZES (TYP)
ROUTE SA DUCT ABOVE ADJACENT CEILINGS,
RE: FLOOR PLANS FOR ROUTING
ROUTE IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS UP TO
CONCENTRIC VENT KIT AT ROOF.
141 S. Broadway, Suite 202
Denver, Colorado 80209
303 640 3173
open studio | architecture
scale:
checked by:
OSA project no.:
copyright: 2015 open studio | architecture
architect:
project:
sheet title:
original issue date:
FOR
CONSTRUCTION
original issue description:
12" = 1'-0"
12/18/2015 11:40:30 AM
M0.02
SCHEDULES
New Belgium Brewing
Medical Clinic
ABT
2015-004
PRICING AND PERMIT
602 Buckingham St.
Fort Collins, CO 80524
DEC. 18, 2015
New Belgium
Brewing Medical
Clinic
Rev. Description Date
Page 7 of 9
EXCEPTION: INSULATED FLEXIBLE DUCT MAY BE USED FOR CONCEALED CONNECTIONS TO THE AIR OUTLET PROVIDED THE LENGTH OF THE FLEXIBLE DUCT
DOES NOT EXCEED 6 LINEAR FEET.
5. ALL BRANCH DUCT CONNECTIONS TO AIR OUTLETS AND AIR INLETS SHALL BE THE SAME SIZE AS THE DEVICE NECK UNLESS SHOWN OTHERWISE ON THE
DRAWINGS.
THICKNESS DENSITY
(")
LINER/
WRAP
SYSTEM
EXHAUST NONE N/A N/A N/A
RETURN NONE N/A N/A N/A
SUPPLY WRAP 2 3/4 R-5 FSK VAPOR BARRIER
SUPPLY WRAP 2 3/4 R-6
RETURN LINER 2 1-1/2 R-5
SUPPLY LINER 2 1-1/2 R-5
MINIMUM R-VALUE NOTES
FSK VAPOR BARRIER
FORT COLLINS GREEN AMENDMENTS
NOV 13, 2015
DESIGN DEVELOPMENT
(LBS/FT ³)
DEC 18, 2015
PRICING AND PERMIT SET
17. CONTRACTOR TO PROVIDE AS-BUILT DRAWINGS, OPERATION AND MAINTENANCE MANUALS, AND BALANCING REPORTS AT PROJECT COMPLETION.
16. PROVIDE METAL JACKETING ON OUTDOOR REFRIGERANT PIPING FOR PROTECTION FROM WEATHER DAMAGE.
DRAWING INDEX, LEGENDS AND NOTES
DRAWING
NUMBER
M0.01
DRAWING TITLE
REVISIONS
M2.01 FLOOR PLAN - MECHANICAL
WORK NOTE 1, REVISION NO. 1, DEMOLITION NOTE 1, POINT OF CONNECTION
SUPPLY, RETURN, EXHAUST, OUTSIDE, COMBUSTION AIR AND MAKE-UP AIR
SUPPLY AIR, RETURN AIR/EXHAUST AIR/OUTSIDE AIR FLOW ARROWS
THERMOSTAT, HUMIDISTAT, SMOKE DETECTOR,
BAROMETRIC, MOTORIZED AND MANUAL DAMPERS
FIRE, SMOKE AND COMBINATION FIRE AND SMOKE DAMPERS
NORMALLY CLOSED, NORMALLY OPEN
PIPING TO BE REMOVED
ACCESS PANEL, ACCESS PANEL IN DUCT
TEMPERATURE TRANSMITTER, AIR QUALITY SENSOR
DOWN AND BACK UP UNDER BEAM OR OBSTACLE
SUPPLY AIR, RETURN/OUTSIDE AIR AND EXHAUST AIR
DUCTWORK UNLINED AND DUCTWORK LINED
FLEXIBLE AND RIGID ROUND DUCT
PIPE ANCHOR, PIPE GUIDE, PIPE SLEEVE
AUTOMATIC AIR / MANUAL AIR VENT, HOSE END DRAIN VALVE
PIPE ELBOW DOWN, PIPE TEE DOWN, PIPE TEE UP, PIPE ELBOW UP
SQUARE DUCT ELBOW WITH TURNING VANES
FLEX CONNECTION, PIPE EXPANSION JOINT
ANGLE, RELIEF VALVE, GAUGE AND COCK, THERMOMETER
ISOLATION VALVE (RE: SPECIFICATION FOR TYPE)
BALANCING VALVE, CALIBRATED, DYNAMIC BALANCING VALVES
LUBRICATED PLUG VALVE, PRESSURE REDUCING VALVE
THREE WAY CONTROL VALVE, SOLENOID
AND TWO-WAY / MOTORIZED CONTROL VALVE
HEATING WATER SUPPLY AND RETURN PIPING
DESCRIPTION
HWS, HWR HWS HWR
EQUIPMENT NUMBER
EQUIPMENT TYPE
RTU
X
EQUIPMENT TAG
R-RTU-ROOF TOP
M-MAU-MAKE UP
AIR UNIT
