HomeMy WebLinkAbout215 Mathews St - Special Inspections/Field Verification - 12/18/2018Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave., Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
12/18/18
PROJECT
215 Mathews Offices
215 Mathews Street
Fort Collins, CO
***Final Report***
ARCHITECT
Greg D. Fisher
3115 Clyde Street
Fort Collins, CO
ENGINEER
Integrated Mechanical, LLC
223 Linden Street
Suite 204
Fort Collins, CO
CONTRACTOR
Air Comfort, Inc.
150 Rome Ct.
Fort Collins, CO
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
PROJECT: 215 Mathews Offices
ADDRESS: 215 Mathews Street
Fort Collins, CO
The data presented in this report is an exact record of the system performance
and was obtained in accordance with NEBB Standard Procedures. Any
variances from design quantities which exceed NEBB tolerances are noted
throughout the report.
The air distribution systems have been tested & balanced and final adjustments
have been made in accordance with NEBB “Procedural Standards for Testing,
Adjusting & Balancing of Environmental Systems” and the project specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:12/18/18
The hydronic distribution systems have been tested & balanced and final
adjustments have been made in accordance with NEBB “Procedural Standards
for Testing, Adjusting & Balancing of Environmental Systems” and the project
specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:12/18/18
SUBMITTED & CERTIFIED BY
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
TAB SUPERVISOR: David C. Reichel
REG. NO.: 2389 SIGNATURE:
DATE: 12/18/18 CERTIFICATION EXPIRATION DATE: 3/31/2020
Table Of Contents
PROJECT:
LOCATION:
215 Mathews Offices
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
12/18/2018
Emerson Moore
Emerson Moore
Table Of Contents
1 Instrument Calibration Report.pdf............................................................................................................................ 1
2 Abbreviation Report.pdf............................................................................................................................................ 3
3 Roof Top Unit........................................................................................................................................................... 4
3.1 (E)RTU............................................................................................................................................................... 4
3.2 (E)RTU/VVT-01.................................................................................................................................................. 4
3.3 (E)RTU/VVT-02.................................................................................................................................................. 5
3.4 (E)RTU/VVT-03.................................................................................................................................................. 5
3.5 (E)RTU/VVT-04.................................................................................................................................................. 6
3.6 (E)RTU/VVT-05.................................................................................................................................................. 6
3.7 (E)RTU/VVT-06.................................................................................................................................................. 7
3.8 (E)RTU/VVT-07.................................................................................................................................................. 7
4 Mechanical 215 Mathews 2nd Floor 71118.pdf........................................................................................................ 8
L.H. Finn and Associates
Final Report
Manufacturer Model Serial Application Cal. Date
Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014
Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015
Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016
Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 11/9/2018
Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 7/7/2017
Cooper SH66A 92711016 Temperature Measurement 10/9/2017
Extech 461895 Q394479 Rotation Measurement 6/7/2018
Extech 461895 Q083481 Rotation Measurement 1/9/2014
Extech 461895 Q247569 Rotation Measurement 3/8/2016
Extech 461895 L268576 Rotation Measurement 3/8/2016
Extech 461895 Q331990 Rotation Measurement 11/9/2018
Extech 461895 Q477125 Rotation Measurement 9/25/2015
Extech 461895 Q477126 Rotation Measurement 4/5/2016
Extech 461895 Q527632 Rotation Measurement 10/3/2017
Extech 461895 Q590099 Rotation Measurement 4/17/2017
Extech RH390 9099221 Temperature / Humidity 4/9/2015
Fluke 335 96960004 Electrical Measurement 11/5/2015
Fluke 336 97110539R Electrical Measurement 4/5/2016
Fluke 336 97110538R Electrical Measurement 9/29/2015
Fluke 335 92008180 Electrical Measurement 11/4/2014
Fluke 335 72990071 Electrical Measurement 11/5/2018
Fluke 374 15460133 Electrical Measurement 4/18/2014
Fluke 374 20030351 Electrical Measurement 10/3/2017
Fluke 374 20030354 Electrical Measurement 6/4/2018
TSI 8322 55100720 Air Velocity Measurement 10/4/2017
Shortridge ADM-860C M05789 Digital Manometer 11/25/2015
Shortridge ADM-860C M06821 Digital Manometer 6/1/2018
Shortridge ADM-860C M07352 Digital Manometer 6/6/2016
Shortridge ADM-860C M09123 Digital Manometer 4/18/2016
Shortridge ADM-860C M09347 Digital Manometer 9/26/2015
Shortridge ADM-860C M10144 Digital Manometer 4/14/2017
Shortridge ADM-860C M10371 Digital Manometer 11/5/2015
Shortridge ADM-860C M11448 Digital Manometer 4/14/2017
Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015
Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 6/1/2018
Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015
REMARKS: Not all equipment shown was used on this project.
Project: 215 Mathews Offices
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
INSTRUMENT CALIBRATION REPORT
Page 1 of 13
Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017
Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 10/3/2017
Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017
Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 4/19/2018
Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 4/19/2018
Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 9/29/2016
Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 2/26/2018
Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 2/26/2018
Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 10/2/2016
Evergreen Telemetry S-PVF-1 1600322 Pressure Velocity Module 10/3/2016
Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700214 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700216 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/12/2017
Evergreen Telemetry RM-T-1 1700269 Radio Module 5/17/2017
Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016
Evergreen Telemetry RM-T-1 1600235 Radio Module 10/12/2016
Evergreen Telemetry RM-T-1 1600233 Radio Module 10/14/2016
Evergreen Telemetry RM-T-1 1600234 Radio Module 10/16/2016
Evergreen Telemetry RM-T-1 1700260 Radio Module 4/21/2017
Evergreen Telemetry RM-T-1 1700261 Radio Module 4/21/2017
Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 5/17/2017
Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/11/2016
Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/13/2016
Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/15/2016
Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/17/2016
Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017
Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017
Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017
Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017
Evergreen Telemetry S-DP-125 1700112 Water Press. Sensing Module 3/2/2017
REMARKS: Not all equipment shown was used on this project.
