HomeMy WebLinkAbout3501 Stanford St - Special Inspections/Field Verification - 05/16/2020JEDI Balancing, Inc. 568 Briggs Street (physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Certified Test, Adjust & Balance Report Project Foothills Mall Multifamily-McWhinney Address Architect JG Johnson Architects Mechanical Engineer DMCE Contractor MAI Mechanical TABB Certified Supervisor Bryan A. Hund Date 5/16/2018 Job Number 2018-8486 Bryan A. Hund TABB Certified Supervisor TABB Firm Certification #BB009003C Stamp Expires 3/31/19 3501 Stanford Rd. Fort Collins, CO 80525 Warranty Information: The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB International Standards for Environmental Systems Balance. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date information was gathered. Any variances from design quantities, which exceed TABB tolerances, are noted in the TAB report project summary. This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date listed on this cover page. Instrumentation: Instrument Manufacturer Model Serial Number Calibrated On Tachometer Shimpo MT-200 B168B5005P 10-04-2017 Air Temperature Meter Evergreen Telemetry RM-T-1 1700353 10-15-2017 Air Temperature Probe Evergreen Telemetry PR-T-1 1700353 10-15-2017 Immersion Temperature Probe Evergreen Telemetry PR-T-4-6 1700223 10-12-2017 Contact Temperature Probe Evergreen Telemetry PR-T-2 1700117 10-17-2017 Humidity Evergreen Telemetry S-H-3-5 1700296 10-17-2017 Volt-Amp Meter Flir CM-83 Z354881 10-12-2017 Rotating Vane Extech AM-300 Z354582 10-06-2017 Air Pressure TSI / Alnor EBT-731 EBT-731652014 03-15-2018 Air Velocity / Airfoil TSI / Alnor EBT-731 EBT-731652017 03-15-2018 Flowhood TSI / Alnor EBT-731 EBT-731652017 03-15-2018 Hydronic Pressure TSI HM-675 71646136 03-09-2018 Hydronic Differential Pressure TSI HM-675 71646136 03-09-2018 Abbreviation Index TAB: Testing, Adjusting & Balancing Cx: Commissioning AHU: Air Handling Unit Motor FLA: Full Load Amperage RTU: Roof Top Unit S.F.: Service Factor PACU: Packaged Air Conditioning Unit OD: Outside Diameter MAU: Make Up Air Unit P.F.: Power Factor FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency CRAC: Computer Room Air Conditioning Unit RPM: Revolutions per Minute VAV: Variable Air Volume T1: Terminal 1 K Factor: Correction Factor T2: Terminal 2 FPB: Fan Powered Box T3: Terminal 3 AK: Area Correction PSI: Pounds per Square Inch Design D.P.: Design Differential Pressure TDH: Total Dynamic Head Actual D.P.: Recorded Differential Pressure CS: Circuit Setter Ind.Imp.Dia. Indicated Impeller Diameter BV: Balance Valve CUH: Cabinet Unit Heater Valve D.P.: Discharge Pressure UH: Unit Heater Valve S.P.: Suction Pressure ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit EF: Exhaust Fan PEF: Power Exhaust Fan KEF: Kitchen Exhaust Fan SF: Supply Fan RF: Return Fan TF: Transfer Fan Diff.: Differential SEF: Smoke Exhaust Fan SPF: Stairwell Pressurization Fan DX: Direct Expansion SACU: Spilt Air Conditioner Unit SP: Static Pressure TSP: Total Static Pressure in. wc: Inches Water Column ESP: External Static Pressure HW: Heating Water VP: Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA: Return Air HX: Heat Exchanger OSA: Outside Air SWD: Sidewall Diffuser OA: Outside Air EAT: Entering Air Temperature MA: Mixed Air LAT: Leaving Air Temperature SD: Supply Diffuser EWT: Entering Water Temperature CD: Ceiling Diffuser LWT: Leaving Water Temperature ER: Exhaust Register MVD: Manual Volume Damper RG: Return Grille OBD: Opposed Blade Damper CFM: Cubic Feet Per Minute NAC: No Access FPM: Feet Per Minute NG: Not Given SSD: Square Supply Diffuser NIC: Not in Contract SRD: Square Return Diffuser E: Existing TG: Transfer Grille cm: Centimeter l/s: Liters per Second M: Meter mm: Millimeter Pa: Pascal kPa: Kilopascal CMH: Cubic Meters per Hour Report Summary and Remarks SEE ALL FIELD NOTES LOCATED BELOW EQUIPMENT DATA JEDI Balancing, Inc. 568 Briggs Street (physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Scope The Test, Adjust and Balance (TAB) scope of work consisted of 9 fan coil units (FCU) and 4 exhaust fans (EF) Procedures: Typical AHU / RTU POSTURING Submittals Submittals were not provided for the project. RTU and AHU - CONSTANT VOLUME The furnaces have constant volume fans that were set for design airflow and the associated supply outlets and inlets were balanced in full cooling demand. After the distribution systems were complete, the outside air values were measured and set. The Return Air CFM was directly measured. The Outside Air CFM was derived from subtracting Return Air CFM from Total Supply Air CFM. There was no access to the unit discharge to obtain a duct traverse. Total CFM was derived by the sum of the Outlet measurements. All final TAB settings and performance measurements were completed, and data was recorded on to the appropriate test report forms. Exhaust Fan Remarks EXHAUST FANS The exhaust fans were energized, measured and set for total airflow. The associated inlets were balanced as noted in this report. Total CFM was derived as noted on the individual test pages. Final settings and performance measurements were completed, and data recorded on to the appropriate test report forms. SCHEMATIC LINE DIAGRAMS Report includes reduced mechanical drawings used for the test and balance work. These “Keyed Drawing” were used in place of single line schematic diagrams and include the unique designations for the tested items in the final TAB report. Table of Contents PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Table Of Contents 1 Project Summary...................................................................................................................................................... 