HomeMy WebLinkAbout1640 Riverside Ave - Special Inspections/Field Verification - 11/12/2018PROJECT: FAN NO. AHU-6 FAN NO. FAN NO. EXISTING Motor Make/Frame Motor H.P./RPM Volts/Phase/Hertz F.L. Amps/S.F. Motor Sheave Make Motor Sheave Diam./Bore Fan Sheave Make Fan Sheave Diam./Bore No. Belts/Make/Size Sheave CL Distance Filters TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL 2250 2334 NG DD 160 164 115 120 9.6 7.2 REMARKS: DIRECT DRIVE Outside Air Voltage 9.6 / T.P. TEST DATE: 11/12/2018 READINGS BY: CC & JR & LB Fan RPM DIRECT DRIVE FAN TEST REPORT STUDIO BE FAN DATA Location MECH ROOM CFM Amperage DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE NG / 48Y DIRECT DRIVE 3/4 / 1075 115 / 1 / 60 Model Number TUC1D100A9601AF Serial Number 17181V6N2G Service 2ND FLOOR Manufacturer TRANE 1 - 24X25X1 PROJECT: SYSTEM: AREA REMARKS SERVED NO. TYPE SIZE AK 1 SW 10X6 1.0 2 SW 14X6 1.0 3 SW 14X6 1.0 4 SW 14X6 1.0 5 SW 14X6 1.0 6 SW 14X6 1.0 7 SW 14X6 1.0 8 SW 10X6 1.0 9 SW 10X6 1.0 TOTAL REMARKS:  CORRECTED FOR ALTITUDE TEST DATE: 185 257 190 103% 2250 2334 104% 250 368 261 104% 185 212 192 104% 300 405 310 103% 300 399 309 103% 300 278 311 104% 300 400 315 105% 180 296 187 104% 250 262 259 104% OUTLET DESIGN PRELIMINARY FINAL FINAL CFM VEL/CFM CFM % AIR OUTLET TEST REPORT STUDIO BE READINGS BY: CC & JR & LB AHU-6 (EXISTING) TEST APPARATUS: FLOW HOOD 11/12/2018