Project: 215 Mathews Offices
INSTRUMENT CALIBRATION REPORT (Continue)
Page 2 of 13
Project: 215 Mathews Offices
Symbol Description Symbol Description
A Airflow (L/S) NS Not Shown
AF Air Foil NT No Information Tag
ANA Access Not Available OD Outside Diameter
BI Backward Incline RPM Revolution Per Minute
CD Ceiling Diffuser SD Supply Diffuser
CFM Airflow (Cubic Feet / Minute) SNKL Snorkel
DD Direct Drive SP Static Pressure
Des Design SPD Static Pressure Drop
DWDI Double Width Double Inlet SR Supply Register
EF Exhaust Fan SWSI Single Width Single Inlet
EG Exhaust Grille T Temperature ( C )
ER Exhaust Register T Temperature ( F )
ESP External Static Pressure TSP Total Static Pressure
FC Forward Curve VFD Variable Frequency Drive
GPM Waterflow (Gallons / Minute) VS Variable Speed
HC Heat Coil W Waterflow (L/S)
HER Heat Exchanger
HRC Heat Recovery
Hz Hertz
ID Inside Diameter
In. WC Inches of Water Column
NA Not Applicable
NI Not Installed
NIC Not In Contract
NM Not Measurable
NPT No Pressure Tap
NR Not Readable
REMARKS:
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
ABBREVIATION REPORT
Page 3 of 13
Roof Top Unit
PROJECT:
LOCATION:
215 Mathews Offices
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
12/18/2018
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU
Log: (E)RTU 12/13/2018 Emerson Moore Existing RTU to remain. See associated VAVs for
work associated with this project.
(E)RTU 12/13/2018 Emerson Moore Bypass Duct SP setpoint = 0.6 in. wc.
Unit Data
Unit Manufacturer Existing
Test Data
Total CFM Design 4500 CFM
Total CFM Actual 4313 CFM
Outside Air CFM Design 430 CFM
Outside Air CFM Actual 441 CFM
Return Air CFM Design 4070 CFM
Return Air CFM Actual 3872 CFM
Test Pressures
OA Damper Pos Actual 15 %
RA Damper Pos Actual 85 %
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-01
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 10 In.
K Factor - 1 0.78
Term Box Test Data
Max Des. CFM 540 CFM
Max Act. CFM 550 CFM
Min Des. CFM 165 CFM
Min Act. CFM 173 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 2026 D-1 24x24 130 104 133 80 102
Outlet-02 2025 D-1 24x24 120 98 122 82 102
Outlet-03 2024 D-1 24x24 120 113 121 94 101
Outlet-04 2023 D-1 24x24 120 82 123 68 103
Outlet-05 Hall D-1 24x24 50 30 51 60 102
Totals: - - - 540 427 550 79 102
(E)RTU/VVT-01 Supply Outlet Summary
L.H. Finn and Associates
Roof Top Unit
PROJECT:
LOCATION:
215 Mathews Offices
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
12/18/2018
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-02
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 8 In.
K Factor - 1 0.76
Term Box Test Data
Max Des. CFM 460 CFM
Max Act. CFM 457 CFM
Min Des. CFM 140 CFM
Min Act. CFM 137 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 2022 D-1 24x24 230 177 225 77 98
Outlet-02 2022 D-1 24x24 230 185 232 80 101
Totals: - - - 460 362 457 79 99
(E)RTU/VVT-02 Supply Outlet Summary
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-03
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 10 In.
K Factor - 1 0.78
Term Box Test Data
Max Des. CFM 590 CFM
Max Act. CFM 595 CFM
Min Des. CFM 100 CFM
Min Act. CFM 104 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Roof Top Unit
PROJECT:
LOCATION:
215 Mathews Offices
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
12/18/2018
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-04
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 12 In.
K Factor - 1 0.88
Term Box Test Data
Max Des. CFM 920 CFM
Max Act. CFM 918 CFM
Min Des. CFM 280 CFM
Min Act. CFM 277 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 2032 D-1 24x24 190 133 187 70 98
Outlet-02 2031 D-1 24x24 190 137 191 72 101
Outlet-03 2033 D-1 24x24 230 223 228 97 99
Outlet-04 2033 D-1 24x24 230 207 231 90 100
Outlet-05 207 D-2 24x24 80 97 81 121 101
Totals: - - - 920 797 918 87 100
(E)RTU/VVT-04 Supply Outlet Summary
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-05
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 8 In.
K Factor - 1 0.73
Term Box Test Data
Max Des. CFM 480 CFM
Max Act. CFM 484 CFM
Min Des. CFM 145 CFM
Min Act. CFM 148 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
Roof Top Unit
PROJECT:
LOCATION:
215 Mathews Offices
Fort Collins, CO
DATE:
CONTACT:
AUTHOR:
12/18/2018
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-06
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 10 In.
K Factor - 1 0.68
Term Box Test Data
Max Des. CFM 630 CFM
Max Act. CFM 624 CFM
Min Des. CFM 190 CFM
Min Act. CFM 188 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 2014 D-1 24x24 180 117 184 65 102
Outlet-02 Hall D-1 24x24 90 122 88 136 98
Outlet-03 2015 D-1 24x24 180 101 177 56 98
Outlet-04 2016 D-1 24x24 180 102 175 57 97
Totals: - - - 630 442 624 70 99
(E)RTU/VVT-06 Supply Outlet Summary
Tested By: Emerson Moore
Date: 12/13/2018
SYSTEM/UNIT: (E)RTU/VVT-07
Unit Data
Manufacturer Titus
Model Number DESV
Box Inlet Size 12 In.
K Factor - 1 0.77
Term Box Test Data
Max Des. CFM 880 CFM
Max Act. CFM 883 CFM
Min Des. CFM 270 CFM
Min Act. CFM 273 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
PLUMBING LEGEND:
V
G
F
W
GW
HWC
HW
TW
CW
CD
HOT WATER CIRC.
TEMPERED WATER
NATURAL GAS PIPING
WASTE PIPING
VENT PIPING
HOT WATER PIPING
COLD WATER PIPING
SOLENOID VALVE
UNION
CHECK VALVE
BALANCE VALVE
PRESS. RED. VALVE
GATE VALVE
GAS COCK
BALL VALVE
GREASE WASTE PIPING
FIRE PIPING
T & P RELIEF VALVE
CONDENSATE PIPING
PIPE ELBOW UP
PIPE TEE DOWN
PIPE TEE UP
PIPE ELBOW DOWN
PIPE CONTINUATION
PIPE CAP
GRADE CLEANOUT
RD
ORD
ROOF DRAIN PIPE
OVERFLOW RD PIPE
FLOOR CLEANOUT
WALL CLEANOUT
ROOF DRAIN
I.E. INVERT ELEVATION
MECHANICAL DRAWING INDEX
SHEET SHEET NAME
NUMBER
HVAC LEGEND:
ROUND DUCT (NEW SHADED/EXISTING UNSHADED)
RECT TAKE-OFF W/ DAMPER FROM ROUND MAIN
RECT TAKE-OFF W/ DAMPER FROM RECT MAIN
ROUND TAKE-OFF W/ DAMPER FROM ROUND MAIN
ROUND TAKE-OFF W/ DAMPER FROM RECT MAIN
DUCT WITH MOTORIZED DAMPER
DUCT WITH COUNTERBALANCED DAMPER
RETURN/EXHAUST GRILLE (DUCTED)
AIRFLOW PATTERNS
THERMOSTAT WITH ZONE TAG
FIRE DAMPER TAG
(E)R
(E)R
1
(E)EWH (E)EWH
2
T
RTU-1
(E)R
1 2 3 4 5
D
7
C
B
0
A
VVT-1 VVT-2
VVT-3
VVT-4
VVT-7
VVT-5 VVT-6
10"x8"
D-1- 8"ø
130
D-1- 8"ø
120
D-1- 8"ø
120
D-1- 8"ø
120
D-1- 10"ø
230
D-1- 10"ø
230
10"x10"
12"ø
D-1- 8"ø
50
D-1- 8"ø
190 D-2- 8"ø
200
12"x10"
8"x8"
SUITE 203
2031
Office
2032
Office
2033
Conf.
