HomeMy WebLinkAbout215 Mathews St - Special Inspections/Field Verification - 12/18/2018Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 12/18/18 PROJECT 215 Mathews Offices 215 Mathews Street Fort Collins, CO ***Final Report*** ARCHITECT Greg D. Fisher 3115 Clyde Street Fort Collins, CO ENGINEER Integrated Mechanical, LLC 223 Linden Street Suite 204 Fort Collins, CO CONTRACTOR Air Comfort, Inc. 150 Rome Ct. Fort Collins, CO Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: 215 Mathews Offices ADDRESS: 215 Mathews Street Fort Collins, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:12/18/18 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:12/18/18 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 12/18/18 CERTIFICATION EXPIRATION DATE: 3/31/2020 Table Of Contents PROJECT: LOCATION: 215 Mathews Offices Fort Collins, CO DATE: CONTACT: AUTHOR: 12/18/2018 Emerson Moore Emerson Moore Table Of Contents 1 Instrument Calibration Report.pdf............................................................................................................................ 1 2 Abbreviation Report.pdf............................................................................................................................................ 3 3 Roof Top Unit........................................................................................................................................................... 4 3.1 (E)RTU............................................................................................................................................................... 4 3.2 (E)RTU/VVT-01.................................................................................................................................................. 4 3.3 (E)RTU/VVT-02.................................................................................................................................................. 5 3.4 (E)RTU/VVT-03.................................................................................................................................................. 5 3.5 (E)RTU/VVT-04.................................................................................................................................................. 6 3.6 (E)RTU/VVT-05.................................................................................................................................................. 6 3.7 (E)RTU/VVT-06.................................................................................................................................................. 7 3.8 (E)RTU/VVT-07.................................................................................................................................................. 7 4 Mechanical 215 Mathews 2nd Floor 71118.pdf........................................................................................................ 8 L.H. Finn and Associates Final Report Manufacturer Model Serial Application Cal. Date Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014 Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015 Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016 Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 11/9/2018 Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 7/7/2017 Cooper SH66A 92711016 Temperature Measurement 10/9/2017 Extech 461895 Q394479 Rotation Measurement 6/7/2018 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 3/8/2016 Extech 461895 Q331990 Rotation Measurement 11/9/2018 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 10/3/2017 Extech 461895 Q590099 Rotation Measurement 4/17/2017 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 11/5/2015 Fluke 336 97110539R Electrical Measurement 4/5/2016 Fluke 336 97110538R Electrical Measurement 9/29/2015 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 335 72990071 Electrical Measurement 11/5/2018 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 10/3/2017 Fluke 374 20030354 Electrical Measurement 6/4/2018 TSI 8322 55100720 Air Velocity Measurement 10/4/2017 Shortridge ADM-860C M05789 Digital Manometer 11/25/2015 Shortridge ADM-860C M06821 Digital Manometer 6/1/2018 Shortridge ADM-860C M07352 Digital Manometer 6/6/2016 Shortridge ADM-860C M09123 Digital Manometer 4/18/2016 Shortridge ADM-860C M09347 Digital Manometer 9/26/2015 Shortridge ADM-860C M10144 Digital Manometer 4/14/2017 