1 2 Air Handling Unit...................................................................................................................................................... 2 2.1 FCU-1.5A............................................................................................................................................................ 2 2.2 FCU-1.5B............................................................................................................................................................ 4 2.3 FCU-1.5C........................................................................................................................................................... 6 2.4 FCU-1.5D........................................................................................................................................................... 8 2.5 FCU-1.5E............................................................................................................................................................ 10 2.6 FCU-1.5F............................................................................................................................................................ 12 2.7 FCU-1.5G........................................................................................................................................................... 14 2.8 FCU-1.5H........................................................................................................................................................... 16 2.9 FCU-1.5I............................................................................................................................................................. 18 3 Fan Unit.................................................................................................................................................................... 20 3.1 EF-06-01............................................................................................................................................................. 20 3.2 EF-06-02............................................................................................................................................................. 21 3.3 EF-06-03............................................................................................................................................................. 22 3.4 EF-06-04............................................................................................................................................................. 23 JEDI Balancing, Inc. Project Summary PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Test System / Unit Name Date Contact Notes / Comment Logs Air Handling Unit FCU-1.5A 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED 27-Apr-18 Luke Scaggs OBD/DAMPER 100% CLOSED ON OUTLETS 2 AND 4 27-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET, FAN SITS IN OPEN PLENUM Air Handling Unit FCU-1.5B 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Air Handling Unit FCU-1.5C 27-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET, FAN SITS IN OPEN PLENUM 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED Air Handling Unit FCU-1.5D 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED 8-May-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET, FAN SITS IN OPEN PLENUM Air Handling Unit FCU-1.5E 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Air Handling Unit FCU-1.5F 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED Air Handling Unit FCU-1.5G 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED Air Handling Unit FCU-1.5H 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Air Handling Unit FCU-1.5I 30-Apr-18 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET 8-May-18 Luke Scaggs FINAL TESTING ON LOW SPEED Air Apparatus Filter FCU-1.5D/SF Filter Bank 27-Apr-18 Luke Scaggs FILTERS ARE AT BOTH RETURN INLETS Air Apparatus Filter FCU-1.5F/SF Filter Bank 27-Apr-18 Luke Scaggs FILTERS INSTALLED AT EACH RETURN INLET JEDI Balancing, Inc. Page 1 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5A Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z12C105681 Location CORRIDOR Area Served CORRIDOR/STORAGE Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5A/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5A/Supply Fan Motor Volts 1 211 Motor Amps 1 1.4 Corrected FLA 0.01 Unitary FCU-1.5A/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5A/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5A/Supply Fan Drive Type DIRECT DRIVE Motor Sheave Make — Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5A Log: FCU-1.5A 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5A 4/27/2018 Luke Scaggs OBD/DAMPER 100% CLOSED ON OUTLETS 2 AND 4 FCU-1.5A 4/27/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET, FAN SITS IN OPEN PLENUM Filter Data FCU-1.5A/SF Filter Bank Filter Quantity (set 2) NOT APPLICABLE Filter Size (set 2) NOT APPLICABLE System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 175 155 190 109 Flow Hood 1.000 1.000 190 Outlet-02 SD 50 120 55 110 Flow Hood 1.000 1.000 55 Outlet-03 SD 200 200 210 105 Flow Hood 1.000 1.000 210 Outlet-04 SD 50 90 55 110 Flow Hood 1.000 1.000 55 Outlet-05 SD 175 260 190 109 Flow