2017
Office
2016
Office
2015
Office
2014
Office
2013
SUITE 201
2011
V
EXISTING PACKAGED ROOFTOP UNIT SCHEDULE
NUMBER MAKE & MODEL NUMBER
(E)RTU CARRIER 48HCFD12 4,500 -
TONS
NOMINAL
ORIEN-
TATION
TOTAL
CFM
OA
CFM
FAN
RPM
EXT
STATIC
MOTOR
BHP
MBH IN
HEATING
MBH OUT
5000 FT AFUE
FUEL
TYPE
HEATING
STAGES
COOLING
STAGES
TOT MBH
COOLING
SENS
MBH
ENT DB
DEG. F
ENT WB
DEG. F
AMBIENT
DB
REF
TYPE
EER
(SEER)
FILTER
TYPE
TSTAT
TYPE
MIN CIR
AMPS
MAX
FUSE
ELEC
VOLTAGE
HEIGHT
W/CURB LENGTH WIDTH
WEIGHT
W/CURB REMARKS
10 HORIZ 430* ----- - -- ------- - --- - -- -
* REBALANCE OSA TO NEW VALUE INDICATED IN SCHEDULE. A UTILIZE EXISTING CARRIER CCN VVT CONTROLLER FOR VVT OPERATION
A
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
NUMBER MAKE & MODEL NUMBER
D-1 TITUS OMNI-3 SUPPLY
DESCRIPTION COLOR FRAME REMARKS
DUTY SIZE
NECK
SIZE
FRAME
TYPE
FRAME
CONST DAMPER
ARCHITECTURAL UNI-FLO
DIFFUSER
WHITE 24/24 LAY-IN STEEL YES
SEE
PLAN
APPROVED MANUFACTURERS: METALAIRE, KRUEGER
G-1 TITUS PAR-3
RETURN/
EXHAUST
PERFORATED FACE
REGISTER
WHITE 24/NO24 22/22 LAY-IN STEEL
G-2 TITUS PAR-3
PERFORATED FACE
REGISTER
WHITE 24/NO12 22/10 LAY-IN STEEL
RETURN/
EXHAUST
G-3 LOUVERED FACE
REGISTER
WHITE SURFACE STEEL NO
RETURN/
EXHAUST
TITUS 350RL-1
SEE
PLAN
SEE
PLAN
D-2 TITUS OMNI-3 SUPPLY
ARCHITECTURAL UNI-FLO
DIFFUSER
WHITE 24/24 SURFACE STEEL YES
SEE
PLAN
WITH TRIM FRAME
OUTSIDE AIR VENTILATION SCHEDULE
ROOM
2012 OFFICE
SYSTEM REMARKS
(BASED ON ASHRAE 62.1-2010)
AREA
[SF]
(Az)
OCC
DENSITY
[#/1000SF]
NUMBER
PEOPLE
(Pz)
PEOPLE OA RATE
[CFM/PERSON]
(Rp)
AREA OA RATE
[CFM/SF]
(Ra)
BREATHING ZONE
OA [CFM]
(Vbz=RpxPz+RaxAz)
DISTRIBUTION
EFFECTIVENESS
(Ez)
OA INTAKE
[CFM]
(Vot=Vbz/Ez)
OA
PROVIDED
[CFM]
2013 OFFICE
160 5 1 5 0.06 15 0.8 19
2011 SUITE 201 113 5 1 5 0.06 12 0.8 15
109 5 1 5 0.06 12 0.8 15
2014 OFFICE 117 5 1 5 0.06 12 0.8 15
2015 OFFICE 117 5 1 5 0.06 12 0.8 15
2016 OFFICE 117 5 1 5 0.06 12 0.8 15
2017 CONFERENCE 156 50 8 5 0.06 50 0.8 63
2021 SUITE 202 185 5 1 5 0.06 17 0.8 21
2022 CONFERENCE 169 50 9 5 0.06 56 0.8 70
2023 OFFICE 117 5 1 5 0.06 12 0.8 15
2024 OFFICE 117 5 1 5 0.06 12 0.8 15
2025 OFFICE 117 5 1 5 0.06 12 0.8 15
2026 OFFICE 117 5 1 5 0.06 12 0.8 15
2032 OFFICE 156 5 1 5 0.06 15 0.8 19
2031 SUITE 203 156 5 1 5 0.06 15 0.8 19
2033 OFFICE 150 5 1 5 0.06 15 0.8 19
207 HALL 802 - - - 0.06 49 0.8 62
427 430 (E)RTU
PINCHDOWN BOX W/ELECTRIC REHEAT SCHEDULE
NUMBER MAKE & MODEL NUMBER REMARKS
VVT-1 CARRIER 35E-10
1 RATED FOR 5000 FT ELEVATION
10" 1
INLET
SIZE
OUTLET
TYPE (WxH)
540
MAX
CFM
300
MIN
CFM
N/A
FAN
CFM
HEAT
CFM
0.5"
INLET
S.P.