Shortridge ADM-860C M10371 Digital Manometer 11/5/2015 Shortridge ADM-860C M11448 Digital Manometer 4/14/2017 Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015 Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 6/1/2018 Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Project: 215 Mathews Offices Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 1 of 13 Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017 Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 4/19/2018 Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 4/19/2018 Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 9/29/2016 Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 2/26/2018 Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 2/26/2018 Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 10/2/2016 Evergreen Telemetry S-PVF-1 1600322 Pressure Velocity Module 10/3/2016 Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700214 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700216 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/12/2017 Evergreen Telemetry RM-T-1 1700269 Radio Module 5/17/2017 Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1600235 Radio Module 10/12/2016 Evergreen Telemetry RM-T-1 1600233 Radio Module 10/14/2016 Evergreen Telemetry RM-T-1 1600234 Radio Module 10/16/2016 Evergreen Telemetry RM-T-1 1700260 Radio Module 4/21/2017 Evergreen Telemetry RM-T-1 1700261 Radio Module 4/21/2017 Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 5/17/2017 Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/11/2016 Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/13/2016 Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/15/2016 Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/17/2016 Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017 Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017 Evergreen Telemetry S-DP-125 1700112 Water Press. Sensing Module 3/2/2017 REMARKS: Not all equipment shown was used on this project. Project: 215 Mathews Offices INSTRUMENT CALIBRATION REPORT (Continue) Page 2 of 13 Project: 215 Mathews Offices Symbol Description Symbol Description A Airflow (L/S) NS Not Shown AF Air Foil NT No Information Tag ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceiling Diffuser SD Supply Diffuser CFM Airflow (Cubic Feet / Minute) SNKL Snorkel DD Direct Drive SP Static Pressure Des Design SPD Static Pressure Drop DWDI Double Width Double Inlet SR Supply Register EF Exhaust Fan SWSI Single Width Single Inlet EG Exhaust Grille T Temperature ( C ) ER Exhaust Register T Temperature ( F ) ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Frequency Drive GPM Waterflow (Gallons / Minute) VS Variable Speed HC Heat Coil W Waterflow (L/S) HER Heat Exchanger HRC Heat Recovery Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 3 of 13 Roof Top Unit PROJECT: LOCATION: 215 Mathews Offices Fort Collins, CO DATE: CONTACT: AUTHOR: 12/18/2018 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU Log: (E)RTU 12/13/2018 Emerson Moore Existing RTU to remain. See associated VAVs for work associated with this project. (E)RTU 12/13/2018 Emerson Moore Bypass Duct SP setpoint = 0.6 in. wc. Unit Data Unit Manufacturer Existing Test Data Total CFM Design 4500 CFM Total CFM Actual 4313 CFM Outside Air CFM Design 430 CFM Outside Air CFM Actual 441 CFM Return Air CFM Design 4070 CFM Return Air CFM Actual 3872 CFM Test Pressures OA Damper Pos Actual 15 % RA Damper Pos Actual 85 % Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-01 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 10 In. K Factor - 1 0.78 Term Box Test Data Max Des. CFM 540 CFM Max Act. CFM 550 CFM Min Des. CFM 165 CFM Min Act. CFM 173 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 2026 D-1 24x24 130 104 133 80 102 Outlet-02 2025 D-1 24x24 120 98 122 82 102 Outlet-03 2024 D-1 24x24 120 113 121 94 101 Outlet-04 2023 D-1 24x24 120 82 123 68 103 Outlet-05 Hall D-1 24x24 50 30 51 60 102 Totals: - - - 540 427 550 79 102 (E)RTU/VVT-01 Supply Outlet Summary L.H. Finn and Associates Roof Top Unit PROJECT: LOCATION: 215 Mathews Offices Fort Collins, CO DATE: CONTACT: AUTHOR: 12/18/2018 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-02 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 8 In. K Factor - 1 0.76 Term Box Test Data Max Des. CFM 460 CFM Max Act. CFM 457 CFM Min Des. CFM 140 CFM Min Act. CFM 137 