Hood Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5B Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z12C105682 Location ELEVATOR LOBBY Area Served ELEVATOR LOBBY Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5B/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 0 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5B/Supply Fan Motor Volts 1 212 Motor Amps 1 1.2 Motor Amps 3 1.27 Corrected FLA 0.01 Unitary FCU-1.5B/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5B/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5B/Supply Fan Drive Type DIRECT DRIVE Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5B Log: FCU-1.5B 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5B 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Filter Data FCU-1.5B/SF Filter Bank Filter Quantity (set 2) NOT APPLICABLE Filter Size (set 2) NOT APPLICABLE System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 250 215 250 100 Flow Hood 1.000 1.000 250 Outlet-02 SD 200 305 205 103 Flow Hood 1.000 1.000 205 Outlet-03 SD 200 270 190 95 Flow Hood 1.000 1.000 190 Totals: - - - 650 790 645 99 - - - - FCU-1.5B Supply Outlet Summary JEDI Balancing, Inc. Page 5 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5C Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z10C084245 Location CORRIDOR Area Served CORRIDOR Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5C/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5C/Supply Fan Motor Volts 1 210 Motor Amps 1 1.32 Corrected FLA 0.01 Unitary FCU-1.5C/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5C/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5C/Supply Fan Drive Type DIRECT DRIVE Motor Sheave Make — Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5C Log: FCU-1.5C 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5C 4/27/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET, FAN SITS IN OPEN PLENUM Filter Data FCU-1.5C/SF Filter Bank Filter Quantity (set 2) NOT APPLICABLE Filter Size (set 2) NOT APPLICABLE System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 150 215 160 107 Flow Hood 1.000 1.000 160 Outlet-02 SD 75 195 80 107 Flow Hood 1.000 1.000 80 Outlet-03 SD 200 65 220 110 Flow Hood 1.000 1.000 220 Outlet-04 SD 75 120 80 107 Flow Hood 1.000 1.000 80 Outlet-05 SD 150 215 165 110 Flow Hood 1.000 1.000 165 Totals: - - - 650 810 705 108 - - - - Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5D Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z10C084243 Location CORRIDOR Area Served CORRIDOR, ELEVATOR LOBBY Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5D/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5D/Supply Fan Motor Volts 1 209 Motor Amps 1 1.6 Corrected FLA 0.01 Unitary FCU-1.5D/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5D/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5D/Supply Fan Drive Type DIRECT DRIVE Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5D Log: FCU-1.5D 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5D 5/8/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET, FAN SITS IN OPEN PLENUM FCU-1.5D/SF Filter Bank 4/27/2018 Luke Scaggs FILTERS ARE AT BOTH RETURN INLETS Filter Data FCU-1.5D/SF Filter Bank Filter Quantity (set 2) 1 Filter Size (set 2) 8x8x1 System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 200 225 200 100 Flow Hood 1.000 1.000 200 Outlet-02 SD 200 190 210 105 Flow Hood 1.000 1.000 210 Outlet-03 SD 100 55 95 95 Flow Hood 1.000 1.000 95 Outlet-04 SD 150 200 145 97 Flow Hood 1.000 1.000 145 Totals: - - - 650 670 650 100 - - - - FCU-1.5D Supply Outlet Summary JEDI Balancing, Inc. Page 9 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5E Log: FCU-1.5E 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5E 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z10C084238 Location CORRIDOR Area Served CORRIDOR Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5E/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5E/Supply Fan Motor Volts 1 211 Motor Amps 1 1.4 Corrected FLA 0.01 Unitary FCU-1.5E/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5E/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 250 220 265 106 Flow Hood 1.000 1.000 265 Outlet-02 SD 200 235 220 110 Flow Hood 1.000 1.000 220 Outlet-03 SD 200 285 220 110 Flow Hood 1.000 1.000 220 Totals: - - - 650 740 705 108 - - - - FCU-1.5E Supply Outlet Summary JEDI Balancing, Inc. Page 11 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5F Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z10C084241 Location CORRDIOR Area Served CORRIDOR, ELEVATOR LOBBY Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5F/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5F/Supply Fan Motor Volts 1 210 Motor Amps 1 1.25 Corrected FLA 0.01 Unitary FCU-1.5F/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5F/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5F/Supply Fan Drive Type DIRECT DRIVE Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5F Log: FCU-1.5F 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5F 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET FCU-1.5F/SF Filter Bank 4/27/2018 Luke Scaggs FILTERS INSTALLED AT EACH RETURN INLET Filter Data FCU-1.5F/SF Filter Bank Filter Quantity (set 2) 1 Filter Size (set 2) 8x8x1 System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 200 230 210 105 Flow Hood 1.000 1.000 210 Outlet-02 SD 200 225 195 98 Flow Hood 1.000 1.000 195 Outlet-03 SD 100 65 95 95 Flow Hood 1.000 1.000 95 Outlet-04 SD 150 170 150 100 Flow Hood 1.000 1.000 150 Totals: - - - 