N/A
FAN
HP
1.5
ELEC
KW
1
STEPS EAT
55
LAT
73.9
ELEC
DATA
120/1
ELECTRIC HEATING COIL
2 ISOLATION HANGER KIT 3 ELECTRIC HEATING COIL WITH FUSED DISCONNECT SWITCH 4 CARRIER CCN VVT CONTROLS
2 3 4
VVT-2 460 190 N/A 0.5" 1.0 1 74.9 120/1 1 2 3 4
VVT-3 590 300 N/A 0.5" 1.5 1 73.9 120/1 12"X10" 1 2 3 4
VVT-4 920 425 N/A 0.5" 2 2 72.8 120/1 14"X12" 1 3 4
VVT-5 480 190 N/A 0.5" 1.0 1 74.9 120/1 1 2 3 4
VVT-6 630 300 N/A 0.5" 1.5 2 73.9 120/1 12"X12" 1 3 4
VVT-7 880 425 N/A 0.5" 2 2 72.8 120/1 12"X12" 1 2 3 4
SINGLE
DUCT
CARRIER 35E-10 8" SINGLE
DUCT
CARRIER 35E-10 10" SINGLE
DUCT
CARRIER 35E-14 12" SINGLE
DUCT
CARRIER 35E-10 8" SINGLE
DUCT
CARRIER 35E-12 10" SINGLE
DUCT
CARRIER 35E-12 12" SINGLE
DUCT
165
140
100
280
145
190
270
N/A
N/A
N/A
N/A
N/A
N/A
55
55
55
55
55
55
12"X10"
12"X10"
10"X10"
2
2
NOTE: EXISTING VVT BY-PASS DAMPER LOCATED ON ROOF. BALANCE DAMPER AS FOLLOWS MAX CFM = 2,370, MINIMUM CFM = 0
SCALE:
SOUND BOOT
DETAIL NONE
24"x24" OR 24"x12"
RETURN AIR GRILLE
PAINT INTERIOR BLACK
WHERE VISIBLE
THRU GRILLE
1" RIGID FIBERGLASS
DUCTBOARD IN
RETURN AIR PLENUM
22"x10" OPEN
ENDED DUCT
22"x22" DUCT FOR
24"X24" GRILLE
OR 22"x10" DUCT FOR
24"x12" GRILLE
SCALE:
SINK
WASTE & VENT ISOMETRIC NONE
S-1
2"
W
CONNECT TO NEW 2" VENT
IN ADJACENT RESTROOM
TO (E) VENT OF GREATER
OR EQUAL SIZE
CONNECT TO NEW 2" WASTE
IN ADJACENT RESTROOM
TO (E) WASTE OF GREATER
OR EQUAL SIZE
2" WCO-1
SCALE:
PINCH-DOWN VAV BOX WITH
ELECTRIC REHEAT DETAIL NONE
ALLOW FOR REQUIRED
NEC CLEARANCE.
36" MINIMUM
BOX FLOW
METERING
STATION
ELECTRIC HEATING COIL
AND CONTROL ENCLOSURE
CONTROLLER
DAMPER
FLEXIBLE CONNECTION.
TYPICAL
PRIMARY AIR DUCT,
SIZE AS SHOWN ON
EQUIPMENT SCHEDULE
MIN. 3x DUCT DIA.
PRIOR TO TRANSITION
MVD UNLESS
NOTED
OTHERWISE
EXHAUST/RETURN SUPPLY
45°
SCALE:
DUCT TAKE-OFF DETAIL
RECTANGULAR NONE
SCALE:
DUCT TAKE-OFF DETAIL
ROUND NONE
RETURN
AIR
DIRECTION
45° LATERAL
TAKE-OFF
FITTING
WORM
DRIVE
SS CLAMP
FLEX DUCT
SUPPLY WHEN USED
AIR
DIRECTION
FITTING IS TO CONTAIN
MVD WITH HANDLE AND
LOCKNUT UNLESS
NOTED
OTHERWISE SCALE:
DUCT TRANSITION
DETAIL NONE
DIVERGING
AIRFLOW
CONVERGING
AIRFLOW
CONVERGING
AIRFLOW
DIVERGING
AIRFLOW
30° MAX
CONVERGING
AIRFLOW
15° MAX
DIVERGING
AIRFLOW
=
=
30° MAX
CONVERGING
AIRFLOW
15° MAX
DIVERGING
AIRFLOW
=
=
RECTANGULAR OR
ROUND DUCT
RECTANGULAR OR
ROUND DUCT
NOTE: 1) DETAIL APPLIES TO ALL DUCTWORK
ON DUCTWORK TRANSITIONING ON ALL
FOUR SIDES, NONE OF THE
TRANSITION ANGLES MAY EXCEED 15°
2)
223 Linden St., Suite 204
Fort Collins, CO 80524
Phone: 970-556-0570
Front-desk@int-mech.com
6/ 28/ 18
NJF
215 Mat hews Street | Fort Colli ns, Col orado 80524
CURRENT I SSUE:
DRAWN BY:
Architect
3115 Clyde St. | Fort Collins, CO 80524 | 90.484.8433
6/28/18
PERMIT I SSUE:
CONST. I SSUE:
M8. 1
MECHANICAL
SCHEDULES,
DETAILS, AND
ISOMETRIC
PLUMBING FIXTURE SCHEDULE:
SINK - ELKAY LRAD151755, GOURMET SINGLE COMPARTMENT SINK, 15"
X 17.5" O.D. X 5-1/2" DEEP BOWLS, 18 GAUGE, 304 STAINLESS
STEEL, COUNTERTOP, SELF RIMMING, 3 HOLE, 4" CENTERS, BACK
OUTLET DRAINS FOR ADA - KOHLER K-10430-CP FAUCET, ADA,
SINGLE HANDLE, 9" SWING SPOUT, POLISHED CHROME FINISH,
VEGETABLE SPRAY, 1-1/2" PVC P-TRAP, CHROME STOPS AND
SUPPLIES - ISE BADGER 5 DISPOSAL, 1/2 HP, 120/240 VOLT
S-1
WALL CLEANOUT - ZURN Z-1469 COVER PLATE, POLISHED 304
STAINLESS STEEL, PVC PIPE CLEANOUT - SEE PLAN FOR PIPE SIZE
WCO-1
REFRIGERATOR BOX - SIOUX CHIEF 696R10 FIRE RATED OX BOX,
5.5"x4"x3.5" BOX, TOP MOUNTED COLD WATER 1/4 TURN VALVE
RB-1
Page 10 of 13
Office
2012
COMMON
201
HALL
207
SUITE 202
2021
IT
206
KIT.
220
Conf.
2022
Office
2023
Office
2024
Office
2026
Office
2025
D-1- 8"ø
190
D-1- 8"ø
190
D-1- 10"ø
230
D-1- 10"ø
230
14"x12"
12"x10"
10"ø
D-1- 10"ø
240
D-1- 10"ø
240
D-1- 8"ø
180
D-1- 8"ø
180
D-1- 8"ø
180
D-1- 8"ø
200
12"x12"
8"ø
10"x10" 8"x8"
D-1- 8"ø
200 D-1- 10"ø
240
D-1- 10"ø
240
12"x12"
10"x10"
14"x14"
D-1- 8"ø
90
34"x14"
14"ø
8"x8"
12"x10"
28"x14"
30"x14"
30"x14"
12"ø G-1
G-2 G-2
G-2
G-2
G-2
G-2
G-2
G-2
G-2
G-2
G-2 G-2
G-2
G-2
S-1
2" W
T
VVT-7
T
VVT-6
T
VVT-5
T
VVT-4
T
VVT-1
T
VVT-2
T
VVT-3
CW
3
4
4
(E)MSB
6
6 6 6
6
6 6
6
6
6 6
6
6
6
6
D-2- 8"ø
80
12"ø
12"ø
5
5
12"ø
D-1- 8"ø
200
RB-1
8"ø
8"ø
10"ø
10"ø
8"ø
8"ø
G-2
8"ø
8"ø
10"ø
10"ø
8"ø
8"ø
8"ø
8"ø
10"ø
7 7 7
7
7
8 9
10
10"ø
8"ø
8"ø
10
12"ø
10
10
FLAG NOTES:
DEMO EXISTING OPEN ENDED 30"x20" SUPPLY AND RETURN AIR BACK
TO VERTICAL AT CHASE BACK TO VERTICAL AT CHASE. CONNECT NEW
DUCTWORK OF INDICATED SIZE TO BOTH SIDES OF EXISTING DUCT
INSIDE OF CEILING. EXTEND EXISTING DUCT AS NECESSARY TO MAKE
NEW CONNECTIONS.
