HomeMy WebLinkAbout3501 Stanford St - Special Inspections/Field Verification - 05/16/2020JEDI Balancing, Inc.
568 Briggs Street (physical)
P.O. Box 525 (mail)
Erie, CO. 80516
Phone (720) 839-5333
www.jedibalancing.com
Certified Test, Adjust & Balance Report
Project Foothills Mall Multifamily-McWhinney
Address
Architect JG Johnson Architects
Mechanical Engineer DMCE
Contractor MAI Mechanical
TABB Certified Supervisor Bryan A. Hund
Date 5/16/2018
Job Number 2018-8486
Bryan A. Hund
TABB Certified Supervisor
TABB Firm Certification #BB009003C
Stamp Expires 3/31/19
3501 Stanford Rd. Fort Collins, CO 80525
Warranty Information:
The data presented in this report is a record of system measurements and final adjustments
that have been obtained in accordance with the current edition of the TABB International
Standards for Environmental Systems Balance. The measurements shown, and the
information given, in this report are certified to be accurate and complete, at the time and
date information was gathered. Any variances from design quantities, which exceed TABB
tolerances, are noted in the TAB report project summary.
This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date
listed on this cover page.
Instrumentation:
Instrument Manufacturer Model Serial Number Calibrated On
Tachometer Shimpo MT-200 B168B5005P 10-04-2017
Air Temperature
Meter
Evergreen
Telemetry
RM-T-1 1700353 10-15-2017
Air Temperature
Probe
Evergreen
Telemetry
PR-T-1 1700353 10-15-2017
Immersion
Temperature Probe
Evergreen
Telemetry
PR-T-4-6 1700223 10-12-2017
Contact Temperature
Probe
Evergreen
Telemetry
PR-T-2 1700117 10-17-2017
Humidity Evergreen
Telemetry
S-H-3-5 1700296 10-17-2017
Volt-Amp Meter Flir CM-83 Z354881 10-12-2017
Rotating Vane Extech AM-300 Z354582 10-06-2017
Air Pressure TSI / Alnor EBT-731 EBT-731652014 03-15-2018
Air Velocity / Airfoil TSI / Alnor EBT-731 EBT-731652017 03-15-2018
Flowhood TSI / Alnor EBT-731 EBT-731652017 03-15-2018
Hydronic Pressure TSI HM-675 71646136 03-09-2018
Hydronic
Differential Pressure
TSI HM-675 71646136 03-09-2018
Abbreviation Index
TAB: Testing, Adjusting & Balancing Cx: Commissioning
AHU: Air Handling Unit Motor FLA: Full Load Amperage
RTU: Roof Top Unit S.F.: Service Factor
PACU: Packaged Air Conditioning Unit OD: Outside Diameter
MAU: Make Up Air Unit P.F.: Power Factor
FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency
CRAC: Computer Room Air Conditioning Unit RPM: Revolutions per Minute
VAV: Variable Air Volume T1: Terminal 1
K Factor: Correction Factor T2: Terminal 2
FPB: Fan Powered Box T3: Terminal 3
AK: Area Correction PSI: Pounds per Square Inch
Design D.P.: Design Differential Pressure TDH: Total Dynamic Head
Actual D.P.: Recorded Differential Pressure CS: Circuit Setter
Ind.Imp.Dia. Indicated Impeller Diameter BV: Balance Valve
CUH: Cabinet Unit Heater Valve D.P.: Discharge Pressure
UH: Unit Heater Valve S.P.: Suction Pressure
ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit
EF: Exhaust Fan PEF: Power Exhaust Fan
KEF: Kitchen Exhaust Fan SF: Supply Fan
RF: Return Fan TF: Transfer Fan
Diff.: Differential SEF: Smoke Exhaust Fan
SPF: Stairwell Pressurization Fan DX: Direct Expansion
SACU: Spilt Air Conditioner Unit SP: Static Pressure
TSP: Total Static Pressure in. wc: Inches Water Column
ESP: External Static Pressure HW: Heating Water
VP: Velocity Pressure CHW: Cooling Water
SA: Supply Air CW: Condenser Water
RA: Return Air HX: Heat Exchanger
OSA: Outside Air SWD: Sidewall Diffuser
OA: Outside Air EAT: Entering Air Temperature
MA: Mixed Air LAT: Leaving Air Temperature
SD: Supply Diffuser EWT: Entering Water Temperature
CD: Ceiling Diffuser LWT: Leaving Water Temperature
ER: Exhaust Register MVD: Manual Volume Damper
RG: Return Grille OBD: Opposed Blade Damper
CFM: Cubic Feet Per Minute NAC: No Access
FPM: Feet Per Minute NG: Not Given
SSD: Square Supply Diffuser NIC: Not in Contract
SRD: Square Return Diffuser E: Existing
TG: Transfer Grille cm: Centimeter
l/s: Liters per Second M: Meter
mm: Millimeter Pa: Pascal
kPa: Kilopascal CMH: Cubic Meters per Hour
Report Summary and Remarks
SEE ALL FIELD NOTES LOCATED BELOW EQUIPMENT DATA
JEDI Balancing, Inc.
568 Briggs Street (physical)
P.O. Box 525 (mail)
Erie, CO. 80516
Phone (720) 839-5333
www.jedibalancing.com
Scope
The Test, Adjust and Balance (TAB) scope of work consisted of 9 fan coil units (FCU) and 4
exhaust fans (EF)
Procedures:
Typical AHU / RTU POSTURING
Submittals
Submittals were not provided for the project.
RTU and AHU - CONSTANT VOLUME
The furnaces have constant volume fans that were set for design airflow and the associated
supply outlets and inlets were balanced in full cooling demand. After the distribution
systems were complete, the outside air values were measured and set. The Return Air CFM
was directly measured. The Outside Air CFM was derived from subtracting Return Air CFM
from Total Supply Air CFM. There was no access to the unit discharge to obtain a duct
traverse. Total CFM was derived by the sum of the Outlet measurements. All final TAB
settings and performance measurements were completed, and data was recorded on to the
appropriate test report forms.
Exhaust Fan Remarks
EXHAUST FANS
The exhaust fans were energized, measured and set for total airflow. The associated inlets
were balanced as noted in this report. Total CFM was derived as noted on the individual test
pages. Final settings and performance measurements were completed, and data recorded on
to the appropriate test report forms.
SCHEMATIC LINE DIAGRAMS
Report includes reduced mechanical drawings used for the test and balance work. These
“Keyed Drawing” were used in place of single line schematic diagrams and include the
unique designations for the tested items in the final TAB report.