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 2022 D-1 24x24 230 177 225 77 98 Outlet-02 2022 D-1 24x24 230 185 232 80 101 Totals: - - - 460 362 457 79 99 (E)RTU/VVT-02 Supply Outlet Summary Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-03 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 10 In. K Factor - 1 0.78 Term Box Test Data Max Des. CFM 590 CFM Max Act. CFM 595 CFM Min Des. CFM 100 CFM Min Act. CFM 104 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Roof Top Unit PROJECT: LOCATION: 215 Mathews Offices Fort Collins, CO DATE: CONTACT: AUTHOR: 12/18/2018 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-04 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 12 In. K Factor - 1 0.88 Term Box Test Data Max Des. CFM 920 CFM Max Act. CFM 918 CFM Min Des. CFM 280 CFM Min Act. CFM 277 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 2032 D-1 24x24 190 133 187 70 98 Outlet-02 2031 D-1 24x24 190 137 191 72 101 Outlet-03 2033 D-1 24x24 230 223 228 97 99 Outlet-04 2033 D-1 24x24 230 207 231 90 100 Outlet-05 207 D-2 24x24 80 97 81 121 101 Totals: - - - 920 797 918 87 100 (E)RTU/VVT-04 Supply Outlet Summary Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-05 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 8 In. K Factor - 1 0.73 Term Box Test Data Max Des. CFM 480 CFM Max Act. CFM 484 CFM Min Des. CFM 145 CFM Min Act. CFM 148 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final Roof Top Unit PROJECT: LOCATION: 215 Mathews Offices Fort Collins, CO DATE: CONTACT: AUTHOR: 12/18/2018 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-06 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 10 In. K Factor - 1 0.68 Term Box Test Data Max Des. CFM 630 CFM Max Act. CFM 624 CFM Min Des. CFM 190 CFM Min Act. CFM 188 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 2014 D-1 24x24 180 117 184 65 102 Outlet-02 Hall D-1 24x24 90 122 88 136 98 Outlet-03 2015 D-1 24x24 180 101 177 56 98 Outlet-04 2016 D-1 24x24 180 102 175 57 97 Totals: - - - 630 442 624 70 99 (E)RTU/VVT-06 Supply Outlet Summary Tested By: Emerson Moore Date: 12/13/2018 SYSTEM/UNIT: (E)RTU/VVT-07 Unit Data Manufacturer Titus Model Number DESV Box Inlet Size 12 In. K Factor - 1 0.77 Term Box Test Data Max Des. CFM 880 CFM Max Act. CFM 883 CFM Min Des. CFM 270 CFM Min Act. CFM 273 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim PLUMBING LEGEND: V G F W GW HWC HW TW CW CD HOT WATER CIRC. TEMPERED WATER NATURAL GAS PIPING WASTE PIPING VENT PIPING HOT WATER PIPING COLD WATER PIPING SOLENOID VALVE UNION CHECK VALVE BALANCE VALVE PRESS. RED. VALVE GATE VALVE GAS COCK BALL VALVE GREASE WASTE PIPING FIRE PIPING T & P RELIEF VALVE CONDENSATE PIPING PIPE ELBOW UP PIPE TEE DOWN PIPE TEE UP PIPE ELBOW DOWN PIPE CONTINUATION PIPE CAP GRADE CLEANOUT RD ORD ROOF DRAIN PIPE OVERFLOW RD PIPE FLOOR CLEANOUT WALL CLEANOUT ROOF DRAIN I.E. INVERT ELEVATION MECHANICAL DRAWING INDEX SHEET SHEET NAME NUMBER HVAC LEGEND: ROUND DUCT (NEW SHADED/EXISTING UNSHADED) RECT TAKE-OFF W/ DAMPER FROM ROUND MAIN RECT TAKE-OFF W/ DAMPER FROM RECT MAIN ROUND TAKE-OFF W/ DAMPER FROM ROUND MAIN ROUND TAKE-OFF W/ DAMPER FROM RECT MAIN DUCT WITH MOTORIZED DAMPER DUCT WITH COUNTERBALANCED DAMPER RETURN/EXHAUST GRILLE (DUCTED) AIRFLOW PATTERNS THERMOSTAT WITH ZONE TAG FIRE DAMPER TAG (E)R (E)R 1 (E)EWH (E)EWH 2 T RTU-1 (E)R 1 2 3 4 5 D 7 C B 0 A VVT-1 VVT-2 VVT-3 VVT-4 VVT-7 VVT-5 VVT-6 10"x8" D-1- 8"ø 130 D-1- 8"ø 120 D-1- 8"ø 120 D-1- 8"ø 120 D-1- 10"ø 230 D-1- 10"ø 230 10"x10" 12"ø D-1- 8"ø 50 D-1- 8"ø 190 D-2- 8"ø 200 12"x10" 8"x8" SUITE 203 2031 Office 2032 Office 2033 Conf. 2017 Office 2016 Office 2015 Office 2014 Office 2013 SUITE 201 2011 V EXISTING PACKAGED ROOFTOP UNIT SCHEDULE NUMBER MAKE & MODEL NUMBER (E)RTU CARRIER 48HCFD12 4,500 - TONS NOMINAL ORIEN- TATION TOTAL CFM OA CFM FAN RPM EXT STATIC MOTOR BHP MBH IN HEATING MBH OUT 5000 FT AFUE FUEL TYPE HEATING STAGES COOLING STAGES TOT MBH COOLING SENS MBH ENT DB DEG. F ENT WB DEG. F AMBIENT DB REF TYPE EER (SEER) FILTER TYPE TSTAT TYPE MIN CIR AMPS MAX FUSE ELEC VOLTAGE HEIGHT W/CURB LENGTH WIDTH WEIGHT W/CURB REMARKS 10 HORIZ 430* ----- - -- ------- - --- - -- - * REBALANCE OSA TO NEW VALUE INDICATED IN SCHEDULE. A UTILIZE EXISTING CARRIER CCN VVT CONTROLLER FOR VVT OPERATION A GRILLES, REGISTERS AND DIFFUSERS SCHEDULE NUMBER MAKE & MODEL NUMBER D-1 TITUS OMNI-3 SUPPLY DESCRIPTION COLOR FRAME REMARKS