REMOVE EXISTING TEMPORARY RTU T'STAT AND PROVIDE NEW CONTROLS
AS INDICATED ON PLANS.
CONNECT NEW PLUMBING TO EXISTING WITHIN WALL AT THIS LOCATION.
CONNECT 0.5" CW & HW, 2" WASTE AND 1.5" VENT TO EXISTING EQUAL
OR GREATER SIZES.
TERMINATE OPEN ENDED WITH WIRE MESH.
MC TO COORDINATE WITH GC TO CUT OUT A 30"x14" SECTION IN THE
WALL ABOVE THE CEILING IN LOCATION INDICATED. CUT OUT SHALL ACT
AS A TRANSFER OF AIR FROM PLENUM TO CENTRAL RETURN DUCT.
REFER TO SOUND BOOT DETAIL ON SHEET M7.1 FOR MORE INFORMATION
ON INSTALLATION DETAILS.
MC TO COORDINATE WITH GC TO CUT OUT A 18"x6" SECTION IN THE
WALL ABOVE THE CEILING IN LOCATION INDICATED. CUT OUT SHALL ACT
AS A TRANSFER AIR PATH.
SUPPLY AND RETURN MAINS CONTINUED UP TO (E)RTU-1 ON ROOF, NOT
SHOWN. REFER TO SCHEDULES FOR MORE INFORMATION.
EXISTING VVT BY-PASS DAMPER AND FUNCTION IS LOCATED AT THE
RTU EQUIPMENT ON ROOF AND IS NOT SHOWN. CONTRACTOR TO
CONNECT EXISTING DAMPER TO NEW VVT CONTROLS AS NECESSARY.
REFER TO SCHEDULES.
BRANCH DUCTWORK UP FROM TOP OF MAIN AND ROUTE OVER
STRUCTURAL BEAM AT GRIDLINE 'B' & 'C' AS INDICATED. TYPICAL.
1
2
3
4
5
6
7
8
9
10
FIXTURE ROUGH-IN SCHEDULE:
SINK:
REFRIGERATOR BOX:
COLD WATER HOT WATER
0.5"
0.5"
0.5"
-
223 Linden St., Suite 204
Fort Collins, CO 80524
Phone: 970-556-0570
Front-desk@int-mech.com
6/ 28/ 18
NJF
215 Mat hews Street | Fort Colli ns, Col orado 80524
CURRENT I SSUE:
DRAWN BY:
Architect
3115 Clyde St. | Fort Collins, CO 80524 | 90.484.8433
6/28/18
PERMIT I SSUE:
CONST. I SSUE:
SCALE:
MECHANICAL
SECOND FLOOR PLAN 3/16" = 1'-0"
M2. 1
MECHANICAL
SECOND FLOOR
PLAN
Page 9 of 13
FIRE/SMOKE DAMPER WITH DUCT DETECTOR
DUCT WITH VOLUME DAMPER
RETURN GRILLE (UNDUCTED)
DIFFUSER WITH FLEX DUCT
F
FS
RECT DUCT SIZE CHANGE
RECT DUCT CHANGE TO ROUND
RECT ELBOW UP (SUPPLY)
RECT ELBOW UP (NON-SUPPLY)
RECT ELBOW DOWN (SUPPLY)
RECT ELBOW DOWN (NON-SUPPLY)
ROUND ELBOW DOWN
ROUND ELBOW UP
ROUND ELBOW
RECT ELBOW W/ TURNING VANES
RECT DUCT (NEW SHADED/EXISTING UNSHADED)
SENSOR WITH ZONE TAG
SD SMOKE DAMPER WITH DUCT DETECTOR
C CARBON DIOXIDE SENSOR
O
2
T
RTU-X
S
RTU-X
223 Linden St., Suite 204
Fort Collins, CO 80524
Phone: 970-556-0570
Front-desk@int-mech.com
6/ 28/ 18
NJF
215 Mat hews Street | Fort Colli ns, Col orado 80524
CURRENT I SSUE:
DRAWN BY:
Architect
3115 Clyde St. | Fort Collins, CO 80524 | 90.484.8433
6/28/18
PERMIT I SSUE:
CONST. I SSUE:
MP0.1 MECHANICAL GENERAL NOTES, LEGENDS AND DRAWING INDEX
M2.1 MECHANICAL SECOND FLOOR PLAN
M8.1 MECHANICAL SCHEDULES, DETAILS, AND ISOMETRIC
GENERAL PLUMBING NOTES:
PLUMBING WORK SHALL COMPLY WITH ALL APPLICABLE CODES.
VERIFY ALL REQUIREMENTS PRIOR TO SUBMITTING BID OR
COMMENCING WORK. THE PLUMBING DESIGN IS BASED ON THE
2015 INTERNATIONAL PLUMBING CODE.
1.
WASTE AND VENT PIPING BELOW SLAB SHALL BE SCHEDULE 40, DWV,
PVC, PLASTIC. FITTINGS SHALL BE PVC.
2.
WASTE AND VENT PIPING ABOVE SLAB SHALL BE SCHEDULE 40, DWV,
PVC, PLASTIC. FITTINGS SHALL BE PVC.
3.
4.
5.
8.
POTABLE WATER PIPING BELOW GRADE SHALL BE TYPE K COPPER
WITHOUT JOINTS.
POTABLE WATER PIPING ABOVE GRADE SHALL BE TYPE L COPPER
WITH SOLDERED COPPER FITTINGS AND NO LEAD SOLDER UNLESS
NOTED OTHERWISE.
POTABLE WATER BRANCH PIPING 1" AND SMALLER MAY BE PEX
TUBING MANUFACTURED BY UPONOR/WIRSBO OR APPROVED EQUAL
AT CONTRACTOR'S OPTION.
POTABLE WATER VALVES SHALL BE FULL PORT, BALL TYPE.
HANGERS FOR 2" AND SMALLER PIPE SHALL BE BAND TYPE, 2.5"
AND LARGER SHALL BE CLEVIS TYPE. USE COPPER COATED TYPE ON
COPPER PIPE.