650 690 650 100 - - - - FCU-1.5F Supply Outlet Summary JEDI Balancing, Inc. Page 13 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5G Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z09C055078 Location CORRIDOR Area Served CORRIDOR Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5G/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5G/Supply Fan Motor Volts 1 210 Motor Amps 1 1.35 Corrected FLA 0.01 Unitary FCU-1.5G/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5G/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5G/Supply Fan Drive Type DIRECT DRIVE Motor Sheave Make — Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5G Log: FCU-1.5G 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5G 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Filter Data FCU-1.5G/SF Filter Bank Filter Quantity (set 2) NOT APPLICABLE Filter Size (set 2) NOT APPLICABLE System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 250 230 260 104 Flow Hood 1.000 1.000 260 Outlet-02 SD 200 215 200 100 Flow Hood 1.000 1.000 200 Outlet-03 SD 200 220 200 100 Flow Hood 1.000 1.000 200 Totals: - - - 650 665 660 102 - - - - FCU-1.5G Supply Outlet Summary JEDI Balancing, Inc. Page 15 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5H Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z09C055079 Location CORRIDOR Area Served CORRIDOR, ELEVATOR LOBBY Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5H/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5H/Supply Fan Motor Volts 1 209 Motor Amps 1 1.17 Corrected FLA 0.01 Unitary FCU-1.5H/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5H/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5H/Supply Fan Drive Type DIRECT DRIVE Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5H Log: FCU-1.5H 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5H 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 200 305 220 110 Flow Hood 1.000 1.000 220 Outlet-02 SD 200 195 220 110 Flow Hood 1.000 1.000 220 Outlet-03 SD 100 100 110 110 Flow Hood 1.000 1.000 110 Outlet-04 SD 150 210 160 107 Flow Hood 1.000 1.000 160 Totals: - - - 650 810 710 109 - - - - FCU-1.5H Supply Outlet Summary JEDI Balancing, Inc. Page 17 of 23 Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5I Unit Data Unit Manufacturer FIRST CO Unit Model Number 25HX5-240 Unit Serial Number Z10C084242 Location CORRIDOR Area Served CORRIDOR Service SUPPLY Fan Type Direct Drive Coil Size Not Given sq. ft. Starter Data FCU-1.5I/Supply Fan Starter Size NOT APPLICABLE Starter Setting — Design Data Total CFM Design 650 CFM Total Connected Design CFM 650 CFM Outside Air CFM Design 100 CFM Design TSP 0.35 in. wc Electrical Test Data FCU-1.5I/Supply Fan Motor Volts 1 209 Motor Amps 1 1.05 Corrected FLA 0.01 Unitary FCU-1.5I/Supply Fan Starter Model No. — Installed Thermal INTERNAL Rating (Amps) — Required Thermals — Required Amps — Motor Data FCU-1.5I/Supply Fan Motor Manufacturer INTERTEK Motor HP 1/5 Motor RPM NOT GIVEN Motor Frame NOT GIVEN Motor Type NOT GIVEN Motor Rated Volts 208/240 Motor Phase 1 Motor FL Amps 2 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN Power Factor NOT GIVEN Sheave Data FCU-1.5I/Supply Fan Drive Type DIRECT DRIVE Motor Sheave Make — Air Handling Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 5/8/2018 SYSTEM/UNIT: FCU-1.5I Log: FCU-1.5I 5/8/2018 Luke Scaggs FINAL TESTING ON LOW SPEED FCU-1.5I 4/30/2018 Luke Scaggs NO STATIC PROFILE PERFORMED, FINISHED CABINET Filter Data FCU-1.5I/SF Filter Bank Filter Quantity (set 2) NOT APPLICABLE Filter Size (set 2) NOT APPLICABLE System/Unit Area Served Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instrum ent Open Area (sq ft) Ak (sq ft) Final Vel FPM Outlet-01 SD 250 295 270 108 Flow Hood 1.000 1.000 270 Outlet-02 SD 200 280 215 108 Flow Hood 1.000 1.000 215 Outlet-03 SD 200 280 215 108 Flow Hood 1.000 1.000 215 Totals: - - - 650 855 700 108 - - - - FCU-1.5I Supply Outlet Summary JEDI Balancing, Inc. Page 19 of 23 Fan Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 4/30/2018 SYSTEM/UNIT: EF-06-01 Unit Data Fan Manufacturer COOK Fan Model Number GC-422 Fan Serial Number NO ACCESS Location TRASH DUMPSTER ROOM Area Served TRASH DUMPSTER ROOM Service EXHAUST Fan Type Direct Drive Starter Data Starter Manufacturer Not Applicable Starter Model No. — Starter Size — Installed Thermal — Rating (Amps) — Amps Required Thermals — Required Amps — Thermal Set At — Design Data Total CFM Design 250 Total Connected Design CFM 250 Design TSP 0.3 in. wc Test Data Actual TSP — Actual ESP — Electrical Test Data Motor Volts 1 Actual 121 Motor Volts 2 Actual 0.7 Motor Amps 1 Actual 0.75 Corrected FLA 0.95 Motor Data Motor Manufacturer MCMILLAN Motor HP 1/23 Motor RPM 1500 Motor Frame Not Given Motor Type Not Given Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 1 Motor Service Factor NOT GIVEN Nominal Efficiency NOT GIVEN % Power Factor NOT GIVEN Sheave Data Drive Type Direct Drive Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 4/30/2018 SYSTEM/UNIT: EF-06-02 Unit Data Fan Manufacturer COOK Fan Model Number GC-422 Fan Serial Number NO ACCESS Location JANITORS CLOSET Area Served JANITORS CLOSET/TRASH CLOSET Starter Data Starter Manufacturer Not Applicable Starter Model No. — Starter Size — Installed Thermal — Rating (Amps) — Amps Required Thermals — Required Amps — Thermal Set At — Design Data Total CFM Design 250 Total Connected Design CFM 250 Design TSP 0.3 in. wc Test Data Actual TSP — Actual ESP — Electrical Test