DUTY SIZE NECK SIZE FRAME TYPE FRAME CONST DAMPER ARCHITECTURAL UNI-FLO DIFFUSER WHITE 24/24 LAY-IN STEEL YES SEE PLAN APPROVED MANUFACTURERS: METALAIRE, KRUEGER G-1 TITUS PAR-3 RETURN/ EXHAUST PERFORATED FACE REGISTER WHITE 24/NO24 22/22 LAY-IN STEEL G-2 TITUS PAR-3 PERFORATED FACE REGISTER WHITE 24/NO12 22/10 LAY-IN STEEL RETURN/ EXHAUST G-3 LOUVERED FACE REGISTER WHITE SURFACE STEEL NO RETURN/ EXHAUST TITUS 350RL-1 SEE PLAN SEE PLAN D-2 TITUS OMNI-3 SUPPLY ARCHITECTURAL UNI-FLO DIFFUSER WHITE 24/24 SURFACE STEEL YES SEE PLAN WITH TRIM FRAME OUTSIDE AIR VENTILATION SCHEDULE ROOM 2012 OFFICE SYSTEM REMARKS (BASED ON ASHRAE 62.1-2010) AREA [SF] (Az) OCC DENSITY [#/1000SF] NUMBER PEOPLE (Pz) PEOPLE OA RATE [CFM/PERSON] (Rp) AREA OA RATE [CFM/SF] (Ra) BREATHING ZONE OA [CFM] (Vbz=RpxPz+RaxAz) DISTRIBUTION EFFECTIVENESS (Ez) OA INTAKE [CFM] (Vot=Vbz/Ez) OA PROVIDED [CFM] 2013 OFFICE 160 5 1 5 0.06 15 0.8 19 2011 SUITE 201 113 5 1 5 0.06 12 0.8 15 109 5 1 5 0.06 12 0.8 15 2014 OFFICE 117 5 1 5 0.06 12 0.8 15 2015 OFFICE 117 5 1 5 0.06 12 0.8 15 2016 OFFICE 117 5 1 5 0.06 12 0.8 15 2017 CONFERENCE 156 50 8 5 0.06 50 0.8 63 2021 SUITE 202 185 5 1 5 0.06 17 0.8 21 2022 CONFERENCE 169 50 9 5 0.06 56 0.8 70 2023 OFFICE 117 5 1 5 0.06 12 0.8 15 2024 OFFICE 117 5 1 5 0.06 12 0.8 15 2025 OFFICE 117 5 1 5 0.06 12 0.8 15 2026 OFFICE 117 5 1 5 0.06 12 0.8 15 2032 OFFICE 156 5 1 5 0.06 15 0.8 19 2031 SUITE 203 156 5 1 5 0.06 15 0.8 19 2033 OFFICE 150 5 1 5 0.06 15 0.8 19 207 HALL 802 - - - 0.06 49 0.8 62 427 430 (E)RTU PINCHDOWN BOX W/ELECTRIC REHEAT SCHEDULE NUMBER MAKE & MODEL NUMBER REMARKS VVT-1 CARRIER 35E-10 1 RATED FOR 5000 FT ELEVATION 10" 1 INLET SIZE OUTLET TYPE (WxH) 540 MAX CFM 300 MIN CFM N/A FAN CFM HEAT CFM 0.5" INLET S.P. N/A FAN HP 1.5 ELEC KW 1 STEPS EAT 55 LAT 73.9 ELEC DATA 120/1 ELECTRIC HEATING COIL 2 ISOLATION HANGER KIT 3 ELECTRIC HEATING COIL WITH FUSED DISCONNECT SWITCH 4 CARRIER CCN VVT CONTROLS 2 3 4 VVT-2 460 190 N/A 0.5" 1.0 1 74.9 120/1 1 2 3 4 VVT-3 590 300 N/A 0.5" 1.5 1 73.9 120/1 12"X10" 1 2 3 4 VVT-4 920 425 N/A 0.5" 2 2 72.8 120/1 14"X12" 1 3 4 VVT-5 480 190 N/A 0.5" 1.0 1 74.9 120/1 1 2 3 4 VVT-6 630 300 N/A 0.5" 1.5 2 73.9 120/1 12"X12" 1 3 4 VVT-7 880 425 N/A 0.5" 2 2 72.8 120/1 12"X12" 1 2 3 4 SINGLE DUCT CARRIER 35E-10 8" SINGLE DUCT CARRIER 35E-10 10" SINGLE DUCT CARRIER 35E-14 12" SINGLE DUCT CARRIER 35E-10 8" SINGLE DUCT CARRIER 35E-12 10" SINGLE DUCT CARRIER 35E-12 12" SINGLE DUCT 165 140 100 280 145 190 270 N/A N/A N/A N/A N/A N/A 55 55 55 55 55 55 12"X10" 12"X10" 10"X10" 2 2 NOTE: EXISTING VVT BY-PASS DAMPER LOCATED ON ROOF. BALANCE DAMPER AS FOLLOWS MAX CFM = 2,370, MINIMUM CFM = 0 SCALE: SOUND BOOT DETAIL NONE 24"x24" OR 24"x12" RETURN AIR GRILLE PAINT INTERIOR BLACK WHERE VISIBLE THRU GRILLE 1" RIGID FIBERGLASS DUCTBOARD IN RETURN AIR PLENUM 22"x10" OPEN ENDED DUCT 22"x22" DUCT FOR 24"X24" GRILLE OR 22"x10" DUCT FOR 24"x12" GRILLE SCALE: SINK WASTE & VENT ISOMETRIC NONE S-1 2" W CONNECT TO NEW 2" VENT IN ADJACENT RESTROOM TO (E) VENT OF GREATER OR EQUAL SIZE CONNECT TO NEW 2" WASTE IN ADJACENT RESTROOM TO (E) WASTE OF GREATER OR EQUAL SIZE 2" WCO-1 SCALE: PINCH-DOWN VAV BOX WITH ELECTRIC REHEAT DETAIL NONE ALLOW FOR REQUIRED NEC CLEARANCE. 36" MINIMUM BOX FLOW METERING STATION ELECTRIC HEATING COIL AND CONTROL ENCLOSURE CONTROLLER DAMPER FLEXIBLE CONNECTION. TYPICAL PRIMARY AIR DUCT, SIZE AS SHOWN ON EQUIPMENT SCHEDULE MIN. 3x DUCT DIA. PRIOR TO TRANSITION MVD UNLESS NOTED OTHERWISE EXHAUST/RETURN SUPPLY 45° SCALE: DUCT TAKE-OFF DETAIL RECTANGULAR NONE SCALE: DUCT TAKE-OFF DETAIL ROUND NONE RETURN AIR DIRECTION 45° LATERAL TAKE-OFF FITTING WORM DRIVE SS CLAMP FLEX DUCT SUPPLY WHEN USED AIR DIRECTION FITTING IS TO CONTAIN MVD WITH HANDLE AND LOCKNUT UNLESS NOTED OTHERWISE SCALE: DUCT TRANSITION DETAIL NONE DIVERGING AIRFLOW CONVERGING AIRFLOW CONVERGING AIRFLOW DIVERGING AIRFLOW 30° MAX CONVERGING AIRFLOW 15° MAX DIVERGING AIRFLOW = = 30° MAX CONVERGING AIRFLOW 15° MAX DIVERGING AIRFLOW = = RECTANGULAR OR ROUND DUCT RECTANGULAR OR ROUND DUCT NOTE: 1) DETAIL APPLIES TO ALL DUCTWORK ON DUCTWORK TRANSITIONING ON ALL FOUR SIDES, NONE OF THE TRANSITION ANGLES MAY EXCEED 15° 2) 223 Linden St., Suite 204 Fort Collins, CO 80524 Phone: 970-556-0570 Front-desk@int-mech.com 6/ 28/ 18 NJF 215 Mat hews Street | Fort Colli ns, Col orado 80524 CURRENT I SSUE: DRAWN BY: Architect 3115 Clyde St. | Fort Collins, CO 80524 | 90.484.8433 6/28/18 PERMIT I SSUE: CONST. I SSUE: M8. 