6.
7.
GENERAL HVAC NOTES:
MECHANICAL WORK SHALL COMPLY WITH ALL APPLICABLE CODES.
VERIFY ALL REQUIREMENTS PRIOR TO SUBMITTING BID OR
COMMENCING WORK. THE MECHANICAL DESIGN IS BASED ON THE
2015 INTERNATIONAL MECHANICAL CODE.
1.
2. ALL DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEET
METAL - CONSTRUCTION AND INSTALLATION SHALL CONFORM TO THE
CURRENT EDITION OF SMACNA OR AS REQUIRED BY ALL APPLICABLE
CODES.
CONSTRUCT ALL SUPPLY AND RETURN DUCTWORK TO SMACNA 2"
PRESSURE CLASS.
CONSTRUCT ALL EXHAUST DUCTWORK TO SMACNA 1" PRESSURE
CLASS.
DIMENSIONS OF DUCTWORK SHOWN INDICATES CLEAR INSIDE
DIMENSIONS - WHERE DUCT LINER IS TO BE ADDED, INCREASE THE
SIZE OF SHEET METAL ACCORDINGLY.
UNLESS NOTED OTHERWISE, THE SIZE OF THE BRANCH DUCT
SERVING A SINGLE DIFFUSER SHALL BE THE SAME AS THE NECK
SIZE OF THE DIFFUSER SERVED. FLEXIBLE DUCTWORK SHALL NOT
EXCEED 8'-0" IN LENGTH. FLEXIBLE DUCTWORK SHALL BE UL181
LISTED WITH 50/25 SMOKE/FLAME RATING, CONSISTING OF
POLYESTER FILM ENCAPSULATING AN INNER CORROSION RESISTANT
STEEL WIRE HELIX CORE. FLEXIBLE DUCT SHALL INCLUDE AN
EXTERIOR FIBERGLASS INSULATION WITH FOIL SCRIM FILM VAPOR
BARRIER JACKET, R-6.
MAINTAIN A MINIMUM 10'-0" SEPARATION FROM OUTSIDE AIR
INTAKES TO EXHAUST TERMINATIONS AND PLUMBING VENTS.
MAINTAIN A MINIMUM 3'-0" SEPARATION FROM EXHAUST
TERMINATIONS TO OPERABLE WINDOWS AND DOORS.
WALL MOUNTED THERMOSTATS AND SENSORS SHALL BE INSTALLED
48" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.
THERMOSTATS AND SENSORS LOCATED ON EXTERIOR WALL SURFACES
SHALL BE PROVIDED WITH AN INSULATED SUB-BASE.
TEMPORARY HEATING: THE PERMANENT HVAC SYSTEM MAY NOT BE
UTILIZED FOR HEATING UNTIL ALL GYPSUM WORK IS COMPLETED AND
HAS BEEN PAINTED. IF THE PERMANENT HVAC SYSTEM IS UTILIZED
DURING CONSTRUCTION, ALL DUCT INTAKES SHALL BE COVERED WITH
FILTER MEDIA (MERV-8 RATING). IF EXCESSIVE DUST OR DEBRIS
HAS ENTERED THE SYSTEM THEN ALL COIL AND DUCT SURFACES
SHALL BE CLEANED. NEW FILTERS ARE TO BE PROVIDED JUST
PRIOR TO TURNOVER TO OWNER. TEMPORARY HEATING OF THE
BUILDING PRIOR TO ANY USE OF THE PERMANENT HVAC SYSTEM
SHALL BE THE RESPONSIBILITY OF THE G.C.
3.
4.
5.
6.
7.
8.
9.
10.
WHERE CEILING SPACE IS TO BE USED AS A RETURN AIR PLENUM,
COMPLY WITH ALL APPLICABLE CODES. ALL MATERIALS WITHIN THE
CEILING PLENUM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE
THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50.
11.
ENERGY CODE/INSULATION NOTES:
THE MECHANICAL DESIGN IS BASED ON THE 2015 INTERNATIONAL
ENERGY CONSERVATION CODE.
1.
ALL SUPPLY, RETURN AND EXHAUST DUCTWORK SHALL BE SEALED
AIRTIGHT WITH DUCT SEALANT ALONG ALL SEAMS AND JOINTS.
2.
ALL RECTANGULAR SUPPLY DUCTWORK SHALL BE LINED WITH 1.5",
1.5 LB DENSITY DUCT LINER, MINIMUM R-5.
3.
ALL CONCEALED ROUND SUPPLY DUCTWORK SHALL BE WRAPPED WITH
1.5" THICK FIBERGLASS INSULATION WITH FOIL SCRIM VAPOR
BARRIER JACKET, MINIMUM R-5.
4.
ALL RECTANGULAR RETURN DUCTWORK SHALL BE LINED WITH 1.5",
1.5 LB DENSITY DUCT LINER, MINIMUM R-5.
5.
6. ALL SUPPLY AND RETURN DUCTWORK INSTALLED OUTDOORS SHALL
BE LINED WITH 2", 1.5 LB DENSITY DUCT LINER, MINIMUM R-8.
DUCTWORK SHALL BE SEALED WATER TIGHT.
HOT WATER PIPING SHALL BE INSULATED USING FIBERGLASS
INSULATION WITH ALL SERVICE JACKET HAVING MAXIMUM 'K' FACTOR
OF 0.27. INSULATION THICKNESS SHALL BE 1".
HOT WATER RECIRCULATION PIPING SHALL BE INSULATED
FIBERGLASS INSULATION WITH ALL SERVICE JACKET HAVING MAXIMUM
'K' FACTOR OF 0.27. INSULATION THICKNESS SHALL BE 1".
COLD WATER PIPING SHALL BE INSULATED USING FIBERGLASS
INSULATION WITH ALL SERVICE JACKET HAVING MAXIMUM 'K' FACTOR
OF 0.27. INSULATION THICKNESS SHALL BE 0.5".
7.
8.
9.
GENERAL MECHANICAL REQUIREMENTS:
CODES AND PERMITS
WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL CODES, REGULATIONS AND
ORDINANCES. PERMITS NECESSARY FOR PERFORMANCE OF WORK SHALL BE SECURED AND PAID FOR BY THE
CONTRACTOR.
DRAWINGS AND COORDINATION
DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC IN NATURE, AND ARE NOT INTENDED TO BE SCALED FOR
EXACT MEASUREMENTS NOR TO SERVE AS SHOP DRAWINGS. CHANGES FROM THE PLANS MADE WITHOUT
CONSENT OF THE ENGINEER SHALL RELIEVE THE ENGINEER OF RESPONSIBILITY FOR ALL CONSEQUENCES
ARRIVING OUT OF SUCH CHANGES. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS. WHERE CONDITIONS REQUIRE REASONABLE CHANGES TO THOSE INDICATED ON THE
DRAWINGS, MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. COORDINATE ALL WORK WITH
OTHER TRADES.
