HomeMy WebLinkAbout1640 Riverside Ave - Special Inspections/Field Verification - 11/12/2018PROJECT:
FAN NO. AHU-6 FAN NO. FAN NO.
EXISTING
Motor Make/Frame
Motor H.P./RPM
Volts/Phase/Hertz
F.L. Amps/S.F.
Motor Sheave Make
Motor Sheave Diam./Bore
Fan Sheave Make
Fan Sheave Diam./Bore
No. Belts/Make/Size
Sheave CL Distance
Filters
TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL
2250 2334
NG DD
160 164
115 120
9.6 7.2
REMARKS:
DIRECT DRIVE
Outside Air
Voltage
9.6 / T.P.
TEST DATE: 11/12/2018 READINGS BY: CC & JR & LB
Fan RPM
DIRECT DRIVE
FAN TEST REPORT
STUDIO BE
FAN DATA
Location MECH ROOM
CFM
Amperage
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NG / 48Y
DIRECT DRIVE
3/4 / 1075
115 / 1 / 60
Model Number TUC1D100A9601AF
Serial Number 17181V6N2G
Service 2ND FLOOR
Manufacturer TRANE
1 - 24X25X1
PROJECT:
SYSTEM:
AREA REMARKS
SERVED NO. TYPE SIZE AK
1 SW 10X6 1.0
2 SW 14X6 1.0
3 SW 14X6 1.0
4 SW 14X6 1.0
5 SW 14X6 1.0
6 SW 14X6 1.0
7 SW 14X6 1.0
8 SW 10X6 1.0
9 SW 10X6 1.0
TOTAL
REMARKS: CORRECTED FOR ALTITUDE
TEST DATE:
185 257 190 103%
2250 2334 104%
250 368 261 104%
185 212 192 104%
300 405 310 103%
300 399 309 103%
300 278 311 104%
300 400 315 105%
180 296 187 104%
250 262 259 104%
OUTLET DESIGN PRELIMINARY FINAL FINAL
CFM VEL/CFM CFM %
AIR OUTLET
TEST REPORT
STUDIO BE
READINGS BY: CC & JR & LB
AHU-6 (EXISTING) TEST APPARATUS: FLOW HOOD
11/12/2018