Table of Contents
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Table Of Contents
1 Project Summary...................................................................................................................................................... 1
2 Air Handling Unit...................................................................................................................................................... 2
2.1 FCU-1.5A............................................................................................................................................................ 2
2.2 FCU-1.5B............................................................................................................................................................ 4
2.3 FCU-1.5C........................................................................................................................................................... 6
2.4 FCU-1.5D........................................................................................................................................................... 8
2.5 FCU-1.5E............................................................................................................................................................ 10
2.6 FCU-1.5F............................................................................................................................................................ 12
2.7 FCU-1.5G........................................................................................................................................................... 14
2.8 FCU-1.5H........................................................................................................................................................... 16
2.9 FCU-1.5I............................................................................................................................................................. 18
3 Fan Unit.................................................................................................................................................................... 20
3.1 EF-06-01............................................................................................................................................................. 20
3.2 EF-06-02............................................................................................................................................................. 21
3.3 EF-06-03............................................................................................................................................................. 22
3.4 EF-06-04............................................................................................................................................................. 23
JEDI Balancing, Inc.
Project Summary
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Test System / Unit Name Date Contact Notes / Comment Logs
Air Handling Unit FCU-1.5A 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
27-Apr-18 Luke Scaggs OBD/DAMPER 100% CLOSED ON OUTLETS 2
AND 4
27-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET, FAN SITS IN OPEN PLENUM
Air Handling Unit FCU-1.5B 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Air Handling Unit FCU-1.5C 27-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET, FAN SITS IN OPEN PLENUM
8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
Air Handling Unit FCU-1.5D 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
8-May-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET, FAN SITS IN OPEN PLENUM
Air Handling Unit FCU-1.5E 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Air Handling Unit FCU-1.5F 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
Air Handling Unit FCU-1.5G 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
Air Handling Unit FCU-1.5H 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Air Handling Unit FCU-1.5I 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED
Air Apparatus Filter FCU-1.5D/SF Filter Bank 27-Apr-18 Luke Scaggs FILTERS ARE AT BOTH RETURN INLETS
Air Apparatus Filter FCU-1.5F/SF Filter Bank 27-Apr-18 Luke Scaggs FILTERS INSTALLED AT EACH RETURN INLET
JEDI Balancing, Inc. Page 1 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5A
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z12C105681
Location CORRIDOR
Area Served CORRIDOR/STORAGE
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5A/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5A/Supply Fan
Motor Volts 1 211
Motor Amps 1 1.4
Corrected FLA 0.01
Unitary
FCU-1.5A/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5A/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5A/Supply Fan
Drive Type DIRECT DRIVE
Motor Sheave Make —
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5A
Log: FCU-1.5A 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5A 4/27/2018 Luke Scaggs OBD/DAMPER 100% CLOSED ON OUTLETS 2
AND 4
FCU-1.5A 4/27/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET, FAN SITS IN OPEN PLENUM
Filter Data
FCU-1.5A/SF Filter Bank
Filter Quantity (set 2) NOT APPLICABLE
Filter Size (set 2) NOT APPLICABLE
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 175 155 190 109 Flow
Hood
1.000 1.000 190
Outlet-02 SD 50 120 55 110 Flow
Hood
1.000 1.000 55
Outlet-03 SD 200 200 210 105 Flow
Hood
1.000 1.000 210
Outlet-04 SD 50 90 55 110 Flow
Hood
1.000 1.000 55
Outlet-05 SD 175 260 190 109 Flow
Hood
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5B
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z12C105682
Location ELEVATOR LOBBY
Area Served ELEVATOR LOBBY
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5B/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 0 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5B/Supply Fan
Motor Volts 1 212
Motor Amps 1 1.2
Motor Amps 3 1.27
Corrected FLA 0.01
Unitary
FCU-1.5B/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5B/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5B/Supply Fan
Drive Type DIRECT DRIVE
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5B
Log: FCU-1.5B 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5B 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Filter Data
FCU-1.5B/SF Filter Bank
Filter Quantity (set 2) NOT APPLICABLE
Filter Size (set 2) NOT APPLICABLE
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 250 215 250 100 Flow
Hood
1.000 1.000 250
Outlet-02 SD 200 305 205 103 Flow
Hood
1.000 1.000 205
Outlet-03 SD 200 270 190 95 Flow
Hood
1.000 1.000 190
Totals: - - - 650 790 645 99 - - - -
FCU-1.5B Supply Outlet Summary
JEDI Balancing, Inc. Page 5 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5C
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z10C084245
Location CORRIDOR
Area Served CORRIDOR
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5C/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5C/Supply Fan
Motor Volts 1 210
Motor Amps 1 1.32
Corrected FLA 0.01
Unitary
FCU-1.5C/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5C/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5C/Supply Fan
Drive Type DIRECT DRIVE
Motor Sheave Make —
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5C
Log: FCU-1.5C 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5C 4/27/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET, FAN SITS IN OPEN PLENUM
Filter Data
FCU-1.5C/SF Filter Bank
Filter Quantity (set 2) NOT APPLICABLE
Filter Size (set 2) NOT APPLICABLE
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 150 215 160 107 Flow
Hood
1.000 1.000 160
Outlet-02 SD 75 195 80 107 Flow
Hood
1.000 1.000 80
Outlet-03 SD 200 65 220 110 Flow
Hood
1.000 1.000 220
Outlet-04 SD 75 120 80 107 Flow
Hood
1.000 1.000 80
Outlet-05 SD 150 215 165 110 Flow
Hood
1.000 1.000 165
Totals: - - - 650 810 705 108 - - - -
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5D
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z10C084243
Location CORRIDOR
Area Served CORRIDOR, ELEVATOR
LOBBY
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5D/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5D/Supply Fan
Motor Volts 1 209
Motor Amps 1 1.6
Corrected FLA 0.01
Unitary
FCU-1.5D/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5D/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5D/Supply Fan
Drive Type DIRECT DRIVE
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5D