Data Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.75 Corrected FLA 1.00 Motor Data Motor Manufacturer MCMILLAN Motor HP 1/23 Motor RPM 1500 Motor Frame Not Given Motor Type Not Given Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 1.05 Motor Service Factor NOT GIVEN Nominal Efficiency Not Given % Power Factor Not Given Sheave Data Drive Type Direct Drive Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — Fan Sheave Bore — in. Fan Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 4/30/2018 SYSTEM/UNIT: EF-06-03 Unit Data Fan Manufacturer COOK Fan Model Number GC-422 Fan Serial Number NO ACCESS Location JANITORS CLOSET Area Served JANITORS CLOSET/TRASH CLOSET Starter Data Starter Manufacturer Not Applicable Starter Model No. — Starter Size — Installed Thermal — Rating (Amps) — Amps Required Thermals — Required Amps — Thermal Set At — Design Data Total CFM Design 250 Total Connected Design CFM 250 Design TSP 0.3 in. wc Test Data Actual TSP — Actual ESP — Electrical Test Data Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.75 Corrected FLA 1.00 Motor Data Motor Manufacturer MCMILLAN Motor HP 1/23 Motor RPM 1500 Motor Frame Not Given Motor Type Not Given Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 1.05 Motor Service Factor NOT GIVEN Nominal Efficiency Not Given % Power Factor Not Given Sheave Data Drive Type Direct Drive Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — Fan Sheave Bore — in. Fan Unit PROJECT: LOCATION: FOOTHILLS MULTI BLDG 18 FT COLLINS, CO PROJECT #: 2018-8486 DATE: CONTACT: 5/16/2018 Josh Cota Tested By: Luke Scaggs Date: 4/30/2018 SYSTEM/UNIT: EF-06-04 Unit Data Fan Manufacturer COOK Fan Model Number GC-422 Fan Serial Number NO ACCESS Location JANITORS CLOSET Area Served JANITORS CLOSET/TRASH CLOSET Starter Data Starter Manufacturer Not Applicable Starter Model No. — Starter Size — Installed Thermal — Rating (Amps) — Amps Required Thermals — Required Amps — Thermal Set At — Design Data Total CFM Design 250 Total Connected Design CFM 250 Design TSP 0.3 in. wc Test Data Actual TSP — Actual ESP — Electrical Test Data Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.75 Corrected FLA 1.00 Motor Data Motor Manufacturer MCMILLAN Motor HP 1/23 Motor RPM 1500 Motor Frame Not Given Motor Type Not Given Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 1.05 Motor Service Factor NOT GIVEN Nominal Efficiency Not Given % Power Factor Not Given Sheave Data Drive Type Direct Drive Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — Fan Sheave Bore — in. PROJECT COPYRIGHT BY JOHNSON NATHAN STROHE (JNS). ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE MODIFIED, DUPLICATED, DISCLOSED, USED FOR ANOTHER PROJECT, OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT AND INDEMNIFICATION OF JNS SHEET TITLE ISSUES/REVISIONS STAMP SHEET NUMBER PRINTED ON 1600 Wynkoop St., Suite 100 | Denver, CO 80202 303.892.7062 WWW.JNS.DESIGN 8/5/2016 3:50:18 PM C:\Users\open1\Documents\FH BUILDING 19_open1.rvt LOT 3, 4, 5 & 6 OF FOOTHILLS MALL REDEVELOPMENT M00.00 MCWHINNEY FOOTHILLS MALL MULTIFAMILY #1506 MECHANICAL COVERSHEET Date Description 3/16/16 FOR PERMIT 5/03/16 CD REVISION 2 5/10/16 CD REVISION 3 8/5/2016 CD REVISION 16 - ASI #16 SYMBOL ABBREV. DESCRIPTION SYMBOL ABBREV. DESCRIPTION ABBREV. DESCRIPTION S SYMBOL U.C. SIZE H 20/16 M B W H S MECHANICAL LEGEND BUTTERFLY VALVE PIPE DOWN PIPE TEE DOWN SAND OIL WASTE GREASE WASTE STORM PIPE GATE VALVE BALANCING VALVE BALL VALVE COLD WATER HOT WATER HOT WATER RECIRCULATE VENT PIPE WASTE PIPE AUTO FLOW CONTROL VALVE PROJECT COPYRIGHT BY JOHNSON NATHAN STROHE (JNS). ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE MODIFIED, DUPLICATED, DISCLOSED, USED FOR ANOTHER PROJECT, OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT AND INDEMNIFICATION OF JNS SHEET TITLE ISSUES/REVISIONS STAMP SHEET NUMBER PRINTED ON 1600 Wynkoop St., Suite 100 | Denver, CO 80202 303.892.7062 WWW.JNS.DESIGN 8/5/2016 3:50:18 PM C:\Users\open1\Documents\FH BUILDING 19_open1.rvt LOT 3, 4, 5 & 6 OF FOOTHILLS MALL REDEVELOPMENT MCWHINNEY FOOTHILLS MALL MULTIFAMILY #1506 Date Description 3/16/16 FOR PERMIT 5/03/16 CD REVISION 2 5/10/16 CD REVISION 3 8/5/16 CD REVISION 16 - ASI #16 10/19/16 ASI #30 01/06/17 RFI #137 01/18/17 ASI #34 M00.01 MECHANICAL SCHEDULES ASI 34 ASI 34 42 ASI 34 42 42 ASI 34 42 PROJECT COPYRIGHT BY JOHNSON NATHAN STROHE (JNS). ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE MODIFIED, DUPLICATED, DISCLOSED, USED FOR ANOTHER PROJECT, OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT AND INDEMNIFICATION OF JNS SHEET TITLE ISSUES/REVISIONS STAMP SHEET NUMBER PRINTED ON 1600 Wynkoop St., Suite 100 | Denver, CO 80202 303.892.7062 WWW.JNS.DESIGN 8/5/2016 3:50:18 PM C:\Users\open1\Documents\FH BUILDING 19_open1.rvt LOT 3, 4, 5 & 6 OF FOOTHILLS MALL REDEVELOPMENT MCWHINNEY FOOTHILLS MALL MULTIFAMILY #1506 Date Description 3/16/16 FOR PERMIT 5/03/16 CD REVISION 2 5/10/16 CD REVISION 3 8/5/2016 CD REVISION 16 - ASI #16 M00.02 MECHANICAL SCHEDULES 18 ASI 16 18 ASI 16 FCU-1.5A FCU-1.5B FCU-1.5C 1 2 3 1 1 2 3 4 5 1 2 3 4 5 1 EF-06-01 1 FCU-1.5D FCU-1.5E 1 2 1 2 1 2 3 4 1 3 2 1 EF-06-02 FCU-1.5F FCU-1.5G 1 3 2 1 1 2 1 2 1 2 3 4 EF-06-03 FCU-1.5H FCU-1.5I 1 2 1 2 1 2 3 4 3 2 1 1 EF-06-04 03/15/2016 This electronic stamp & signature is under the sole & direct control of the signee Denis J Miller, P.E. GLOBE VALVE STOP & DRAIN VALVE CHECK VALVE NITROGEN CHILLED WATER RETURN REFRIGERANT LIQUID REFRIGERANT SUCTION REFRIGERANT HOT GAS HIGH PRESSURE STEAM LOW PRESSURE STEAM HIGH PRESSURE STEAM RETURN LOW PRESSURE STEAM RETURN HEATING WATER SUPPLY PIPE UP ST GW SO HW DHC FIRE W VENT AIR HPSR LPS CWS CWR CHS CHR RH RS RL VAC VACUUM AIR FIRE CW LPR HWS HWR HPS A HEATING WATER RETURN CONDENSER WATER SUPPLY CONDENSER WATER RETURN CHILLED WATER SUPPLY PLUG VALVE MANUAL DAMPER W/ LOCKING FLEXIBLE DUCT CONNECTOR VACUUM BREAKER THERMOMETER FIRE & SMOKE DAMPER SMOKE DAMPER EXISTING FIRE DAMPER RETURN GRILLE CONNECTION NEW TO EXISTING. FLEXIBLE PIPE CONNECTION DOOR UNDERCUT FIRE DAMPER ƒ'8&77$.