WARRANTY
WORKMANSHIP, MATERIALS, EQUIPMENT AND PROPER OPERATION SHALL BE GUARANTEED FOR A PERIOD OF ONE
YEAR FROM THE DATE OF FINAL ACCEPTANCE FROM THE OWNER. INITIAL ACCEPTANCE OF WORK SHALL NOT WAIVE
THIS GUARANTEE. THIS GUARANTEE SHALL NOT INCLUDE NORMAL MAINTENANCE REQUIRED BY THE OWNER AS
DESCRIBED IN EQUIPMENT OPERATION AND MAINTENANCE MANUALS.
SUBMITTALS
CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER A MINIMUM OF (5) COPIES OF SUBMITTAL
BROCHURES FOR REVIEW. PROVIDE INFORMATION ON ALL MAJOR EQUIPMENT AS LISTED ON DRAWING EQUIPMENT
SCHEDULES, AS WELL AS VALVES, DUCTWORK ACCESSORIES AND TEMPERATURE CONTROL DIAGRAMS AS
APPLICABLE.
OPERATION AND MAINTENANCE MANUALS
CONTRACTOR SHALL FURNISH AT THE COMPLETION OF THE PROJECT (2) COPIES OF COMPLETE OPERATION AND
MAINTENANCE MANUALS TO THE ARCHITECT/ENGINEER FOR REVIEW PRIOR TO TURNOVER TO OWNER. MANUALS TO
BE BOUND AND INCLUDE INSTALLATION INSTRUCTIONS, REPLACEMENT PARTS LISTS AND MAINTENANCE INFORMATION
ON ALL EQUIPMENT AS DESCRIBED IN THE SUBMITTALS SECTION. COMPLETED OPERATION AND MAINTENANCE
MANUALS ARE TO BE FORWARDED TO THE OWNER WITHIN 90 DAYS AFTER OWNER BUILDING ACCEPTANCE.
PRODUCT SUBSTITUTIONS
MANUFACTURER MODEL NUMBERS LISTED ON THE DRAWINGS AND/OR SPECIFICATIONS ARE TO BE CONSIDERED AS
THE BASIS OF DESIGN. WHERE TWO OR MORE ALTERNATE MANUFACTURERS OR MATERIALS ARE LISTED, THE CHOICE
OF THESE SHALL BE OPTIONAL WITH THE CONTRACTOR. PRIOR TO THE AWARDING OF THE CONTRACT, CONTRACTOR
MAY REQUEST A PROPOSED SUBSTITUTION OF MATERIALS IN WRITING TO THE ARCHITECT/ENGINEER NO LATER THAN
SEVEN DAYS PRIOR TO THE RECEIPT OF BIDS. THE COST OF ANY CHANGES REQUIRED BY OTHER TRADES,
INCLUDING A/E DESIGN, DUE TO THE USE OF EQUIPMENT AND/OR MATERIALS OTHER THAN THAT OF THE BASIS OF
DESIGN SHALL BE PAID BY THE CONTRACTOR.
RECORD DRAWINGS
CONTRACTORS SHALL MAINTAIN A COMPLETE AND ACCURATE SET OF MARKED UP DRAWINGS SHOWING ACTUAL
LOCATIONS OF INSTALLED WORK. THESE DRAWINGS ARE TO BE FORWARDED TO THE OWNER AS PART OF THE
OPERATION AND MAINTENANCE MANUALS AT THE COMPLETION OF THE PROJECT.
ACCESS DOORS
PROVIDE ALL ACCESS DOORS/PANELS AS REQUIRED FOR ACCESS TO VALVES, DAMPERS, CONTROL DEVICES,
FILTERS AND ANY OTHER ITEMS FOR WHICH ACCESS IS REQUIRED FOR EITHER OPERATION OR SERVICING.
WHERE ACCESS DOORS ARE TO BE INSTALLED IN ASSEMBLIES REQUIRED TO HAVE A SPECIFIC FIRE RATING,
ACCESS DOORS SHALL ALSO BE FIRE RATED.
PIPING AND DUCTWORK SEALANT THROUGH RATED ASSEMBLIES
PENETRATIONS SHALL BE SEALED AS REQUIRED IN ACCORDANCE WITH BUILDING AND MECHANICAL CODES TO RESIST
THE PASSAGE OF FLAME AND PRODUCTS OF COMBUSTION IN ORDER TO MAINTAIN THE RESISTANCE RATING OF THE
CONSTRUCTION BEING PENETRATED.
PROTECTION OF MATERIALS AND EQUIPMENT
CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALL WORK, MATERALS, AND EQUIPMENT PROVIDED UNDER
THIS SECTION. PIPE OPENINGS SHALL BE CLOSED WITH CAPS OR PLUGS TO PREVENT THE ENTRANCE OF DEBRIS
DURING CONSTRUCTION. ALL DUCTWORK OPENINGS SHALL BE SEALED CLOSED DURING CONSTRUCTION.
EQUIPMENT AND PIPING IDENTIFICATION
PROVIDE EQUIPMENT LABELS FOR ALL MAJOR EQUIPMENT, INCLUDING BUT NOT LIMITED TO AIR HANDLING SYSTEMS,
FANS, VAV BOXES, CONTROLS, DAMPERS, CONTROL VALVES AND PUMPS.
PROVIDE PIPE MARKERS ON CW, HW AND HWC SYSTEMS. LABELS TO BE AT MAXIMUM 8 FEET APART, WITH FLOW
DIRECTION INDICATED, AS APPLICABLE.
ADDITIONALLY, PROVIDE LABELING ON POTABLE WATER MANIFOLDS INDICATING PLUMBING FIXTURE SERVED BY THE
OUTLET, AS APPLICABLE.
LABELS SHALL BE AFFIXED OR ADHERED PERMANENTLY TO EQUIPMENT. EQUIPMENT INSTALLED INDOORS TO BE
LABELED WITH EMBOSSING TAPE.
EQUIPMENT INSTALLED OUTDOORS TO BE LABELED WITH ENGRAVED PLASTIC LAMINATE SIGNS.
PIPE MARKERS TO BE SELF-ADHESIVE, MANUFACTURED FOR SUCH PURPOSE.
STARTERS AND DISCONNECTS
EQUIPMENT STARTERS SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE
ELECTRICAL CONTRACTOR. EQUIPMENT DISCONNECTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR
UNLESS NOTED OTHERWISE ON THE DRAWINGS. STARTERS SHALL BE NEMA TYPE, AND SHALL INCLUDE PHASE
MONITORING FOR MOTORS 5 HP AND LARGER.