Log: FCU-1.5D 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5D 5/8/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET, FAN SITS IN OPEN PLENUM
FCU-1.5D/SF Filter Bank 4/27/2018 Luke Scaggs FILTERS ARE AT BOTH RETURN INLETS
Filter Data
FCU-1.5D/SF Filter Bank
Filter Quantity (set 2) 1
Filter Size (set 2) 8x8x1
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 200 225 200 100 Flow
Hood
1.000 1.000 200
Outlet-02 SD 200 190 210 105 Flow
Hood
1.000 1.000 210
Outlet-03 SD 100 55 95 95 Flow
Hood
1.000 1.000 95
Outlet-04 SD 150 200 145 97 Flow
Hood
1.000 1.000 145
Totals: - - - 650 670 650 100 - - - -
FCU-1.5D Supply Outlet Summary
JEDI Balancing, Inc. Page 9 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5E
Log: FCU-1.5E 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5E 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z10C084238
Location CORRIDOR
Area Served CORRIDOR
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5E/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5E/Supply Fan
Motor Volts 1 211
Motor Amps 1 1.4
Corrected FLA 0.01
Unitary
FCU-1.5E/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5E/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 250 220 265 106 Flow
Hood
1.000 1.000 265
Outlet-02 SD 200 235 220 110 Flow
Hood
1.000 1.000 220
Outlet-03 SD 200 285 220 110 Flow
Hood
1.000 1.000 220
Totals: - - - 650 740 705 108 - - - -
FCU-1.5E Supply Outlet Summary
JEDI Balancing, Inc. Page 11 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5F
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z10C084241
Location CORRDIOR
Area Served CORRIDOR, ELEVATOR
LOBBY
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5F/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5F/Supply Fan
Motor Volts 1 210
Motor Amps 1 1.25
Corrected FLA 0.01
Unitary
FCU-1.5F/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5F/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5F/Supply Fan
Drive Type DIRECT DRIVE
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5F
Log: FCU-1.5F 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5F 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
FCU-1.5F/SF Filter Bank 4/27/2018 Luke Scaggs FILTERS INSTALLED AT EACH RETURN INLET
Filter Data
FCU-1.5F/SF Filter Bank
Filter Quantity (set 2) 1
Filter Size (set 2) 8x8x1
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 200 230 210 105 Flow
Hood
1.000 1.000 210
Outlet-02 SD 200 225 195 98 Flow
Hood
1.000 1.000 195
Outlet-03 SD 100 65 95 95 Flow
Hood
1.000 1.000 95
Outlet-04 SD 150 170 150 100 Flow
Hood
1.000 1.000 150
Totals: - - - 650 690 650 100 - - - -
FCU-1.5F Supply Outlet Summary
JEDI Balancing, Inc. Page 13 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5G
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z09C055078
Location CORRIDOR
Area Served CORRIDOR
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5G/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5G/Supply Fan
Motor Volts 1 210
Motor Amps 1 1.35
Corrected FLA 0.01
Unitary
FCU-1.5G/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5G/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5G/Supply Fan
Drive Type DIRECT DRIVE
Motor Sheave Make —
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5G
Log: FCU-1.5G 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5G 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Filter Data
FCU-1.5G/SF Filter Bank
Filter Quantity (set 2) NOT APPLICABLE
Filter Size (set 2) NOT APPLICABLE
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 250 230 260 104 Flow
Hood
1.000 1.000 260
Outlet-02 SD 200 215 200 100 Flow
Hood
1.000 1.000 200
Outlet-03 SD 200 220 200 100 Flow
Hood
1.000 1.000 200
Totals: - - - 650 665 660 102 - - - -
FCU-1.5G Supply Outlet Summary
JEDI Balancing, Inc. Page 15 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5H
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z09C055079
Location CORRIDOR
Area Served CORRIDOR, ELEVATOR
LOBBY
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5H/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5H/Supply Fan
Motor Volts 1 209
Motor Amps 1 1.17
Corrected FLA 0.01
Unitary
FCU-1.5H/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5H/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5H/Supply Fan
Drive Type DIRECT DRIVE
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5H
Log: FCU-1.5H 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5H 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 200 305 220 110 Flow
Hood
1.000 1.000 220
Outlet-02 SD 200 195 220 110 Flow
Hood
1.000 1.000 220
Outlet-03 SD 100 100 110 110 Flow
Hood
1.000 1.000 110
Outlet-04 SD 150 210 160 107 Flow
Hood
1.000 1.000 160
Totals: - - - 650 810 710 109 - - - -
FCU-1.5H Supply Outlet Summary
JEDI Balancing, Inc. Page 17 of 23
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5I
Unit Data
Unit Manufacturer FIRST CO
Unit Model Number 25HX5-240
Unit Serial Number Z10C084242
Location CORRIDOR
Area Served CORRIDOR
Service SUPPLY
Fan Type Direct Drive
Coil Size Not Given sq. ft.
Starter Data
FCU-1.5I/Supply Fan
Starter Size NOT APPLICABLE
Starter Setting —
Design Data
Total CFM Design 650 CFM
Total Connected Design CFM 650 CFM
Outside Air CFM Design 100 CFM
Design TSP 0.35 in. wc
Electrical Test Data
FCU-1.5I/Supply Fan
Motor Volts 1 209
Motor Amps 1 1.05
Corrected FLA 0.01
Unitary
FCU-1.5I/Supply Fan
Starter Model No. —
Installed Thermal INTERNAL
Rating (Amps) —
Required Thermals —
Required Amps —
Motor Data
FCU-1.5I/Supply Fan
Motor Manufacturer INTERTEK
Motor HP 1/5
Motor RPM NOT GIVEN
Motor Frame NOT GIVEN
Motor Type NOT GIVEN
Motor Rated Volts 208/240
Motor Phase 1
Motor FL Amps 2
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN
Power Factor NOT GIVEN
Sheave Data
FCU-1.5I/Supply Fan
Drive Type DIRECT DRIVE
Motor Sheave Make —
Air Handling Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 5/8/2018
SYSTEM/UNIT: FCU-1.5I
Log: FCU-1.5I 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED
FCU-1.5I 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED
CABINET
Filter Data
FCU-1.5I/SF Filter Bank
Filter Quantity (set 2) NOT APPLICABLE
Filter Size (set 2) NOT APPLICABLE
System/Unit Area
Served
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instrum
ent
Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Outlet-01 SD 250 295 270 108 Flow
Hood
1.000 1.000 270
Outlet-02 SD 200 280 215 108 Flow
Hood
1.000 1.000 215
Outlet-03 SD 200 280 215 108 Flow
Hood
1.000 1.000 215
Totals: - - - 650 855 700 108 - - - -
FCU-1.5I Supply Outlet Summary
JEDI Balancing, Inc. Page 19 of 23
Fan Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 4/30/2018
SYSTEM/UNIT: EF-06-01
Unit Data
Fan Manufacturer COOK
Fan Model Number GC-422
Fan Serial Number NO ACCESS
Location TRASH DUMPSTER ROOM
Area Served TRASH DUMPSTER ROOM
Service EXHAUST
Fan Type Direct Drive
Starter Data
Starter Manufacturer Not Applicable
Starter Model No. —
Starter Size —
Installed Thermal —
Rating (Amps) — Amps
Required Thermals —
Required Amps —
Thermal Set At —
Design Data
Total CFM Design 250
Total Connected Design CFM 250
Design TSP 0.3 in. wc
Test Data
Actual TSP —
Actual ESP —
Electrical Test Data
Motor Volts 1 Actual 121
Motor Volts 2 Actual 0.7
Motor Amps 1 Actual 0.75
Corrected FLA 0.95
Motor Data
Motor Manufacturer MCMILLAN
Motor HP 1/23
Motor RPM 1500
Motor Frame Not Given
Motor Type Not Given
Motor Rated Volts 115
Motor Phase 1
Motor FL Amps 1
Motor Service Factor NOT GIVEN
Nominal Efficiency NOT GIVEN %
Power Factor NOT GIVEN
Sheave Data
Drive Type Direct Drive
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 4/30/2018
SYSTEM/UNIT: EF-06-02
Unit Data
Fan Manufacturer COOK
Fan Model Number GC-422
Fan Serial Number NO ACCESS
Location JANITORS CLOSET
Area Served JANITORS CLOSET/TRASH
CLOSET
Starter Data
Starter Manufacturer Not Applicable
Starter Model No. —
Starter Size —
Installed Thermal —
Rating (Amps) — Amps
Required Thermals —
Required Amps —
Thermal Set At —
Design Data
Total CFM Design 250
Total Connected Design CFM 250
Design TSP 0.3 in. wc
Test Data
Actual TSP —
Actual ESP —
Electrical Test Data
Motor Volts 1 Actual 121
Motor Amps 1 Actual 0.75
Corrected FLA 1.00
Motor Data
Motor Manufacturer MCMILLAN
Motor HP 1/23
Motor RPM 1500
Motor Frame Not Given
Motor Type Not Given
Motor Rated Volts 115
Motor Phase 1
Motor FL Amps 1.05
Motor Service Factor NOT GIVEN
Nominal Efficiency Not Given %
Power Factor Not Given
Sheave Data
Drive Type Direct Drive
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size —
Fan Sheave Bore — in.