(2)) PRESSURE GAUGE FLOW SENSOR DUCT SIZE INDICATING SHEET METAL DIMENSIONS. FIRST NUMBER WIDTH & SECOND IS DEPTH. DUCT ELBOW W/ TURNING VANE MOTORIZED DAMPER QUADRANT. CFM DIFFUSER I.D. DEMO ITEM LINE WEIGHT NECESSARILY USED ON THIS PROJECT. } NOTE: NOT ALL SYMBOLS ON THIS LEGEND ARE FLEX DIFFUSER NECK SIZE DUCT TEE W/ TURNING VANES EXISTING ITEM LINE WEIGHT NEW ITEM LINE WEIGHTS [[‘ FLEX SIZE F.D. BRK F.S. F.S. CO CO R.D. VTR O.R.D. H B W H P# BOILER DRAIN VALVE SMOKE DETECTOR PIPE ANCHOR VENT THRU ROOF FLOOR DRAIN WALL HYDRANT DOWNSPOUT NOZZLE HOSE BIBB AIR VENT P-T TAP PIPE GUIDE (SLEEVE) PIPE EXPANSION JOINT PRESSURE/TEMP. RELIEF PUMP PRESSURE REDUCING VALVE SOLENOID VALVE MOTORIZED GATE VALVE REDUCED PRESSURE BACKFLOW PREVENTOR WAFER BALANCE VALVE VENTURI UNION PIPE REDUCER STRAINER STRAINER W/ BLOWOFF VALVE EQUIPMENT ROOM DRAIN FLOOR SINK - HALF GRATE FLOOR SINK - 1/4 GRATE DRAIN ABOVE ROOF DRAIN CLEANOUT - VERTICAL CLEANOUT - HORIZONTAL ROOF DRAIN - OVERFLOW PIPE CAP BREAK - MISC. GAS COCK TEMP. CONTROL - 2-WAY TEMP. CONTROL - 3-WAY 3-WAY VALVE SPIN-IN FITTING W/ DAMPER RIGID DUCT (N) NEW (E) (R) EXISTING RELOCATED GAS PRESSURE REGULATOR ACCESS DOOR IN CEILING CWS CWR CHS CHR RS RL RH HWS HWR HPS HPSR LPS LPSR N VAC A N F W V GAS GAS PIPE GW SO G STM PIPE TEE UP GAS COCK AND UNION FS BALL DRAIN W/ HOSE END CONNECTION. REMOTE SENSOR CARBON DIOXIDE SENSOR CARBON MONOXIDE SENSOR T THERMOSTAT S CD CM H HUMIDISTAT *NOTE: ALL DASHED PLUMBING LINES INDICATE BELOW FLOOR ELEVATION UNLESS OTHERWISE NOTED ON DRAWINGS. S SPECIFIED MANUFACTURER / MODEL NECESSARILY USED ON THIS PROJECT. NOTE: NOT ALL VALVES ON THIS LIST ARE SYMBOL DESCRIPTION EQUALS BY LEGEND SPECIFICATION LIST BALL VALVE AUTO FLOW CONTROL VALVE CHECK VALVE GAS COCK STRAINER MILWAUKEE / 105 or 115 MILWAUKEE / CL 223 or CL 323 MILWAUKEE / BA 100 H FLOWSET / AV POTTROFF / VFD-10 TRERICE / 600C METRAFLEX / METRASPHERE EPDM FLOWSET / YR KEYSTONE / SERIES 500 AMTROL 705 WATTS / SERIES 40, 140, 240, or 340 BY T.C. CONTRACTOR AMBER-BOOTH / 2600 EPDM NIBCO NIBCO STOCKHAM MILLIKEN CENTERLINE - ASHCROFT / MAG PETERSON / PETE's PLUG - - KEYSTONE RED & WHITE - - - - - NIBCO DEZURIK - GERAND APOLLO BURKET BARCO KECKLEY KECKLEY ASHCROFT / MA CONBRACO CONBRACO - UNIVERSAL / 45PT-N NIBCO - - - - - NIBCO GRISWOLD STOCKHAM - - MASON / MFNC EPDM WEKSLER / EA14 WEKSLER / AA5H - RED & WHITE RED & WHITE - - - - NIBCO - - - - SKINNER GERAND TEMPERING VALVE LEONARD LAWLER VENTURI REDUCED PRESSURE MANUAL AIR VENT AUTOMATIC AIR VENT FLEXIBLE PIPE CONNECTION THERMOMETER PRESSURE GAUGE SMOKE DAMPER PRESSURE/TEMP. RELIEF P-T TAP STRAINER W/ BLOWOFF VALVE FIRE DAMPER FIRE & SMOKE DAMPER BOILER DRAIN VALVE FLOWSET / SUPERSEAL MILWAUKEE / 105 or 115 MILWAUKEE / 590T or 1590T MILWAUKEE / 509T, 1590T, F2974(M)(A), 548, or 1400 SERIES - MILWAUKEE / BA-100 or BA-150 WATTS / ACV 115 FLOWSET / ACCUSETTER ASCO / RED HAT BY T.C. CONTRACTOR WATTS / SERIES 77S with B-6081 VALVE MAXITROL / BV37 or BV64 WATTS / 909QTS POTTROFF / FSD-142 POTTROFF / SD-142 WATTS / B-3000 or B-3001 for 1/2" - 3" FLOWSET / VW WATTS / SERIES 77S for 1/2" thru 2-1/2" TRERICE / BX91403 1/2 HOFFMAN FLOWSET A PRESSURE REDUCING VALVE BALANCING VALVE GATE VALVE BACKFLOW PREVENTOR SOLENOID VALVE WAFER BALANCE VALVE BUTTERFLY VALVE STOP/DRAIN VALVE GATE VALVE IN GROUND BOX GLOBE VALVE TEMP. CONTROL - 2-WAY TEMP. CONTROL - 3-WAY PLUG VALVE - GAS PRESSURE REGULATOR SCHLUMBERGER / VARIES - - AIR ADMITTANCE VALVE STUDOR VENT - - APOLLO / 78-103-1 1/2" N.P.T. BY HOSE NIBCO STOCKHAM GENERAL NOTES 1. FOLLOW ALL APPLICABLE CODES AND ORDINANCES. PAY ALL FEES AND PERMITS AND ATTAIN THE SAME. 2. ALL EQUIPMENT, INSULATION, AND CONTROLS TO MEET LOCAL JURISDICTIONAL AUTHORITY'S ADOPTED ENERGY CODE. 3. VISIT SITE AND ASCERTAIN EXISTING CONDITIONS PRIOR TO BID. 4. THE INFORMATION PRESENTED ON THIS DRAWING IS DIAGRAMMATIC AND IS NOT TO BE SCALED. IT DOES NOT NECESSARILY REPRESENT ALL ELBOWS, DUCT EXTENSIONS, OFFSETS, HANGERS, ETC. REQUIRED FOR A COMPLETE WORKING SYSTEM. 5. SHOP DRAWINGS SHALL BE SUBMITTED ON ALL VALVES, FIXTURES, INSULATION, G.R.D.'S AND EQUIPMENT FOR RESPONSE PRIOR TO ORDERING. SIX (6) COPIES OF EACH IN ONE SUBMITTAL WITHIN 10 DAYS OF SIGNING CONTRACT. CLEARLY NOTE ANY DEVIATION BETWEEN SUBMITTED ITEMS AND SPECIFIED ITEMS ON THE COVER SHEET OF THE SUBMITTAL. FAILURE TO SUBMIT MAY CAUSE SPECIFIED ITEMS TO BE REJECTED AND REPLACED AT CONTRACTOR'S EXPENSE. 6. EXTRA COSTS OR CHANGES ALLOWED ONLY IF APPROVED IN WRITING BY ARCHITECT/OWNER WITH DOLLAR AMOUNT PRIOR TO ORDERING. NO EXTENSIONS OF COMPLETION TIME ALLOWED WITHOUT WRITTEN AUTHORIZATION. 7. THIS CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL FIELD CONDITIONS PRIOR TO THE PURCHASE OF ANY MATERIALS AND THE COMMENCEMENT OF ANY WORK AND IS TO NOTIFY THE ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION. 8. PROVIDE OWNER WITH 3 SETS OF TYPEWRITTEN AND BOUND "OPERATING INSTRUCTIONS" FOR ALL SYSTEMS AND EQUIPMENT, INCLUDING MANUFACTURER'S MAINTENANCE MANUALS. INCLUDE APPROVED EQUIPMENT SUBMITTALS, EQUIPMENT START-UP REPORTS, LUBRICATION, FILTER TYPES AND SIZES, BALANCE REPORT, STARTING AND STOPPING PROCEDURES, AND LIST SERVICE CONTRACTOR'S 24 HOUR TELEPHONE NUMBERS. 