TESTING
TESTING SHALL BE PERFORMED ON THE FOLLOWING SYSTEMS SPECIFIED. ALL SYSTEMS LISTED MAY NOT BE
INCLUDED IN PROJECT, REFER TO DRAWINGS FOR APPLICABLE SYSTEMS.
SOIL, WASTE AND STORM DRAINAGE PIPING SHALL BE TESTED IN ACCORDANCE WITH APPLICABLE STATE AND LOCAL
CODES.
DOMESTIC WATER PIPING SHALL BE TESTED AND PROVEN WATERTIGHT UNDER A PRESSURE NOT LESS THAN THE
WORKING PRESSURE OF THE SYSTEM FOR A 24 HOUR PERIOD.
DOMESTIC WATER PIPING SYSTEM SHALL BE CHLORINATED AND STERILIZED IN ACCORDANCE WITH REQUIREMENTS OF
LOCAL JURISDICTION.
NATURAL GAS PIPING SHALL BE TESTED WITH AN AIR PRESSURE OF MINIMUM TWO TIMES THE DESIGN SYSTEM
PRESSURE, BUT NO LESS THAN 3 PSIG, FOR A PERIOD OF 24 HOURS WITHOUT PRESSURE DROP.
BALANCING
SYSTEM BALANCING SHALL BE PERFORMED BY A CERTIFIED BALANCING CONTRACTOR. BALANCE ALL SYSTEMS
INCLUDING AIRFLOW TO AND FROM ALL OPENINGS, AND PUMPED WATER SYSTEMS INCLUDING DOMESTIC WATER
RECIRCULATION SYSTEMS AS APPLICABLE. MAKE ANY ADJUSTMENTS NECESSARY TO RESULT IN CONDITIONS
INDICATED AND PROVIDE READJUSTMENTS TO ITEMS IN REPORT AS MAY BE REQUESTED BY ARCHITECT/ENGINEER.
SUBMIT TWO COPIES OF TEST AND BALANCE REPORT FOR APPROVAL. FAN AND PUMP SYSTEMS TO BE BALANCED
WITHIN PLUS OR MINUS 5 PERCENT OF LISTED VALUES. AIR INLETS AND OUTLETS TO BE BALANCED WITHIN PLUS
10 PERCENT OR MINUS 5 PERCENT OF LISTED VALUES. BALANCE REPORT TO INCLUDE:
UNIT IDENTIFICATION
MANUFACTURER AND NAMEPLATE DATA
EQUIPMENT NAMEPLATE AMPERAGE AND ACTUAL AMPERAGE
RPM (DESIGN AND ACTUAL)
FAN CFM (DESIGN AND ACTUAL)
FAN STATIC PRESSURE (DESIGN AND ACTUAL)
PUMP GPM (DESIGN AND ACTUAL)
PUMP DISCHARGE AND SUCTION PRESSURE
REGISTER, GRILLE, DIFFUSER REFERENCE NUMBER AND LOCATION
INLET/OUTLET CFM (DESIGN AND ACTUAL)
FLOW DEVICE PRESSURE DROP, CFM OR GPM
A FINAL BALANCING REPORT SHALL BE PROVIDED TO THE OWNER AFTER COMPLETION OF THE PROJECT.
CLEANING
AT THE COMPLETION OF WORK, ALL FIXTURES AND EQUIPMENT SHALL BE THOROUGHLY CLEANED AND DELIVERED IN
A CONDITION SATISFACTORY TO THE ARCHITECT. ALL FILTERS SHALL BE REPLACED WITH NEW PRIOR TO OWNER
ACCEPTANCE OF THE BUILDING.
CITY OF FORT COLLINS
GREEN CODE REQUIREMENTS:
BEFORE OCCUPANCY AND AFTER ALL INTERIOR FINISHES ARE
COMPLETE, THE BUILDING IS TO BE FLUSHED OUT (VENTILATED) FOR
A PERIOD OF 14 DAYS. WHERE CONTINUOUS VENTILATION IS NOT
POSSIBLE, THE AGGREGATE OF FLUSH-OUT PERIODS SHALL BE
EQUIVALENT TO 14 DAYS. CONTRACTOR SHALL PROVIDE FLUSH-OUT
REPORTS TO THE BUILDING OFFICIAL UPON COMPLETION OF WORK.
CONTRACTOR TO COORDINATE WITH BUILDING OFFICIAL FOR
INFORMATION TO BE CONTAINED IN FLUSH-OUT REPORTS.
1.
PROTECT HVAC EQUIPMENT FROM CONSTRUCTION DUST AND DEBRIS.
DO NOT OPERATE HVAC EQUIPMENT DURING CONSTRUCTION AND SEAL
ALL DUCT OPENINGS WITH PLASTIC.
2.
THE FOLLOWING LOW-VOLATILE ORGANIC COMPOUND (VOC) MATERIALS
SHALL BE USED AS APPLICABLE TO THIS SCOPE OF WORK.
-DUCT INSULATION ADHESIVE: DESIGN POLYMERICS 2501,
2502 OR APPROVED EQUAL.
-DUCT SEALANT: DESIGN POLYMERICS 1010, 1015
OR APPROVED EQUAL.
-FIRE CAULK: 3M FIRE BARRIER 1C 15WB+,
FD 150+, CP 25WB+ OR
APPROVED EQUAL.
3.
MP0. 1
MECHANICAL
GENERAL NOTES,
LEGENDS AND
DRAWING INDEX
Page 8 of 13
Deviation
% Final
Deviation
Outlet-01 2012 D-1 24x24 240 184 238 77 99
Outlet-02 2012 D-1 24x24 240 233 242 97 101
Outlet-03 2011 D-1 24x24 200 125 200 63 100
Outlet-04 2013 D-1 24x24 200 138 203 69 102
Totals: - - - 880 680 883 77 100
(E)RTU/VVT-07 Supply Outlet Summary
L.H. Finn and Associates
Final Report
Page 7 of 13
% Prelim
Deviation
% Final
Deviation
Outlet-01 2017 D-1 24x24 240 173 242 72 101
Outlet-02 2017 D-1 24x24 240 188 242 78 101
Totals: - - - 480 361 484 75 101
(E)RTU/VVT-05 Supply Outlet Summary
L.H. Finn and Associates
Final Report
Page 6 of 13
Deviation
Outlet-01 220 D-2 24x24 200 155 202 78 101
Outlet-02 2021 D-1 24x24 190 138 190 73 100
Outlet-03 2021 D-1 24x24 200 163 203 82 102
Totals: - - - 590 456 595 77 101
(E)RTU/VVT-03 Supply Outlet Summary
L.H. Finn and Associates
Final Report
Page 5 of 13
Final Report
Page 4 of 13