Fan Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 4/30/2018
SYSTEM/UNIT: EF-06-03
Unit Data
Fan Manufacturer COOK
Fan Model Number GC-422
Fan Serial Number NO ACCESS
Location JANITORS CLOSET
Area Served JANITORS CLOSET/TRASH
CLOSET
Starter Data
Starter Manufacturer Not Applicable
Starter Model No. —
Starter Size —
Installed Thermal —
Rating (Amps) — Amps
Required Thermals —
Required Amps —
Thermal Set At —
Design Data
Total CFM Design 250
Total Connected Design CFM 250
Design TSP 0.3 in. wc
Test Data
Actual TSP —
Actual ESP —
Electrical Test Data
Motor Volts 1 Actual 121
Motor Amps 1 Actual 0.75
Corrected FLA 1.00
Motor Data
Motor Manufacturer MCMILLAN
Motor HP 1/23
Motor RPM 1500
Motor Frame Not Given
Motor Type Not Given
Motor Rated Volts 115
Motor Phase 1
Motor FL Amps 1.05
Motor Service Factor NOT GIVEN
Nominal Efficiency Not Given %
Power Factor Not Given
Sheave Data
Drive Type Direct Drive
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size —
Fan Sheave Bore — in.
Fan Unit
PROJECT:
LOCATION:
FOOTHILLS MULTI BLDG 18
FT COLLINS, CO
PROJECT #: 2018-8486
DATE:
CONTACT:
5/16/2018
Josh Cota
Tested By: Luke Scaggs
Date: 4/30/2018
SYSTEM/UNIT: EF-06-04
Unit Data
Fan Manufacturer COOK
Fan Model Number GC-422
Fan Serial Number NO ACCESS
Location JANITORS CLOSET
Area Served JANITORS CLOSET/TRASH
CLOSET
Starter Data
Starter Manufacturer Not Applicable
Starter Model No. —
Starter Size —
Installed Thermal —
Rating (Amps) — Amps
Required Thermals —
Required Amps —
Thermal Set At —
Design Data
Total CFM Design 250
Total Connected Design CFM 250
Design TSP 0.3 in. wc
Test Data
Actual TSP —
Actual ESP —
Electrical Test Data
Motor Volts 1 Actual 121
Motor Amps 1 Actual 0.75
Corrected FLA 1.00
Motor Data
Motor Manufacturer MCMILLAN
Motor HP 1/23
Motor RPM 1500
Motor Frame Not Given
Motor Type Not Given
Motor Rated Volts 115
Motor Phase 1
Motor FL Amps 1.05
Motor Service Factor NOT GIVEN
Nominal Efficiency Not Given %
Power Factor Not Given
Sheave Data
Drive Type Direct Drive
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size —
Fan Sheave Bore — in.
PROJECT
COPYRIGHT BY JOHNSON
NATHAN STROHE (JNS). ALL
DRAWN AND WRITTEN
INFORMATION APPEARING
HEREIN SHALL NOT BE
MODIFIED, DUPLICATED,
DISCLOSED, USED FOR
ANOTHER PROJECT, OR
OTHERWISE USED WITHOUT
THE WRITTEN CONSENT AND
INDEMNIFICATION OF JNS
SHEET TITLE
ISSUES/REVISIONS
STAMP
SHEET NUMBER
PRINTED ON
1600 Wynkoop St., Suite 100 | Denver, CO 80202
303.892.7062
WWW.JNS.DESIGN
8/5/2016 3:50:18 PM
C:\Users\open1\Documents\FH BUILDING 19_open1.rvt
LOT 3, 4, 5 & 6 OF FOOTHILLS MALL REDEVELOPMENT
M00.00
MCWHINNEY
FOOTHILLS MALL MULTIFAMILY
#1506
MECHANICAL
COVERSHEET
Date Description
3/16/16 FOR PERMIT
5/03/16 CD REVISION 2
5/10/16 CD REVISION 3
8/5/2016 CD REVISION 16 - ASI #16
SYMBOL ABBREV. DESCRIPTION SYMBOL ABBREV. DESCRIPTION ABBREV. DESCRIPTION
S
SYMBOL
U.C. SIZE
H
20/16
M
B
W H
S
MECHANICAL LEGEND
BUTTERFLY VALVE
PIPE DOWN
PIPE TEE DOWN
SAND OIL WASTE
GREASE WASTE
STORM PIPE
GATE VALVE
BALANCING VALVE
BALL VALVE
COLD WATER
HOT WATER
HOT WATER RECIRCULATE
VENT PIPE
WASTE PIPE
AUTO FLOW CONTROL VALVE
PROJECT
COPYRIGHT BY JOHNSON
NATHAN STROHE (JNS). ALL
DRAWN AND WRITTEN
INFORMATION APPEARING
HEREIN SHALL NOT BE
MODIFIED, DUPLICATED,
DISCLOSED, USED FOR
ANOTHER PROJECT, OR
OTHERWISE USED WITHOUT
THE WRITTEN CONSENT AND
INDEMNIFICATION OF JNS
SHEET TITLE
ISSUES/REVISIONS
STAMP
SHEET NUMBER
PRINTED ON
1600 Wynkoop St., Suite 100 | Denver, CO 80202