1 MECHANICAL SCHEDULES, DETAILS, AND ISOMETRIC PLUMBING FIXTURE SCHEDULE: SINK - ELKAY LRAD151755, GOURMET SINGLE COMPARTMENT SINK, 15" X 17.5" O.D. X 5-1/2" DEEP BOWLS, 18 GAUGE, 304 STAINLESS STEEL, COUNTERTOP, SELF RIMMING, 3 HOLE, 4" CENTERS, BACK OUTLET DRAINS FOR ADA - KOHLER K-10430-CP FAUCET, ADA, SINGLE HANDLE, 9" SWING SPOUT, POLISHED CHROME FINISH, VEGETABLE SPRAY, 1-1/2" PVC P-TRAP, CHROME STOPS AND SUPPLIES - ISE BADGER 5 DISPOSAL, 1/2 HP, 120/240 VOLT S-1 WALL CLEANOUT - ZURN Z-1469 COVER PLATE, POLISHED 304 STAINLESS STEEL, PVC PIPE CLEANOUT - SEE PLAN FOR PIPE SIZE WCO-1 REFRIGERATOR BOX - SIOUX CHIEF 696R10 FIRE RATED OX BOX, 5.5"x4"x3.5" BOX, TOP MOUNTED COLD WATER 1/4 TURN VALVE RB-1 Page 10 of 13 Office 2012 COMMON 201 HALL 207 SUITE 202 2021 IT 206 KIT. 220 Conf. 2022 Office 2023 Office 2024 Office 2026 Office 2025 D-1- 8"ø 190 D-1- 8"ø 190 D-1- 10"ø 230 D-1- 10"ø 230 14"x12" 12"x10" 10"ø D-1- 10"ø 240 D-1- 10"ø 240 D-1- 8"ø 180 D-1- 8"ø 180 D-1- 8"ø 180 D-1- 8"ø 200 12"x12" 8"ø 10"x10" 8"x8" D-1- 8"ø 200 D-1- 10"ø 240 D-1- 10"ø 240 12"x12" 10"x10" 14"x14" D-1- 8"ø 90 34"x14" 14"ø 8"x8" 12"x10" 28"x14" 30"x14" 30"x14" 12"ø G-1 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 S-1 2" W T VVT-7 T VVT-6 T VVT-5 T VVT-4 T VVT-1 T VVT-2 T VVT-3 CW 3 4 4 (E)MSB 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 D-2- 8"ø 80 12"ø 12"ø 5 5 12"ø D-1- 8"ø 200 RB-1 8"ø 8"ø 10"ø 10"ø 8"ø 8"ø G-2 8"ø 8"ø 10"ø 10"ø 8"ø 8"ø 8"ø 8"ø 10"ø 7 7 7 7 7 8 9 10 10"ø 8"ø 8"ø 10 12"ø 10 10 FLAG NOTES: DEMO EXISTING OPEN ENDED 30"x20" SUPPLY AND RETURN AIR BACK TO VERTICAL AT CHASE BACK TO VERTICAL AT CHASE. CONNECT NEW DUCTWORK OF INDICATED SIZE TO BOTH SIDES OF EXISTING DUCT INSIDE OF CEILING. EXTEND EXISTING DUCT AS NECESSARY TO MAKE NEW CONNECTIONS. REMOVE EXISTING TEMPORARY RTU T'STAT AND PROVIDE NEW CONTROLS AS INDICATED ON PLANS. CONNECT NEW PLUMBING TO EXISTING WITHIN WALL AT THIS LOCATION. CONNECT 0.5" CW & HW, 2" WASTE AND 1.5" VENT TO EXISTING EQUAL OR GREATER SIZES. TERMINATE OPEN ENDED WITH WIRE MESH. MC TO COORDINATE WITH GC TO CUT OUT A 30"x14" SECTION IN THE WALL ABOVE THE CEILING IN LOCATION INDICATED. CUT OUT SHALL ACT AS A TRANSFER OF AIR FROM PLENUM TO CENTRAL RETURN DUCT. REFER TO SOUND BOOT DETAIL ON SHEET M7.1 FOR MORE INFORMATION ON INSTALLATION DETAILS. MC TO COORDINATE WITH GC TO CUT OUT A 18"x6" SECTION IN THE WALL ABOVE THE CEILING IN LOCATION INDICATED. CUT OUT SHALL ACT AS A TRANSFER AIR PATH. SUPPLY AND RETURN MAINS CONTINUED UP TO (E)RTU-1 ON ROOF, NOT SHOWN. REFER TO SCHEDULES FOR MORE INFORMATION. EXISTING VVT BY-PASS DAMPER AND FUNCTION IS LOCATED AT THE RTU EQUIPMENT ON ROOF AND IS NOT SHOWN. CONTRACTOR TO CONNECT EXISTING DAMPER TO NEW VVT CONTROLS AS NECESSARY. REFER TO SCHEDULES. BRANCH DUCTWORK UP FROM TOP OF MAIN AND ROUTE OVER STRUCTURAL BEAM AT GRIDLINE 'B' & 'C' AS INDICATED. TYPICAL. 1 2 3 4 5 6 7 8 9 10 FIXTURE ROUGH-IN SCHEDULE: SINK: REFRIGERATOR BOX: COLD WATER HOT WATER 0.5" 0.5" 0.5" - 223 Linden St., Suite 204 Fort Collins, CO 80524 Phone: 970-556-0570 Front-desk@int-mech.com 6/ 28/ 18 NJF 215 Mat hews Street | Fort Colli ns, Col orado 80524 CURRENT I SSUE: DRAWN BY: Architect 3115 Clyde St. | Fort Collins, CO 80524 | 90.484.8433 6/28/18 PERMIT I SSUE: CONST. I SSUE: SCALE: MECHANICAL SECOND FLOOR PLAN 3/16" = 1'-0" M2. 1 MECHANICAL SECOND FLOOR PLAN Page 9 of 13 FIRE/SMOKE DAMPER WITH DUCT DETECTOR DUCT WITH VOLUME DAMPER RETURN GRILLE (UNDUCTED) DIFFUSER WITH FLEX DUCT F FS RECT DUCT SIZE CHANGE RECT DUCT CHANGE TO ROUND RECT ELBOW UP (SUPPLY) RECT ELBOW UP (NON-SUPPLY) RECT ELBOW DOWN (SUPPLY) RECT ELBOW DOWN (NON-SUPPLY) ROUND ELBOW DOWN ROUND ELBOW UP ROUND ELBOW RECT ELBOW W/ TURNING VANES RECT DUCT (NEW SHADED/EXISTING UNSHADED) SENSOR WITH ZONE TAG SD SMOKE DAMPER WITH DUCT DETECTOR C CARBON DIOXIDE SENSOR O 2 T RTU-X S RTU-X 223 Linden St., Suite 204 Fort Collins, CO 80524 Phone: 970-556-0570 Front-desk@int-mech.com 6/ 28/ 18 NJF 215 Mat hews Street | Fort Colli ns, Col orado 80524 CURRENT I SSUE: DRAWN BY: Architect 3115 Clyde St. | Fort Collins, CO 80524 | 90.484.8433 6/28/18 PERMIT I SSUE: CONST. I SSUE: MP0.1 MECHANICAL GENERAL NOTES, LEGENDS AND DRAWING INDEX M2.1 MECHANICAL SECOND FLOOR PLAN M8.1 MECHANICAL SCHEDULES, DETAILS, AND ISOMETRIC GENERAL PLUMBING NOTES: PLUMBING WORK SHALL COMPLY WITH ALL APPLICABLE CODES. VERIFY ALL REQUIREMENTS PRIOR TO SUBMITTING BID OR COMMENCING WORK. THE PLUMBING DESIGN IS BASED ON THE 2015 INTERNATIONAL PLUMBING CODE. 1. WASTE AND VENT PIPING BELOW SLAB SHALL BE SCHEDULE 40, DWV, PVC, PLASTIC. FITTINGS SHALL BE PVC. 2. WASTE AND VENT PIPING ABOVE SLAB SHALL BE SCHEDULE 40, DWV, PVC, PLASTIC. FITTINGS SHALL BE PVC. 3. 