UNIT
1
M-1
R-1
M-1
1
1
AP
SA,RA,EA,OA,CA,MA
NC, NO
RE:
VFD
AP
T, H, SD, TT, AQ
AP
AAV / MAV, HEV
(R/D)
X" ~
(R/D)
TP
HEV
PRV
S
C
M
D
SECTION A ON SHEET M-1
DIAGRAM 1 ON SHEET M-1
RISER R-1 ON SHEET M-1
VARIABLE FREQUENCY DRIVE
REFERENCE
DUCTWORK TO BE REMOVED
TEST PLUG
CHECK VALVE, STRAINER
UNION, FLANGE, BLIND FLANGE
HEAT TRACE TAPE
ABBR. SYMBOL
SPIN-IN WITH REMOTE DAMPER ACTUATOR
SPIN-IN WITH QUADRANT DAMPER, SPIN-IN WITHOUT DAMPER,
THROW DIFFUSER
1-WAY DIRECTIONAL
THROW DIFFUSER
4-WAY DIRECTIONAL 3-WAY DIRECTIONAL
THROW DIFFUSER
2-WAY DIRECTIONAL
THROW DIFFUSER
EXISTING DIFFUSER
REBALANCE EXISTING DIFFUSER
RELOCATE AND
AIR QUANTITY
DIFFUSER TYPE
REB
XXX
AIR QUANTITY
REBALANCE
XXX
COUNT ON PLANS) REL
NECK SIZE
QUANTITY (VERIFY EXACT
X
X"ø
XXX
(X)
DIFFUSER TAG
A
M-1
CW, HW DOMESTIC COLD WATER AND HOT WATER
SD, OSD SD OSD STORM DRAIN AND OVERFLOW STORM DRAIN PIPING
AIR QUANTITY
ROUND SHEET
TRANSITION METAL DUCTWORK
RETURN GRILLE
SQUARE ELBOW
WITH TURNING
SAME SIZE AS DIFFUSER INLET
UNLESS NOTED OTHERWISE
WITH TAG
VANES 10"ø
B
8"ø
250
N
FLEXIBLE DUCTWORK WITH
EXTERNAL INSULATION
(5' MAXIMUM LENGTH)
CEILING DIFFUSER
LINEAR DIFFUSER
RECTANGULAR
SHEET METAL
DUCTWORK
CONICAL SPIN-IN
FITTING WITH
QUADRANT DAMPER
CONICAL SPIN-IN
FITTING WITH REMOTE
DAMPER ACTUATOR
B
4 LF/8"ø
250
SUPPLY GRILLE WITH
45 DEGREE ENTRY
BRANCH AND M.V.D.
M0.02 SCHEDULES
X
EXISTING EQUIPMENT TAG
EQUIPMENT NUMBER
M3.01 ENLARGED MECHANICAL
141 S. Broadway, Suite 202
Denver, Colorado 80209
303 640 3173
open studio | architecture
scale:
checked by:
OSA project no.:
copyright: 2015 open studio | architecture
architect:
project:
sheet title:
original issue date:
FOR
CONSTRUCTION
original issue description:
12" = 1'-0"
12/18/2015 11:40:29 AM
M0.01
DRAWING INDEX, LEGENDS
AND NOTES
New Belgium Brewing
Medical Clinic
ABT
2015-004
PRICING AND PERMIT
602 Buckingham St.
Fort Collins, CO 80524
DEC. 18, 2015
New Belgium
Brewing Medical
Clinic
Rev. Description Date
Page 6 of 9
Motor Volts 1 121 Volts
Motor Amps 1 0.5 Amps
SP In Actual 0.0 in. wc
SP Out Actual 0.02 in. wc
Total SP Actual 0.02 in. wc
Motor Data
Motor Manufacturer ANA
Motor HP NS HP
Motor RPM NS RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 1.1 Amps
Sheave Data
Motor Sheave Make Direct Drive
L.H. Finn and Associates
Final Report Page 5 of 9
Deviation
% Final
Deviation
Outlet-01 107 C 12x6 320 294 318 92 99
Outlet-02 110 A 24x24 200 194 196 97 98
Outlet-03 111 A 24x24 70 79 69 113 99
Outlet-04 112 A 24x24 65 76 66 117 102
Outlet-05 102 C 8x6 200 159 197 80 99
Outlet-06 100 A 24x24 340 289 342 85 101
Outlet-07 100 C 8x6 185 230 184 124 99
Outlet-08 109 A 24x24 100 63 98 63 98
Outlet-09 108 A 24x24 100 47 100 47 100
Outlet-10 105 A 24x24 50 66 50 132 100
Outlet-11 106 A 24x24 40 58 39 145 98
Outlet-12 100 C 8x6 150 281 148 187 99
Outlet-13 104 C 8x6 30 56 30 187 100
Totals: - - - 1850 1892 1837 102 99
L.H. Finn and Associates
Final Report Page 3 of 9