303.892.7062
WWW.JNS.DESIGN
8/5/2016 3:50:18 PM
C:\Users\open1\Documents\FH BUILDING 19_open1.rvt
LOT 3, 4, 5 & 6 OF FOOTHILLS MALL REDEVELOPMENT
MCWHINNEY
FOOTHILLS MALL MULTIFAMILY
#1506
Date Description
3/16/16 FOR PERMIT
5/03/16 CD REVISION 2
5/10/16 CD REVISION 3
8/5/16 CD REVISION 16 - ASI #16
10/19/16 ASI #30
01/06/17 RFI #137
01/18/17 ASI #34
M00.01
MECHANICAL
SCHEDULES
ASI 34
ASI 34
42
ASI 34
42
42
ASI 34
42
PROJECT
COPYRIGHT BY JOHNSON
NATHAN STROHE (JNS). ALL
DRAWN AND WRITTEN
INFORMATION APPEARING
HEREIN SHALL NOT BE
MODIFIED, DUPLICATED,
DISCLOSED, USED FOR
ANOTHER PROJECT, OR
OTHERWISE USED WITHOUT
THE WRITTEN CONSENT AND
INDEMNIFICATION OF JNS
SHEET TITLE
ISSUES/REVISIONS
STAMP
SHEET NUMBER
PRINTED ON
1600 Wynkoop St., Suite 100 | Denver, CO 80202
303.892.7062
WWW.JNS.DESIGN
8/5/2016 3:50:18 PM
C:\Users\open1\Documents\FH BUILDING 19_open1.rvt
LOT 3, 4, 5 & 6 OF FOOTHILLS MALL REDEVELOPMENT
MCWHINNEY
FOOTHILLS MALL MULTIFAMILY
#1506
Date Description
3/16/16 FOR PERMIT
5/03/16 CD REVISION 2
5/10/16 CD REVISION 3
8/5/2016 CD REVISION 16 - ASI #16
M00.02
MECHANICAL
SCHEDULES
18
ASI 16
18
ASI 16
FCU-1.5A
FCU-1.5B
FCU-1.5C
1
2
3
1
1
2
3
4
5
1
2
3
4
5
1
EF-06-01
1
FCU-1.5D FCU-1.5E
1 2
1
2
1
2
3
4
1
3 2 1
EF-06-02
FCU-1.5F FCU-1.5G
1
3 2 1
1 2
1
2
1
2
3
4
EF-06-03
FCU-1.5H FCU-1.5I
1
2
1 2
1
2
3
4
3 2 1
1
EF-06-04
03/15/2016
This electronic stamp & signature is
under the sole & direct control of the
signee Denis J Miller, P.E.
GLOBE VALVE
STOP & DRAIN VALVE
CHECK VALVE
NITROGEN
CHILLED WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
HIGH PRESSURE STEAM
LOW PRESSURE STEAM
HIGH PRESSURE STEAM RETURN
LOW PRESSURE STEAM RETURN
HEATING WATER SUPPLY
PIPE UP
ST
GW
SO
HW
DHC
FIRE
W
VENT
AIR
HPSR
LPS
CWS
CWR
CHS
CHR
RH
RS
RL
VAC VACUUM
AIR
FIRE
CW
LPR
HWS
HWR
HPS
A
HEATING WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CHILLED WATER SUPPLY
PLUG VALVE
MANUAL DAMPER W/ LOCKING
FLEXIBLE DUCT CONNECTOR
VACUUM BREAKER
THERMOMETER
FIRE & SMOKE DAMPER
SMOKE DAMPER
EXISTING FIRE DAMPER
RETURN GRILLE
CONNECTION NEW TO EXISTING.
FLEXIBLE PIPE CONNECTION
DOOR UNDERCUT
FIRE DAMPER
'8&77$.(2))
PRESSURE GAUGE
FLOW SENSOR
DUCT SIZE INDICATING SHEET
METAL DIMENSIONS. FIRST
NUMBER WIDTH & SECOND
IS DEPTH.
DUCT ELBOW W/ TURNING VANE
MOTORIZED DAMPER
QUADRANT.
CFM DIFFUSER I.D.
DEMO ITEM LINE WEIGHT
NECESSARILY USED ON THIS PROJECT.
}
NOTE: NOT ALL SYMBOLS ON THIS LEGEND ARE
FLEX
DIFFUSER
NECK SIZE
DUCT TEE W/ TURNING VANES
EXISTING ITEM LINE WEIGHT
NEW ITEM LINE
WEIGHTS
[[
FLEX SIZE
F.D.
BRK
F.S.
F.S.
CO
CO
R.D.
VTR
O.R.D.
H B
W H
P#
BOILER DRAIN VALVE
SMOKE DETECTOR
PIPE ANCHOR
VENT THRU ROOF
FLOOR DRAIN
WALL HYDRANT
DOWNSPOUT NOZZLE
HOSE BIBB
AIR VENT
P-T TAP
PIPE GUIDE (SLEEVE)
PIPE EXPANSION JOINT
PRESSURE/TEMP. RELIEF
PUMP
PRESSURE REDUCING VALVE
SOLENOID VALVE
MOTORIZED GATE VALVE
REDUCED PRESSURE
BACKFLOW PREVENTOR
WAFER BALANCE VALVE
VENTURI
UNION
PIPE REDUCER
STRAINER
STRAINER W/ BLOWOFF VALVE
EQUIPMENT ROOM DRAIN
FLOOR SINK - HALF GRATE
FLOOR SINK - 1/4 GRATE
DRAIN ABOVE
ROOF DRAIN
CLEANOUT - VERTICAL
CLEANOUT - HORIZONTAL
ROOF DRAIN - OVERFLOW
PIPE CAP
BREAK - MISC.
GAS COCK
TEMP. CONTROL - 2-WAY
TEMP. CONTROL - 3-WAY
3-WAY VALVE
SPIN-IN FITTING W/ DAMPER
RIGID DUCT
(N) NEW
(E)
(R)
EXISTING
RELOCATED
GAS PRESSURE REGULATOR
ACCESS DOOR IN CEILING
CWS
CWR
CHS
CHR
RS
RL
RH
HWS
HWR
HPS
HPSR
LPS
LPSR
N
VAC
A
N
F
W
V
GAS GAS PIPE
GW
SO
G
STM
PIPE TEE UP
GAS COCK AND UNION
FS
BALL DRAIN W/ HOSE END
CONNECTION.