4. 5. 8. POTABLE WATER PIPING BELOW GRADE SHALL BE TYPE K COPPER WITHOUT JOINTS. POTABLE WATER PIPING ABOVE GRADE SHALL BE TYPE L COPPER WITH SOLDERED COPPER FITTINGS AND NO LEAD SOLDER UNLESS NOTED OTHERWISE. POTABLE WATER BRANCH PIPING 1" AND SMALLER MAY BE PEX TUBING MANUFACTURED BY UPONOR/WIRSBO OR APPROVED EQUAL AT CONTRACTOR'S OPTION. POTABLE WATER VALVES SHALL BE FULL PORT, BALL TYPE. HANGERS FOR 2" AND SMALLER PIPE SHALL BE BAND TYPE, 2.5" AND LARGER SHALL BE CLEVIS TYPE. USE COPPER COATED TYPE ON COPPER PIPE. 6. 7. GENERAL HVAC NOTES: MECHANICAL WORK SHALL COMPLY WITH ALL APPLICABLE CODES. VERIFY ALL REQUIREMENTS PRIOR TO SUBMITTING BID OR COMMENCING WORK. THE MECHANICAL DESIGN IS BASED ON THE 2015 INTERNATIONAL MECHANICAL CODE. 1. 2. ALL DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEET METAL - CONSTRUCTION AND INSTALLATION SHALL CONFORM TO THE CURRENT EDITION OF SMACNA OR AS REQUIRED BY ALL APPLICABLE CODES. CONSTRUCT ALL SUPPLY AND RETURN DUCTWORK TO SMACNA 2" PRESSURE CLASS. CONSTRUCT ALL EXHAUST DUCTWORK TO SMACNA 1" PRESSURE CLASS. DIMENSIONS OF DUCTWORK SHOWN INDICATES CLEAR INSIDE DIMENSIONS - WHERE DUCT LINER IS TO BE ADDED, INCREASE THE SIZE OF SHEET METAL ACCORDINGLY. UNLESS NOTED OTHERWISE, THE SIZE OF THE BRANCH DUCT SERVING A SINGLE DIFFUSER SHALL BE THE SAME AS THE NECK SIZE OF THE DIFFUSER SERVED. FLEXIBLE DUCTWORK SHALL NOT EXCEED 8'-0" IN LENGTH. FLEXIBLE DUCTWORK SHALL BE UL181 LISTED WITH 50/25 SMOKE/FLAME RATING, CONSISTING OF POLYESTER FILM ENCAPSULATING AN INNER CORROSION RESISTANT STEEL WIRE HELIX CORE. FLEXIBLE DUCT SHALL INCLUDE AN EXTERIOR FIBERGLASS INSULATION WITH FOIL SCRIM FILM VAPOR BARRIER JACKET, R-6. MAINTAIN A MINIMUM 10'-0" SEPARATION FROM OUTSIDE AIR INTAKES TO EXHAUST TERMINATIONS AND PLUMBING VENTS. MAINTAIN A MINIMUM 3'-0" SEPARATION FROM EXHAUST TERMINATIONS TO OPERABLE WINDOWS AND DOORS. WALL MOUNTED THERMOSTATS AND SENSORS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. THERMOSTATS AND SENSORS LOCATED ON EXTERIOR WALL SURFACES SHALL BE PROVIDED WITH AN INSULATED SUB-BASE. TEMPORARY HEATING: THE PERMANENT HVAC SYSTEM MAY NOT BE UTILIZED FOR HEATING UNTIL ALL GYPSUM WORK IS COMPLETED AND HAS BEEN PAINTED. IF THE PERMANENT HVAC SYSTEM IS UTILIZED DURING CONSTRUCTION, ALL DUCT INTAKES SHALL BE COVERED WITH FILTER MEDIA (MERV-8 RATING). IF EXCESSIVE DUST OR DEBRIS HAS ENTERED THE SYSTEM THEN ALL COIL AND DUCT SURFACES SHALL BE CLEANED. NEW FILTERS ARE TO BE PROVIDED JUST PRIOR TO TURNOVER TO OWNER. TEMPORARY HEATING OF THE BUILDING PRIOR TO ANY USE OF THE PERMANENT HVAC SYSTEM SHALL BE THE RESPONSIBILITY OF THE G.C. 3. 4. 5. 6. 7. 8. 9. 10. WHERE CEILING SPACE IS TO BE USED AS A RETURN AIR PLENUM, COMPLY WITH ALL APPLICABLE CODES. ALL MATERIALS WITHIN THE CEILING PLENUM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50. 11. ENERGY CODE/INSULATION NOTES: THE MECHANICAL DESIGN IS BASED ON THE 2015 INTERNATIONAL ENERGY CONSERVATION CODE. 1. ALL SUPPLY, RETURN AND EXHAUST DUCTWORK SHALL BE SEALED AIRTIGHT WITH DUCT SEALANT ALONG ALL SEAMS AND JOINTS. 2. ALL RECTANGULAR SUPPLY DUCTWORK SHALL BE LINED WITH 1.5", 1.5 LB DENSITY DUCT LINER, MINIMUM R-5. 3. ALL CONCEALED ROUND SUPPLY DUCTWORK SHALL BE WRAPPED WITH 1.5" THICK FIBERGLASS INSULATION WITH FOIL SCRIM VAPOR BARRIER JACKET, MINIMUM R-5. 4. ALL RECTANGULAR RETURN DUCTWORK SHALL BE LINED WITH 1.5", 1.5 LB DENSITY DUCT LINER, MINIMUM R-5. 5. 6. ALL SUPPLY AND RETURN DUCTWORK INSTALLED OUTDOORS SHALL BE LINED WITH 2", 1.5 LB DENSITY DUCT LINER, MINIMUM R-8. DUCTWORK SHALL BE SEALED WATER TIGHT. HOT WATER PIPING SHALL BE INSULATED USING FIBERGLASS INSULATION WITH ALL SERVICE JACKET HAVING MAXIMUM 'K' FACTOR OF 0.27. INSULATION THICKNESS SHALL BE 1". HOT WATER RECIRCULATION PIPING SHALL BE INSULATED FIBERGLASS INSULATION WITH ALL SERVICE JACKET HAVING MAXIMUM 'K' FACTOR OF 0.27. INSULATION THICKNESS SHALL BE 1". COLD WATER PIPING SHALL BE INSULATED USING FIBERGLASS INSULATION WITH ALL SERVICE JACKET HAVING MAXIMUM 'K' FACTOR OF 0.27. INSULATION THICKNESS SHALL BE 0.5". 