9. CONCEAL ALL WORK IN FINISHED AREAS. 10. CUT AND PATCH TO MATCH ADJACENT AREAS. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED WITHOUT STRUCTURAL ENGINEER'S WRITTEN APPROVAL. 11. GUARANTEE ALL LABOR AND EQUIPMENT FOR ONE YEAR FROM THE DATE OF ACCEPTANCE BY OWNER. 12. PROVIDE FACTORY AUTHORIZED START-UPS AND WRITTEN START-UP REPORTS ON ALL EQUIPMENT. 13. FIREPROOF ALL PENETRATIONS OF RATED FLOOR/WALL/CEILING/ROOF ASSEMBLIES. FIREPROOFING AND INSTALLATION TO BE UL CLASSIFIED AND ICBO APPROVED, SUITABLE FOR MOISTURE AND VIBRATION. METALCAULK BY RECTORSEAL OR EQUAL. INSTALL PER ALL MANUFACTURER RECOMMENDATIONS. SUBMIT FIRE STOP SCHEDULE BY MANUFACTURER. 14. PROVIDE CHROME-PLATED FLOOR, WALL, AND CEILING ESCUTCHEONS OF ADJUSTABLE TYPE ON ALL PIPES PASSING THROUGH WALLS, PARTITIONS, AND FLOORS AFTER PAINTING IS COMPLETED. MECHANICAL NOTES 1. IDENTIFY ALL HVAC AND REFRIGERATION EQUIPMENT AS TO THE AREA SERVED BY THE EQUIPMENT. IDENTIFICATION SHALL BE ENGRAVED PLASTIC TAGS OR BRASS PERMANENTLY AFFIXED TO EACH PIECE OF EQUIPMENT. 2. PROVIDE UL RATED FIRE OR FIRE/RADIATION DAMPERS WHERE INDICATED ON PLANS OR SCHEDULES. INSTALL PER BUILDING DEPARTMENT, UL, AND SMACNA REQUIREMENTS. INCLUDE LABELED ACCESS FOR DUCT AND CEILING/WALL STRUCTURES. ACCESS DOORS TO BE UL RATED IN ALL FIRE RATED ARCHITECTURAL ASSEMBLIES. INCLUDE TRANSFORMERS FOR 115V/24V ELECTRICAL CONNECTION. 3. PROVIDE ALL CURBS, SUPPORTS, AND ANCHORS FOR MECHANICAL WORK. NO CHAIN, TAPE, OR WIRE MAY BE USED FOR HANGING OR SUPPORTING. PROVIDE AND INSTALL ALL NECESSARY SHIMS AND LEVELING DEVICES TO PROPERLY INSTALL ALL EQUIPMENT IN A LEVEL CONDITION. 4. RECEIVE, UNCRATE, ASSEMBLE, INSURE, AND INSTALL IN CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS ALL EQUIPMENT FURNISHED BY THIS CONTRACT AND FURNISHED BY THE OWNER. 5. THE NEW MECHANICAL SYSTEMS CONSISTING OF THE AIR DISTRIBUTION SYSTEM WITH: DUCTWORK, FLEXIBLE DUCT, DIFFUSERS, GRILLES, DAMPERS, CONTROL SYSTEMS, ETC. SHALL BE BY THE MECHANICAL CONTRACTOR. 6. CEILING CAVITY IS NOT A RETURN AIR PLENUM. 7. DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS. OVERALL OUTSIDE DUCT DIMENSIONS SHALL BE ADJUSTED TO ALLOW FOR ANY LINER THICKNESS. 8. THIS CONTRACTOR SHALL COORDINATE ALL DUCTWORK WITH OTHER TRADES PRIOR TO INSTALLATION. 9. WEATHERPROOF ALL MECHANICAL ROOF PENETRATIONS PER CODES AND ALL ROOFING MANUFACTURER RECOMMENDATIONS. 10. PROVIDE FIRE OR SMOKE DETECTORS ON RETURN FOR MECHANICAL SYSTEMS OVER 2000 CFM AS REQUIRED BY CODES OR BUILDING STANDARDS. IF TWO OR MORE MECHANICAL SYSTEMS (I.E. ROOFTOP UNITS) SERVE THE SAME AREA AND WHEN COMBINED EXCEED 2000 CFM, A FIRE OR SMOKE DETECTOR SHALL BE INSTALLED ON THE RETURN OF EACH UNIT WHEN REQUIRED BY LOCAL AUTHORITIES. 11. PROVIDE SLEEVES AND COLLARS FOR ALL DUCTWORK AND PIPES THROUGH WALLS, FLOORS, AND CEILINGS. SEAL ALL EXTERNAL PENETRATIONS WEATHER TIGHT WITH EXTERIOR COMMERCIAL GRADE CAULK. FIREPROOF ALL PENETRATIONS OF FIRE RATED WALLS, FLOORS AND CEILINGS. 12. CONFIRM VOLTAGE, PHASE, AND AMPACITY WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT. ALL CONTROL AND INTERLOCK WIRING FOR MECHANICAL EQUIPMENT BY MECHANICAL CONTRACTOR. THREE PHASE MOTORS TO HAVE MAGNETIC STARTERS WITH PROTECTION ON ALL THREE LEADS. CONTROLS AND HEATING/COOLING EQUIPMENT TO AUTOMATICALLY RESTART AFTER POWER FAILURE. ALL WIRE TO BE IN 13. ALL RECIRCULATED AIR SHALL PASS THROUGH STANDARD 30% MERV 8, THROW AWAY FILTERS. PROVIDE ONE ADDITIONAL CLEAN SET FOR OWNER AT PROJECT COMPLETION. 14. A MINIMUM CLEARANCE OF 36 INCHES SHALL BE PROVIDED AROUND ANY EQUIPMENT OR COMPLY WITH MANUFACTURER'S REQUIREMENTS (I.E., FANS, PUMPS, BOILERS, AIR CONDITIONERS, ETC.) FOR SERVICE AND MAINTENANCE. GAS FIRED APPLIANCES SHALL BE VENTED PER THE MANUFACTURER'S LISTING. PROVIDE COMBUSTION AIR AS REQUIRED PER CODE. 15. TEMPERATURE CONTROLS - THE HVAC SYSTEM CONTROLS ARE TO BE FULLY AUTOMATIC. ALL CONTROLS ARE TO BE ELECTRIC. TEMPERATURE CONTROL SETUP AND SETBACK SHALL BE ACCOMPLISHED BY MEANS OF AN ELECTRIC THERMOSTAT WITH THE FOLLOWING FEATURES BEING STANDARD: a. ADJUSTABLE HEATING AND COOLING SETPOINTS. b. NIGHT AND WEEKEND PROGRAMMABLE SETBACK. c. AUTOMATIC CHANGEOVER BETWEEN HEATING AND COOLING CYCLES IN COMMON AREAS (MANUAL CHANGE d. MINIMUM JOB EIGHT (8) HOUR BATTERY BACKUPS DURING POWER FAILURE. e. OPTIMAL SYSTEM STARTUPS TO ENSURE CORRECT TEMPERATURE AT OCCUPANCY. f. LOCKABLE COVERS IN COMMON AREAS. g. ALL CONTROL SYSTEMS SHALL BE DESIGNED AND PROVIDED BY A CONTROL MANUFACTURER WHO HAS BEEN IN THE BUSINESS OF MANUFACTURING, DESIGNING AND INSTALLING CONTROL COMPONENTS AND SYSTEMS FOR A MINIMUM OF TEN (10) YEARS. OVER IN RESIDENCES.) 