REMOTE SENSOR
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
T THERMOSTAT
S
CD
CM
H HUMIDISTAT
*NOTE: ALL DASHED PLUMBING LINES INDICATE BELOW FLOOR ELEVATION UNLESS OTHERWISE
NOTED ON DRAWINGS.
S
SPECIFIED MANUFACTURER / MODEL
NECESSARILY USED ON THIS PROJECT.
NOTE: NOT ALL VALVES ON THIS LIST ARE
SYMBOL DESCRIPTION EQUALS BY
LEGEND SPECIFICATION LIST
BALL VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
GAS COCK
STRAINER
MILWAUKEE / 105 or 115
MILWAUKEE / CL 223 or CL 323
MILWAUKEE / BA 100 H
FLOWSET / AV
POTTROFF / VFD-10
TRERICE / 600C
METRAFLEX / METRASPHERE EPDM
FLOWSET / YR
KEYSTONE / SERIES 500
AMTROL 705
WATTS / SERIES 40, 140, 240, or 340
BY T.C. CONTRACTOR
AMBER-BOOTH / 2600 EPDM
NIBCO
NIBCO
STOCKHAM
MILLIKEN
CENTERLINE
-
ASHCROFT / MAG
PETERSON / PETE's PLUG
-
-
KEYSTONE
RED & WHITE
-
-
-
-
-
NIBCO
DEZURIK
-
GERAND
APOLLO
BURKET
BARCO
KECKLEY
KECKLEY
ASHCROFT / MA
CONBRACO
CONBRACO
-
UNIVERSAL / 45PT-N
NIBCO
-
-
-
-
-
NIBCO
GRISWOLD
STOCKHAM
-
-
MASON / MFNC EPDM
WEKSLER / EA14
WEKSLER / AA5H
-
RED & WHITE
RED & WHITE
-
-
-
-
NIBCO
-
-
-
-
SKINNER
GERAND
TEMPERING VALVE LEONARD LAWLER
VENTURI
REDUCED PRESSURE
MANUAL AIR VENT
AUTOMATIC AIR VENT
FLEXIBLE PIPE CONNECTION
THERMOMETER
PRESSURE GAUGE
SMOKE DAMPER
PRESSURE/TEMP. RELIEF
P-T TAP
STRAINER W/ BLOWOFF VALVE
FIRE DAMPER
FIRE & SMOKE DAMPER
BOILER DRAIN VALVE
FLOWSET / SUPERSEAL
MILWAUKEE / 105 or 115
MILWAUKEE / 590T or 1590T
MILWAUKEE / 509T, 1590T, F2974(M)(A), 548, or 1400 SERIES
-
MILWAUKEE / BA-100 or BA-150
WATTS / ACV 115
FLOWSET / ACCUSETTER
ASCO / RED HAT
BY T.C. CONTRACTOR
WATTS / SERIES 77S with B-6081 VALVE
MAXITROL / BV37 or BV64
WATTS / 909QTS
POTTROFF / FSD-142
POTTROFF / SD-142
WATTS / B-3000 or B-3001 for 1/2" - 3"
FLOWSET / VW
WATTS / SERIES 77S for 1/2" thru 2-1/2"
TRERICE / BX91403 1/2
HOFFMAN FLOWSET
A
PRESSURE REDUCING VALVE
BALANCING VALVE
GATE VALVE
BACKFLOW PREVENTOR
SOLENOID VALVE
WAFER BALANCE VALVE
BUTTERFLY VALVE
STOP/DRAIN VALVE
GATE VALVE IN GROUND BOX
GLOBE VALVE
TEMP. CONTROL - 2-WAY
TEMP. CONTROL - 3-WAY
PLUG VALVE
-
GAS PRESSURE REGULATOR SCHLUMBERGER / VARIES - -
AIR ADMITTANCE VALVE STUDOR VENT - -
APOLLO / 78-103-1 1/2" N.P.T. BY HOSE NIBCO STOCKHAM
GENERAL NOTES
1. FOLLOW ALL APPLICABLE CODES AND ORDINANCES. PAY ALL FEES AND PERMITS AND ATTAIN THE SAME.
2. ALL EQUIPMENT, INSULATION, AND CONTROLS TO MEET LOCAL JURISDICTIONAL AUTHORITY'S ADOPTED ENERGY
CODE.
3. VISIT SITE AND ASCERTAIN EXISTING CONDITIONS PRIOR TO BID.
4. THE INFORMATION PRESENTED ON THIS DRAWING IS DIAGRAMMATIC AND IS NOT TO BE SCALED. IT DOES NOT
NECESSARILY REPRESENT ALL ELBOWS, DUCT EXTENSIONS, OFFSETS, HANGERS, ETC. REQUIRED FOR A
COMPLETE WORKING SYSTEM.
5. SHOP DRAWINGS SHALL BE SUBMITTED ON ALL VALVES, FIXTURES, INSULATION, G.R.D.'S AND EQUIPMENT FOR
RESPONSE PRIOR TO ORDERING. SIX (6) COPIES OF EACH IN ONE SUBMITTAL WITHIN 10 DAYS OF SIGNING
CONTRACT. CLEARLY NOTE ANY DEVIATION BETWEEN SUBMITTED ITEMS AND SPECIFIED ITEMS ON THE COVER
SHEET OF THE SUBMITTAL. FAILURE TO SUBMIT MAY CAUSE SPECIFIED ITEMS TO BE REJECTED AND REPLACED
AT CONTRACTOR'S EXPENSE.
6. EXTRA COSTS OR CHANGES ALLOWED ONLY IF APPROVED IN WRITING BY ARCHITECT/OWNER WITH DOLLAR
AMOUNT PRIOR TO ORDERING. NO EXTENSIONS OF COMPLETION TIME ALLOWED WITHOUT WRITTEN
AUTHORIZATION.
7. THIS CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL FIELD CONDITIONS PRIOR TO THE PURCHASE OF ANY
MATERIALS AND THE COMMENCEMENT OF ANY WORK AND IS TO NOTIFY THE ARCHITECT OF ANY DISCREPANCIES
FOR RESOLUTION.
8. PROVIDE OWNER WITH 3 SETS OF TYPEWRITTEN AND BOUND "OPERATING INSTRUCTIONS" FOR ALL SYSTEMS AND
EQUIPMENT, INCLUDING MANUFACTURER'S MAINTENANCE MANUALS. INCLUDE APPROVED EQUIPMENT
SUBMITTALS, EQUIPMENT START-UP REPORTS, LUBRICATION, FILTER TYPES AND SIZES, BALANCE REPORT,
STARTING AND STOPPING PROCEDURES, AND LIST SERVICE CONTRACTOR'S 24 HOUR TELEPHONE NUMBERS.
