Loading...
HomeMy WebLinkAbout3500 S College Ave - Special Inspections/Field Verification - 09/13/2019Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 9/13/18 PROJECT Advanced Eye Care 3500 South College Fort Collins, CO ***Final Report*** ARCHITECT None Shown ENGINEER Integrated Mechanical 223 Linden Street Fort Collins, CO CONTRACTOR Air Comfort 150 Rome Fort Collins, CO Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: Advanced Eye Care ADDRESS: 3500 South College Avenue Fort Collins, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:9/13/18 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:9/13/18 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 9/13/18 CERTIFICATION EXPIRATION DATE: 3/31/2020 Table Of Contents PROJECT: LOCATION: Advanced Eye Care Fort Collins, CO DATE: CONTACT: AUTHOR: 9/13/2018 Joe Marshall Joe Marshall Table Of Contents 1 Instrument Calibration Report.pdf............................................................................................................................ 1 2 Abbreviation Report.pdf............................................................................................................................................ 3 3 Roof Top Unit........................................................................................................................................................... 4 3.1 RTU-01............................................................................................................................................................... 4 3.2 RTU-01/RTU-01.................................................................................................................................................. 5 4 Fan Unit.................................................................................................................................................................... 6 4.1 EF-01.................................................................................................................................................................. 6 5 Prints.pdf.................................................................................................................................................................. 7 L.H. Finn and Associates Final Report Manufacturer Model Serial Application Cal. Date Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014 Alnor HM-680 70750150 Hydronic Press. & Diff. Press. 12/14/2015 Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015 Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016 Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 6/10/2015 Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 7/7/2017 Cooper SH66A 92711016 Temperature Measurement 10/9/2017 Extech 461895 Q394479 Rotation Measurement 4/17/2017 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 3/8/2016 Extech 461895 Q331990 Rotation Measurement 11/4/2014 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 10/3/2017 Extech 461895 Q590099 Rotation Measurement 4/17/2017 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 11/5/2015 Fluke 336 97110539R Electrical Measurement 4/5/2016 Fluke 336 97110538R Electrical Measurement 9/29/2015 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 335 12990071 Electrical Measurement 3/4/2016 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 10/3/2017 Fluke 374 20030354 Electrical Measurement 4/17/2017 TSI 8322 55100720 Air Velocity Measurement 10/4/2017 Shortridge ADM-860C M05789 Digital Manometer 11/25/2015 Shortridge ADM-860C M06821 Digital Manometer 4/18/2017 Shortridge ADM-860C M07352 Digital Manometer 6/6/2016 Shortridge ADM-860C M09123 Digital Manometer 4/18/2016 Shortridge ADM-860C M09347 Digital Manometer 9/26/2015 Shortridge ADM-860C M10144 Digital Manometer 4/14/2017 Shortridge ADM-860C M10371 Digital Manometer 11/5/2015 Shortridge ADM-860C M11448 Digital Manometer 4/14/2017 Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015 Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 4/18/2017 Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Project: Advanced Eye Care Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 1 of 10 Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017 Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 4/19/2018 Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 4/19/2018 Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 9/29/2016 Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 2/26/2018 Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 2/26/2018 Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 10/2/2016 Evergreen Telemetry S-PVF-1 1600322 Pressure Velocity Module 10/3/2016 Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700214 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700216 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/12/2017 Evergreen Telemetry RM-T-1 1700269 Radio Module 5/17/2017 Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1600235 Radio Module 10/12/2016 Evergreen Telemetry RM-T-1 1600233 Radio Module 10/14/2016 Evergreen Telemetry RM-T-1 1600234 Radio Module 10/16/2016 Evergreen Telemetry RM-T-1 1700260 Radio Module 4/21/2017 Evergreen Telemetry RM-T-1 1700261 Radio Module 4/21/2017 Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 5/17/2017 Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/11/2016 Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/13/2016 Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/15/2016 Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/17/2016 Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017 Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017 Evergreen Telemetry S-DP-125 1700112 Water Press. Sensing Module 3/2/2017 REMARKS: Not all equipment shown was used on this project. Project: Advanced Eye Care INSTRUMENT CALIBRATION REPORT (Continue) Page 2 of 10 Project: Advanced Eye Care Symbol Description Symbol Description A Airflow (L/S) NS Not Shown AF Air Foil NT No Information Tag ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceiling Diffuser SD Supply Diffuser CFM Airflow (Cubic Feet / Minute) SNKL Snorkel DD Direct Drive SP Static Pressure Des Design SPD Static Pressure Drop DWDI Double Width Double Inlet SR Supply Register EF Exhaust Fan SWSI Single Width Single Inlet EG Exhaust Grille T Temperature ( C ) ER Exhaust Register T Temperature ( F ) ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Frequency Drive GPM Waterflow (Gallons / Minute) VS Variable Speed HC Heat Coil W Waterflow (L/S) HER Heat Exchanger HRC Heat Recovery Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 3 of 10 Roof Top Unit PROJECT: LOCATION: Advanced Eye Care Fort Collins, CO DATE: CONTACT: AUTHOR: 9/13/2018 Joe Marshall Joe Marshall Tested By: Joe Marshall Date: 9/13/2018 SYSTEM/UNIT: RTU-01 Unit Data Unit Manufacturer Carrier Unit Model Number 48JCFS06A2M6A6B1C0 Unit Serial Number 2118C7710 Unit Discharge Vertical/Down RTU-01/Supply Fan Fan Type Forward Curve Fan Class 1 Fan Arrangement DWDI Fan Discharge Vertical/Down RTU-01/Filter Bank Filter Type Disposable Filter Quantity 4 Filter Size 16x16x2 Test Data Total CFM Design 2225 CFM Total CFM Actual 2336 CFM Outside Air CFM Design 640 CFM Outside Air CFM Actual 656 CFM Return Air CFM Design 1585 CFM Return Air CFM Actual 1580 CFM RTU-01/Supply Fan Fan RPM Actual 1374 RPM Motor Volts 1 472 Volts Motor Volts 2 470 Volts Motor Volts 3 470 Volts Motor Amps 1 2.7 Amps Motor Amps 2 2.7 Amps Motor Amps 3 2.8 Amps Motor Data RTU-01/Supply Fan Motor Manufacturer Marathon Motor Frame 56HZ Motor RPM 1725 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.3 Amps Motor Service Factor 1.15 Sheave Data RTU-01/Supply Fan Motor Sheave Make Power Drive Motor Sheave Model VL50 Motor Sheave Diam. 5 in. Motor Sheave Bore 7/8 in. Motor Operating Diameter 4 in. Roof Top Unit PROJECT: LOCATION: Advanced Eye Care Fort Collins, CO DATE: CONTACT: AUTHOR: 9/13/2018 Joe Marshall Joe Marshall Tested By: Joe Marshall Date: 9/13/2018 SYSTEM/UNIT: RTU-01/RTU-01 Test Pressures Pre Filter SP In -0.40 in. w.c. Pre Filter SP Out ANA in. w.c. Supply Fan SP In -0.62 in. w.c. Supply Fan SP Out ANA in. w.c. Cooling Coil SP In ANA in. w.c. Cooling Coil SP Out -0.62 in. w.c. Heat Exchanger SP In ANA in. w.c. Heat Exchanger SP Out -0.43 in. w.c. Static Pressure Profile System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 See Print D-1 24x24 100 121 104 121 104 Outlet-02 See Print D-1 24x24 100 163 106 163 106 Outlet-03 See Print D-1 24x24 165 145 172 88 104 Outlet-04 See Print D-1 24x24 90 110 96 122 107 Outlet-05 See Print D-1 24x24 165 186 173 113 105 Outlet-06 See Print D-1 24x24 90 112 94 124 104 Outlet-07 See Print D-1 24x24 125 196 131 157 105 Outlet-08 See Print D-1 24x24 90 103 95 114 106 Outlet-09 See Print D-4 10x4 175 214 182 122 104 Outlet-10 See Print D-4 10x4 175 213 184 122 105 Outlet-11 See Print D-4 10x4 175 229 186 131 106 Outlet-12 See Print D-4 10x4 175 259 181 148 103 Outlet-13 See Print D-4 12x6 300 326 313 109 104 Outlet-14 See Print D-4 12x6 300 298 319 99 106 Totals: - - - 2225 2675 2336 120 105 RTU-01 Supply Outlet Summary L.H. Finn and Associates Final Report Page 5 of 10 Fan Unit PROJECT: LOCATION: Advanced Eye Care Fort Collins, CO DATE: CONTACT: AUTHOR: 9/13/2018 Joe Marshall Joe Marshall Tested By: Joe Marshall Date: 9/13/2018 SYSTEM/UNIT: EF-01 Unit Data Fan Manufacturer Twin City Fan Fan Model Number DRCD060BE2 Fan Serial Number E18-0000002514060 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Downblast Starter Data Installed Thermal Internal Test Data Total CFM Design 225 CFM Total CFM Actual 218 CFM Fan RPM Actual High Speed RPM Motor Volts 1 121 Volts Motor Amps 1 1.2 Amps Motor Data Motor Manufacturer Twin City Motor HP 1/6 HP Motor RPM 350-800 RPM Motor Rated Volts 110/120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A See Print R 12x12 75 59 72 79 96 Inlet-B See Print R 12x12 75 63 72 84 96 Inlet-C See Print R 12x12 75 84 74 112 99 Totals: - - - 225 206 218 92 97 EF-01 Exhaust Inlet Summary L.H. Finn and Associates Final Report Page 6 of 10 Page 7 of 10 Page 8 of 10 1 2 3 4 5 6 7 8 9 10 11 13 12 14 15 A B C Page 9 of 10 Page 10 of 10 Fan Sheave Make Power Drive Fan Sheave Model AK49 Fan Sheave Diam. 4 3/4 in. Fan Sheave Bore 5/8 in. Number of Belts 1 Belt Size A-40 Sheave Center Line 14 1/4 in. Test Pressures OA Damper Pos Actual 30 % RA Damper Pos Actual 70 % L.H. Finn and Associates Final Report Page 4 of 10