18 ASI 16 ASI 16 18 Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — in. Final Data Total Fan CFM Actual 230 Measured Data Fan RPM Actual DIRECT DRIVE Test Pressures Fan SP In Actual NO ACCESS in. wc Fan SP Out Actual NO ACCESS in. wc System/Unit Area Serve d Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instruments Open Area (sq ft) Ak (sq ft) Final Vel FPM Inlet-01 ER 100 100 100 100 Flow Hood 1.000 1.000 100 Inlet-02 ER 150 160 160 107 Flow Hood 1.000 1.000 160 Totals: - - - 250 260 260 104 - - - - EF-06-04 Exhaust Inlet Summary JEDI Balancing, Inc. Page 23 of 23 Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — in. Final Data Total Fan CFM Actual 230 Measured Data Fan RPM Actual DIRECT DRIVE Test Pressures Fan SP In Actual NO ACCESS in. wc Fan SP Out Actual NO ACCESS in. wc System/Unit Area Serve d Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instruments Open Area (sq ft) Ak (sq ft) Final Vel FPM Inlet-01 ER 100 90 90 90 Flow Hood 1.000 1.000 90 Inlet-02 ER 150 140 140 93 Flow Hood 1.000 1.000 140 Totals: - - - 250 230 230 92 - - - - EF-06-03 Exhaust Inlet Summary JEDI Balancing, Inc. Page 22 of 23 Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — in. Final Data Total Fan CFM Actual 255 Measured Data Fan RPM Actual DIRECT DRIVE Test Pressures Fan SP In Actual NO ACCESS in. wc Fan SP Out Actual NO ACCESS in. wc System/Unit Area Serve d Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instruments Open Area (sq ft) Ak (sq ft) Final Vel FPM Inlet-01 ER 100 140 100 100 Flow Hood 1.000 1.000 100 Inlet-02 ER 150 115 155 103 Flow Hood 1.000 1.000 155 Totals: - - - 250 255 255 102 - - - - EF-06-02 Exhaust Inlet Summary JEDI Balancing, Inc. Page 21 of 23 Fan Sheave Model / Size — Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — in. Final Data Total Fan CFM Actual 320 Fan CFM Test Method FLOW HOOD Measured Data Fan RPM Actual DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. wc Fan SP Out Actual NO ACCESS in. wc System/Unit Area Serve d Outlet Type Size (in) Design Reading Prelim Reading Final Reading % Final Instruments Open Area (sq ft) Ak (sq ft) Final Vel FPM Inlet-01 TOTAL 250 320 240 96 Flow Hood 1.000 1.000 240 Totals: - - - 250 320 240 96 - - - - EF-06-01 Exhaust Inlet Summary JEDI Balancing, Inc. Page 20 of 23 Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 700 Outside Air CFM Actual 105 OA Damper Pos 90 CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 595 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5I/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5I/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 20x20x1 JEDI Balancing, Inc. Page 18 of 23 Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 710 Outside Air CFM Actual 105 OA Damper Pos 50 % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 605 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5H/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5H/SF Filter Bank Filter Type PLEATED Filter Quantity (set 1) 1 Filter Size (set 1) 20x20x1 JEDI Balancing, Inc. Page 16 of 23 Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 660 Outside Air CFM Actual 105 OA Damper Pos FULLY CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 555 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5G/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5G/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 12x24x1 JEDI Balancing, Inc. Page 14 of 23 Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 650 Outside Air CFM Actual 110 OA Damper Pos 90 CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 540 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5F/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5F/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 12x24x1 JEDI Balancing, Inc. Page 12 of 23 FCU-1.5E/Supply Fan Drive Type DIRECT DRIVE Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 705 Outside Air CFM Actual 100 OA Damper Pos 80 CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 605 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5E/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz JEDI Balancing, Inc. Page 10 of 23 Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 650 Outside Air CFM Actual 110 OA Damper Pos 90 CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 540 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5D/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5D/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 12x24x1 JEDI Balancing, Inc. Page 8 of 23 FCU-1.5C Supply Outlet Summary JEDI Balancing, Inc. Page 7 of 23 Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 705 Outside Air CFM Actual 95 OA Damper Pos 90 CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 615 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5C/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5C/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 12x24x1 JEDI Balancing, Inc. Page 6 of 23 Motor Sheave Make — Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 645 Outside Air CFM Actual NOT APPLICABLE OA Damper Pos — % OA CFM Test Method — Return Air CFM Actual 645 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5B/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5B/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 12x24x1 JEDI Balancing, Inc. Page 4 of 23 1.000 1.000 190 Totals: - - - 650 825 700 108 - - - - FCU-1.5A Supply Outlet Summary JEDI Balancing, Inc. Page 3 of 23 Motor Sheave Model / Size — in. Motor Sheave Bore — in. Fan Sheave Make — Fan Sheave Model / Size — in. Fan Sheave Bore — in. Sheave Center Line — in. Number of Belts — Belt Make — Belt Size — Final Data Total CFM Actual 700 Outside Air CFM Actual 105 OA Damper Pos 90 CLOSED % OA CFM Test Method SUPPLY - RETURN Return Air CFM Actual 595 RA Damper Position NOT APPLICABLE Coil Velocity NOT GIVEN FPM Duct Static Setpoint NOT APPLICABLE in. wc Measured Data FCU-1.5A/Supply Fan Fan RPM Actual — Motor RPM Actual — Fan Rotation - Actual COUNTER CLOCKWISE Fan Speed / Setpoint — Operating Hertz 60 Hz Filter Data FCU-1.5A/SF Filter Bank Filter Service RETURN Filter Type MERV 8 Filter Quantity (set 1) 1 Filter Size (set 1) 12x24x1 JEDI Balancing, Inc. Page 2 of 23