9. CONCEAL ALL WORK IN FINISHED AREAS.
10. CUT AND PATCH TO MATCH ADJACENT AREAS. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED WITHOUT
STRUCTURAL ENGINEER'S WRITTEN APPROVAL.
11. GUARANTEE ALL LABOR AND EQUIPMENT FOR ONE YEAR FROM THE DATE OF ACCEPTANCE BY OWNER.
12. PROVIDE FACTORY AUTHORIZED START-UPS AND WRITTEN START-UP REPORTS ON ALL EQUIPMENT.
13. FIREPROOF ALL PENETRATIONS OF RATED FLOOR/WALL/CEILING/ROOF ASSEMBLIES. FIREPROOFING AND
INSTALLATION TO BE UL CLASSIFIED AND ICBO APPROVED, SUITABLE FOR MOISTURE AND VIBRATION.
METALCAULK BY RECTORSEAL OR EQUAL. INSTALL PER ALL MANUFACTURER RECOMMENDATIONS. SUBMIT FIRE
STOP SCHEDULE BY MANUFACTURER.
14. PROVIDE CHROME-PLATED FLOOR, WALL, AND CEILING ESCUTCHEONS OF ADJUSTABLE TYPE ON ALL PIPES
PASSING THROUGH WALLS, PARTITIONS, AND FLOORS AFTER PAINTING IS COMPLETED.
MECHANICAL NOTES
1. IDENTIFY ALL HVAC AND REFRIGERATION EQUIPMENT AS TO THE AREA SERVED BY THE EQUIPMENT.
IDENTIFICATION SHALL BE ENGRAVED PLASTIC TAGS OR BRASS PERMANENTLY AFFIXED TO EACH PIECE OF EQUIPMENT.
2. PROVIDE UL RATED FIRE OR FIRE/RADIATION DAMPERS WHERE INDICATED ON PLANS OR SCHEDULES. INSTALL
PER BUILDING DEPARTMENT, UL, AND SMACNA REQUIREMENTS. INCLUDE LABELED ACCESS FOR DUCT AND
CEILING/WALL STRUCTURES. ACCESS DOORS TO BE UL RATED IN ALL FIRE RATED ARCHITECTURAL ASSEMBLIES.
INCLUDE TRANSFORMERS FOR 115V/24V ELECTRICAL CONNECTION.
3. PROVIDE ALL CURBS, SUPPORTS, AND ANCHORS FOR MECHANICAL WORK. NO CHAIN, TAPE, OR WIRE MAY BE
USED FOR HANGING OR SUPPORTING. PROVIDE AND INSTALL ALL NECESSARY SHIMS AND LEVELING DEVICES TO
PROPERLY INSTALL ALL EQUIPMENT IN A LEVEL CONDITION.
4. RECEIVE, UNCRATE, ASSEMBLE, INSURE, AND INSTALL IN CONFORMANCE TO MANUFACTURER'S
RECOMMENDATIONS ALL EQUIPMENT FURNISHED BY THIS CONTRACT AND FURNISHED BY THE OWNER.
5. THE NEW MECHANICAL SYSTEMS CONSISTING OF THE AIR DISTRIBUTION SYSTEM WITH: DUCTWORK, FLEXIBLE
DUCT, DIFFUSERS, GRILLES, DAMPERS, CONTROL SYSTEMS, ETC. SHALL BE BY THE MECHANICAL CONTRACTOR.
6. CEILING CAVITY IS NOT A RETURN AIR PLENUM.
7. DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS. OVERALL OUTSIDE DUCT DIMENSIONS SHALL BE ADJUSTED
TO ALLOW FOR ANY LINER THICKNESS.
8. THIS CONTRACTOR SHALL COORDINATE ALL DUCTWORK WITH OTHER TRADES PRIOR TO INSTALLATION.
9. WEATHERPROOF ALL MECHANICAL ROOF PENETRATIONS PER CODES AND ALL ROOFING MANUFACTURER
RECOMMENDATIONS.
10. PROVIDE FIRE OR SMOKE DETECTORS ON RETURN FOR MECHANICAL SYSTEMS OVER 2000 CFM AS REQUIRED BY
CODES OR BUILDING STANDARDS. IF TWO OR MORE MECHANICAL SYSTEMS (I.E. ROOFTOP UNITS) SERVE THE
SAME AREA AND WHEN COMBINED EXCEED 2000 CFM, A FIRE OR SMOKE DETECTOR SHALL BE INSTALLED ON THE
RETURN OF EACH UNIT WHEN REQUIRED BY LOCAL AUTHORITIES.
11. PROVIDE SLEEVES AND COLLARS FOR ALL DUCTWORK AND PIPES THROUGH WALLS, FLOORS, AND CEILINGS.
SEAL ALL EXTERNAL PENETRATIONS WEATHER TIGHT WITH EXTERIOR COMMERCIAL GRADE CAULK. FIREPROOF
ALL PENETRATIONS OF FIRE RATED WALLS, FLOORS AND CEILINGS.
12. CONFIRM VOLTAGE, PHASE, AND AMPACITY WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.
ALL CONTROL AND INTERLOCK WIRING FOR MECHANICAL EQUIPMENT BY MECHANICAL CONTRACTOR. THREE
PHASE MOTORS TO HAVE MAGNETIC STARTERS WITH PROTECTION ON ALL THREE LEADS. CONTROLS AND
HEATING/COOLING EQUIPMENT TO AUTOMATICALLY RESTART AFTER POWER FAILURE. ALL WIRE TO BE IN
13. ALL RECIRCULATED AIR SHALL PASS THROUGH STANDARD 30% MERV 8, THROW AWAY FILTERS. PROVIDE ONE
ADDITIONAL CLEAN SET FOR OWNER AT PROJECT COMPLETION.
14. A MINIMUM CLEARANCE OF 36 INCHES SHALL BE PROVIDED AROUND ANY EQUIPMENT OR COMPLY WITH
MANUFACTURER'S REQUIREMENTS (I.E., FANS, PUMPS, BOILERS, AIR CONDITIONERS, ETC.) FOR SERVICE AND
MAINTENANCE. GAS FIRED APPLIANCES SHALL BE VENTED PER THE MANUFACTURER'S LISTING. PROVIDE
COMBUSTION AIR AS REQUIRED PER CODE.