7. 8. 9. GENERAL MECHANICAL REQUIREMENTS: CODES AND PERMITS WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL CODES, REGULATIONS AND ORDINANCES. PERMITS NECESSARY FOR PERFORMANCE OF WORK SHALL BE SECURED AND PAID FOR BY THE CONTRACTOR. DRAWINGS AND COORDINATION DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC IN NATURE, AND ARE NOT INTENDED TO BE SCALED FOR EXACT MEASUREMENTS NOR TO SERVE AS SHOP DRAWINGS. CHANGES FROM THE PLANS MADE WITHOUT CONSENT OF THE ENGINEER SHALL RELIEVE THE ENGINEER OF RESPONSIBILITY FOR ALL CONSEQUENCES ARRIVING OUT OF SUCH CHANGES. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHERE CONDITIONS REQUIRE REASONABLE CHANGES TO THOSE INDICATED ON THE DRAWINGS, MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. COORDINATE ALL WORK WITH OTHER TRADES. WARRANTY WORKMANSHIP, MATERIALS, EQUIPMENT AND PROPER OPERATION SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE FROM THE OWNER. INITIAL ACCEPTANCE OF WORK SHALL NOT WAIVE THIS GUARANTEE. THIS GUARANTEE SHALL NOT INCLUDE NORMAL MAINTENANCE REQUIRED BY THE OWNER AS DESCRIBED IN EQUIPMENT OPERATION AND MAINTENANCE MANUALS. SUBMITTALS CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER A MINIMUM OF (5) COPIES OF SUBMITTAL BROCHURES FOR REVIEW. PROVIDE INFORMATION ON ALL MAJOR EQUIPMENT AS LISTED ON DRAWING EQUIPMENT SCHEDULES, AS WELL AS VALVES, DUCTWORK ACCESSORIES AND TEMPERATURE CONTROL DIAGRAMS AS APPLICABLE. OPERATION AND MAINTENANCE MANUALS CONTRACTOR SHALL FURNISH AT THE COMPLETION OF THE PROJECT (2) COPIES OF COMPLETE OPERATION AND MAINTENANCE MANUALS TO THE ARCHITECT/ENGINEER FOR REVIEW PRIOR TO TURNOVER TO OWNER. MANUALS TO BE BOUND AND INCLUDE INSTALLATION INSTRUCTIONS, REPLACEMENT PARTS LISTS AND MAINTENANCE INFORMATION ON ALL EQUIPMENT AS DESCRIBED IN THE SUBMITTALS SECTION. COMPLETED OPERATION AND MAINTENANCE MANUALS ARE TO BE FORWARDED TO THE OWNER WITHIN 90 DAYS AFTER OWNER BUILDING ACCEPTANCE. PRODUCT SUBSTITUTIONS MANUFACTURER MODEL NUMBERS LISTED ON THE DRAWINGS AND/OR SPECIFICATIONS ARE TO BE CONSIDERED AS THE BASIS OF DESIGN. WHERE TWO OR MORE ALTERNATE MANUFACTURERS OR MATERIALS ARE LISTED, THE CHOICE OF THESE SHALL BE OPTIONAL WITH THE CONTRACTOR. PRIOR TO THE AWARDING OF THE CONTRACT, CONTRACTOR MAY REQUEST A PROPOSED SUBSTITUTION OF MATERIALS IN WRITING TO THE ARCHITECT/ENGINEER NO LATER THAN SEVEN DAYS PRIOR TO THE RECEIPT OF BIDS. THE COST OF ANY CHANGES REQUIRED BY OTHER TRADES, INCLUDING A/E DESIGN, DUE TO THE USE OF EQUIPMENT AND/OR MATERIALS OTHER THAN THAT OF THE BASIS OF DESIGN SHALL BE PAID BY THE CONTRACTOR. RECORD DRAWINGS CONTRACTORS SHALL MAINTAIN A COMPLETE AND ACCURATE SET OF MARKED UP DRAWINGS SHOWING ACTUAL LOCATIONS OF INSTALLED WORK. THESE DRAWINGS ARE TO BE FORWARDED TO THE OWNER AS PART OF THE OPERATION AND MAINTENANCE MANUALS AT THE COMPLETION OF THE PROJECT. ACCESS DOORS PROVIDE ALL ACCESS DOORS/PANELS AS REQUIRED FOR ACCESS TO VALVES, DAMPERS, CONTROL DEVICES, FILTERS AND ANY OTHER ITEMS FOR WHICH ACCESS IS REQUIRED FOR EITHER OPERATION OR SERVICING. WHERE ACCESS DOORS ARE TO BE INSTALLED IN ASSEMBLIES REQUIRED TO HAVE A SPECIFIC FIRE RATING, ACCESS DOORS SHALL ALSO BE FIRE RATED. PIPING AND DUCTWORK SEALANT THROUGH RATED ASSEMBLIES PENETRATIONS SHALL BE SEALED AS REQUIRED IN ACCORDANCE WITH BUILDING AND MECHANICAL CODES TO RESIST THE PASSAGE OF FLAME AND PRODUCTS OF COMBUSTION IN ORDER TO MAINTAIN THE RESISTANCE RATING OF THE CONSTRUCTION BEING PENETRATED. PROTECTION OF MATERIALS AND EQUIPMENT CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALL WORK, MATERALS, AND EQUIPMENT PROVIDED UNDER THIS SECTION. PIPE OPENINGS SHALL BE CLOSED WITH CAPS OR PLUGS TO PREVENT THE ENTRANCE OF DEBRIS DURING CONSTRUCTION. ALL DUCTWORK OPENINGS SHALL BE SEALED CLOSED DURING CONSTRUCTION. EQUIPMENT AND PIPING IDENTIFICATION PROVIDE EQUIPMENT LABELS FOR ALL MAJOR EQUIPMENT, INCLUDING BUT NOT LIMITED TO AIR HANDLING SYSTEMS, FANS, VAV BOXES, CONTROLS, DAMPERS, CONTROL VALVES AND PUMPS. PROVIDE PIPE MARKERS ON CW, HW AND HWC SYSTEMS. LABELS TO BE AT MAXIMUM 8 FEET APART, WITH FLOW DIRECTION INDICATED, AS APPLICABLE. ADDITIONALLY, PROVIDE LABELING ON POTABLE WATER MANIFOLDS INDICATING PLUMBING FIXTURE SERVED BY THE OUTLET, AS APPLICABLE. LABELS SHALL BE AFFIXED OR ADHERED PERMANENTLY TO EQUIPMENT. EQUIPMENT INSTALLED INDOORS TO BE LABELED WITH EMBOSSING TAPE. EQUIPMENT INSTALLED OUTDOORS