15. TEMPERATURE CONTROLS - THE HVAC SYSTEM CONTROLS ARE TO BE FULLY AUTOMATIC. ALL CONTROLS ARE TO
BE ELECTRIC. TEMPERATURE CONTROL SETUP AND SETBACK SHALL BE ACCOMPLISHED BY MEANS OF AN
ELECTRIC THERMOSTAT WITH THE FOLLOWING FEATURES BEING STANDARD:
a. ADJUSTABLE HEATING AND COOLING SETPOINTS.
b. NIGHT AND WEEKEND PROGRAMMABLE SETBACK.
c. AUTOMATIC CHANGEOVER BETWEEN HEATING AND COOLING CYCLES IN COMMON AREAS (MANUAL CHANGE
d. MINIMUM JOB EIGHT (8) HOUR BATTERY BACKUPS DURING POWER FAILURE.
e. OPTIMAL SYSTEM STARTUPS TO ENSURE CORRECT TEMPERATURE AT OCCUPANCY.
f. LOCKABLE COVERS IN COMMON AREAS.
g. ALL CONTROL SYSTEMS SHALL BE DESIGNED AND PROVIDED BY A CONTROL MANUFACTURER WHO HAS
BEEN IN THE BUSINESS OF MANUFACTURING, DESIGNING AND INSTALLING CONTROL COMPONENTS AND
SYSTEMS FOR A MINIMUM OF TEN (10) YEARS.
OVER IN RESIDENCES.)
18
ASI 16
ASI 16
18
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size — in.
Final Data
Total Fan CFM Actual 230
Measured Data
Fan RPM Actual DIRECT DRIVE
Test Pressures
Fan SP In Actual NO ACCESS in. wc
Fan SP Out Actual NO ACCESS in. wc
System/Unit Area
Serve
d
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instruments Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Inlet-01 ER 100 100 100 100 Flow Hood 1.000 1.000 100
Inlet-02 ER 150 160 160 107 Flow Hood 1.000 1.000 160
Totals: - - - 250 260 260 104 - - - -
EF-06-04 Exhaust Inlet Summary
JEDI Balancing, Inc. Page 23 of 23
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size — in.
Final Data
Total Fan CFM Actual 230
Measured Data
Fan RPM Actual DIRECT DRIVE
Test Pressures
Fan SP In Actual NO ACCESS in. wc
Fan SP Out Actual NO ACCESS in. wc
System/Unit Area
Serve
d
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instruments Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Inlet-01 ER 100 90 90 90 Flow Hood 1.000 1.000 90
Inlet-02 ER 150 140 140 93 Flow Hood 1.000 1.000 140
Totals: - - - 250 230 230 92 - - - -
EF-06-03 Exhaust Inlet Summary
JEDI Balancing, Inc. Page 22 of 23
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size — in.
Final Data
Total Fan CFM Actual 255
Measured Data
Fan RPM Actual DIRECT DRIVE
Test Pressures
Fan SP In Actual NO ACCESS in. wc
Fan SP Out Actual NO ACCESS in. wc
System/Unit Area
Serve
d
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instruments Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Inlet-01 ER 100 140 100 100 Flow Hood 1.000 1.000 100
Inlet-02 ER 150 115 155 103 Flow Hood 1.000 1.000 155
Totals: - - - 250 255 255 102 - - - -
EF-06-02 Exhaust Inlet Summary
JEDI Balancing, Inc. Page 21 of 23
Fan Sheave Model / Size —
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size — in.
Final Data
Total Fan CFM Actual 320
Fan CFM Test Method FLOW HOOD
Measured Data
Fan RPM Actual DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. wc
Fan SP Out Actual NO ACCESS in. wc
System/Unit Area
Serve
d
Outlet
Type
Size
(in)
Design
Reading
Prelim
Reading
Final
Reading
%
Final
Instruments Open
Area
(sq ft)
Ak (sq
ft)
Final
Vel
FPM
Inlet-01 TOTAL 250 320 240 96 Flow Hood 1.000 1.000 240
Totals: - - - 250 320 240 96 - - - -
EF-06-01 Exhaust Inlet Summary
JEDI Balancing, Inc. Page 20 of 23
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 700
Outside Air CFM Actual 105
OA Damper Pos 90 CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 595
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5I/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5I/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 20x20x1
JEDI Balancing, Inc. Page 18 of 23
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 710
Outside Air CFM Actual 105
OA Damper Pos 50 %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 605
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5H/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5H/SF Filter Bank
Filter Type PLEATED
Filter Quantity (set 1) 1
Filter Size (set 1) 20x20x1
JEDI Balancing, Inc. Page 16 of 23
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 660
Outside Air CFM Actual 105
OA Damper Pos FULLY CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 555
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5G/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5G/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 12x24x1
JEDI Balancing, Inc. Page 14 of 23
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 650
Outside Air CFM Actual 110
OA Damper Pos 90 CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 540
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5F/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5F/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 12x24x1
JEDI Balancing, Inc. Page 12 of 23
FCU-1.5E/Supply Fan
Drive Type DIRECT DRIVE
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 705
Outside Air CFM Actual 100
OA Damper Pos 80 CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 605
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5E/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
JEDI Balancing, Inc. Page 10 of 23
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 650
Outside Air CFM Actual 110
OA Damper Pos 90 CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 540
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5D/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5D/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 12x24x1
JEDI Balancing, Inc. Page 8 of 23
FCU-1.5C Supply Outlet Summary
JEDI Balancing, Inc. Page 7 of 23
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 705
Outside Air CFM Actual 95
OA Damper Pos 90 CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 615
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5C/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5C/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 12x24x1
JEDI Balancing, Inc. Page 6 of 23
Motor Sheave Make —
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 645
Outside Air CFM Actual NOT APPLICABLE
OA Damper Pos — %
OA CFM Test Method —
Return Air CFM Actual 645
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5B/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5B/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 12x24x1
JEDI Balancing, Inc. Page 4 of 23
1.000 1.000 190
Totals: - - - 650 825 700 108 - - - -
FCU-1.5A Supply Outlet Summary
JEDI Balancing, Inc. Page 3 of 23
Motor Sheave Model / Size — in.
Motor Sheave Bore — in.
Fan Sheave Make —
Fan Sheave Model / Size — in.
Fan Sheave Bore — in.
Sheave Center Line — in.
Number of Belts —
Belt Make —
Belt Size —
Final Data
Total CFM Actual 700
Outside Air CFM Actual 105
OA Damper Pos 90 CLOSED %
OA CFM Test Method SUPPLY - RETURN
Return Air CFM Actual 595
RA Damper Position NOT APPLICABLE
Coil Velocity NOT GIVEN FPM
Duct Static Setpoint NOT APPLICABLE in. wc
Measured Data
FCU-1.5A/Supply Fan
Fan RPM Actual —
Motor RPM Actual —
Fan Rotation - Actual COUNTER CLOCKWISE
Fan Speed / Setpoint —
Operating Hertz 60 Hz
Filter Data
FCU-1.5A/SF Filter Bank
Filter Service RETURN
Filter Type MERV 8
Filter Quantity (set 1) 1
Filter Size (set 1) 12x24x1
JEDI Balancing, Inc. Page 2 of 23