TO BE LABELED WITH ENGRAVED PLASTIC LAMINATE SIGNS. PIPE MARKERS TO BE SELF-ADHESIVE, MANUFACTURED FOR SUCH PURPOSE. STARTERS AND DISCONNECTS EQUIPMENT STARTERS SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR. EQUIPMENT DISCONNECTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR UNLESS NOTED OTHERWISE ON THE DRAWINGS. STARTERS SHALL BE NEMA TYPE, AND SHALL INCLUDE PHASE MONITORING FOR MOTORS 5 HP AND LARGER. TESTING TESTING SHALL BE PERFORMED ON THE FOLLOWING SYSTEMS SPECIFIED. ALL SYSTEMS LISTED MAY NOT BE INCLUDED IN PROJECT, REFER TO DRAWINGS FOR APPLICABLE SYSTEMS. SOIL, WASTE AND STORM DRAINAGE PIPING SHALL BE TESTED IN ACCORDANCE WITH APPLICABLE STATE AND LOCAL CODES. DOMESTIC WATER PIPING SHALL BE TESTED AND PROVEN WATERTIGHT UNDER A PRESSURE NOT LESS THAN THE WORKING PRESSURE OF THE SYSTEM FOR A 24 HOUR PERIOD. DOMESTIC WATER PIPING SYSTEM SHALL BE CHLORINATED AND STERILIZED IN ACCORDANCE WITH REQUIREMENTS OF LOCAL JURISDICTION. NATURAL GAS PIPING SHALL BE TESTED WITH AN AIR PRESSURE OF MINIMUM TWO TIMES THE DESIGN SYSTEM PRESSURE, BUT NO LESS THAN 3 PSIG, FOR A PERIOD OF 24 HOURS WITHOUT PRESSURE DROP. BALANCING SYSTEM BALANCING SHALL BE PERFORMED BY A CERTIFIED BALANCING CONTRACTOR. BALANCE ALL SYSTEMS INCLUDING AIRFLOW TO AND FROM ALL OPENINGS, AND PUMPED WATER SYSTEMS INCLUDING DOMESTIC WATER RECIRCULATION SYSTEMS AS APPLICABLE. MAKE ANY ADJUSTMENTS NECESSARY TO RESULT IN CONDITIONS INDICATED AND PROVIDE READJUSTMENTS TO ITEMS IN REPORT AS MAY BE REQUESTED BY ARCHITECT/ENGINEER. SUBMIT TWO COPIES OF TEST AND BALANCE REPORT FOR APPROVAL. FAN AND PUMP SYSTEMS TO BE BALANCED WITHIN PLUS OR MINUS 5 PERCENT OF LISTED VALUES. AIR INLETS AND OUTLETS TO BE BALANCED WITHIN PLUS 10 PERCENT OR MINUS 5 PERCENT OF LISTED VALUES. BALANCE REPORT TO INCLUDE: UNIT IDENTIFICATION MANUFACTURER AND NAMEPLATE DATA EQUIPMENT NAMEPLATE AMPERAGE AND ACTUAL AMPERAGE RPM (DESIGN AND ACTUAL) FAN CFM (DESIGN AND ACTUAL) FAN STATIC PRESSURE (DESIGN AND ACTUAL) PUMP GPM (DESIGN AND ACTUAL) PUMP DISCHARGE AND SUCTION PRESSURE REGISTER, GRILLE, DIFFUSER REFERENCE NUMBER AND LOCATION INLET/OUTLET CFM (DESIGN AND ACTUAL) FLOW DEVICE PRESSURE DROP, CFM OR GPM A FINAL BALANCING REPORT SHALL BE PROVIDED TO THE OWNER AFTER COMPLETION OF THE PROJECT. CLEANING AT THE COMPLETION OF WORK, ALL FIXTURES AND EQUIPMENT SHALL BE THOROUGHLY CLEANED AND DELIVERED IN A CONDITION SATISFACTORY TO THE ARCHITECT. ALL FILTERS SHALL BE REPLACED WITH NEW PRIOR TO OWNER ACCEPTANCE OF THE BUILDING. CITY OF FORT COLLINS GREEN CODE REQUIREMENTS: BEFORE OCCUPANCY AND AFTER ALL INTERIOR FINISHES ARE COMPLETE, THE BUILDING IS TO BE FLUSHED OUT (VENTILATED) FOR A PERIOD OF 14 DAYS. WHERE CONTINUOUS VENTILATION IS NOT POSSIBLE, THE AGGREGATE OF FLUSH-OUT PERIODS SHALL BE EQUIVALENT TO 14 DAYS. CONTRACTOR SHALL PROVIDE FLUSH-OUT REPORTS TO THE BUILDING OFFICIAL UPON COMPLETION OF WORK. CONTRACTOR TO COORDINATE WITH BUILDING OFFICIAL FOR INFORMATION TO BE CONTAINED IN FLUSH-OUT REPORTS. 1. PROTECT HVAC EQUIPMENT FROM CONSTRUCTION DUST AND DEBRIS. DO NOT OPERATE HVAC EQUIPMENT DURING CONSTRUCTION AND SEAL ALL DUCT OPENINGS WITH PLASTIC. 2. THE FOLLOWING LOW-VOLATILE ORGANIC COMPOUND (VOC) MATERIALS SHALL BE USED AS APPLICABLE TO THIS SCOPE OF WORK. -DUCT INSULATION ADHESIVE: DESIGN POLYMERICS 2501, 2502 OR APPROVED EQUAL. -DUCT SEALANT: DESIGN POLYMERICS 1010, 1015 OR APPROVED EQUAL. -FIRE CAULK: 3M FIRE BARRIER 1C 15WB+, FD 150+, CP 25WB+ OR APPROVED EQUAL. 3. MP0. 1 MECHANICAL GENERAL NOTES, LEGENDS AND DRAWING INDEX Page 8 of 13 Deviation % Final Deviation Outlet-01 2012 D-1 24x24 240 184 238 77 99 Outlet-02 2012 D-1 24x24 240 233 242 97 101 Outlet-03 2011 D-1 24x24 200 125 200 63 100 Outlet-04 2013 D-1 24x24 200 138 203 69 102 Totals: - - - 880 680 883 77 100 (E)RTU/VVT-07 Supply Outlet Summary L.H. Finn and Associates Final Report Page 7 of 13 % Prelim Deviation % Final Deviation Outlet-01 2017 D-1 24x24 240 173 242 72 101 Outlet-02 2017 D-1 24x24 240 188 242 78 101 Totals: - - - 480 361 484 75 101 (E)RTU/VVT-05 Supply Outlet Summary L.H. Finn and Associates Final Report Page 6 of 13 Deviation Outlet-01 220 D-2 24x24 200 155 202 78 101 Outlet-02 2021 D-1 24x24 190 138 190 73 100 Outlet-03 2021 D-1 24x24 200 163 203 82 102 Totals: - - - 590 456 595 77 101 (E)RTU/VVT-03 Supply Outlet Summary L.H. Finn and Associates Final Report Page 5 of 13 Final Report Page 4 of 13