CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
5/8/18
PROJECT
Butters Restaurant
1103 West Elizabeth
Fort Collins, CO
***Final Report***
ARCHITECT
None Shown
ENGINEER
Integrated Mechanical
223 Linden Street
Fort Collins, CO
CONTRACTOR
Air Comfort
150 Rome
Fort Collins, CO
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
PROJECT: Butters Restaurant
ADDRESS: 1103 West Elizabeth
Fort Collins, CO
The data presented in this report is an exact record of the system performance
and was obtained in accordance with NEBB Standard Procedures. Any
variances from design quantities which exceed NEBB tolerances are noted
throughout the report.
The air distribution systems have been tested & balanced and final adjustments
have been made in accordance with NEBB “Procedural Standards for Testing,
Adjusting & Balancing of Environmental Systems” and the project specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:5/8/18
The hydronic distribution systems have been tested & balanced and final
adjustments have been made in accordance with NEBB “Procedural Standards
for Testing, Adjusting & Balancing of Environmental Systems” and the project
specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:5/8/18
SUBMITTED & CERTIFIED BY
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
TAB SUPERVISOR: David C. Reichel
REG. NO.: 2389 SIGNATURE:
DATE: 5/8/18 CERTIFICATION EXPIRATION DATE: 3/31/2020
Table Of Contents
PROJECT:
LOCATION:
Butters Restaurant
, CO
DATE:
CONTACT:
AUTHOR:
5/8/2018
Joe Marshall
Joe Marshall
Table Of Contents
1 Instrument Calibration Report.pdf............................................................................................................................ 1
2 Abbreviation Report.pdf............................................................................................................................................ 3
3 Roof Top Unit........................................................................................................................................................... 4
3.1 RTU-01............................................................................................................................................................... 4
4 Make-Up Air Unit...................................................................................................................................................... 5
4.1 MUA-01.............................................................................................................................................................. 5
5 Energy Recovery Unit.............................................................................................................................................. 6
5.1 ERU-01............................................................................................................................................................... 6
5.2 ERU-01/Exhaust................................................................................................................................................. 7
5.3 ERU-01/Supply................................................................................................................................................... 7
6 Fan Unit.................................................................................................................................................................... 8
6.1 (E) EF-02............................................................................................................................................................ 8
6.2 (E) EF-03............................................................................................................................................................ 8
6.3 KEF-01............................................................................................................................................................... 8
7 Prints.pdf.................................................................................................................................................................. 9
7.1 H2 1 HVAC Plan ................................................................................................................................................ 9
7.2 H7 1 HVAC Details ............................................................................................................................................
7.3 H8 1 HVAC Schedules ......................................................................................................................................
7.4 M0 1 Mechanical General Nores Legends and Drawings ................................................................................
7.5 REFERENCE - NOT IN PROJECT M1 1 Mechanical Demo Plan ...................................................................
7.6 REFERENCE - NOT IN PROJECT M2 1 Mechanical Plan ..............................................................................
7.7 REFERENCE - NOT IN PROJECT M8 1 Mechanical Schedule and Details ...................................................
7.8 REFERENCE - NOT IN PROJECT MP0 1 Mechanical General Notes Legends and Drawing Index .............
7.9 H2 1 HVAC Plan ................................................................................................................................................
7.10 H7 1 HVAC Details ..........................................................................................................................................
7.11 H8 1 HVAC Schedules .....................................................................................................................................
7.12 M0 1 Mechanical General Nores Legends and Drawings ..............................................................................
7.13 REFERENCE - NOT IN PROJECT M1 1 Mechanical Demo Plan .................................................................
7.14 REFERENCE - NOT IN PROJECT M2 1 Mechanical Plan ............................................................................
7.15 REFERENCE - NOT IN PROJECT M8 1 Mechanical Schedule and Details .................................................
7.16 REFERENCE - NOT IN PROJECT MP0 1 Mechanical General Notes Legends and Drawing Index ...........
L.H. Finn and Associates
Final Report
Manufacturer Model Serial Application Cal. Date
Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014
Alnor HM-680 70750150 Hydronic Press. & Diff. Press. 12/14/2015
Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/30/2015
Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 4/5/2016
Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 6/10/2015
Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 7/7/2017
Cooper SH66A 92711016 Temperature Measurement 10/9/2017
Extech 461895 Q394479 Rotation Measurement 4/17/2017
Extech 461895 Q083481 Rotation Measurement 1/9/2014
Extech 461895 Q247569 Rotation Measurement 3/8/2016
Extech 461895 L268576 Rotation Measurement 3/8/2016
Extech 461895 Q331990 Rotation Measurement 11/4/2014
Extech 461895 Q477125 Rotation Measurement 9/25/2015
Extech 461895 Q477126 Rotation Measurement 4/5/2016
Extech 461895 Q527632 Rotation Measurement 10/3/2017
Extech 461895 Q590099 Rotation Measurement 4/17/2017
Extech RH390 9099221 Temperature / Humidity 4/9/2015
Fluke 335 96960004 Electrical Measurement 11/5/2015
Fluke 336 97110539R Electrical Measurement 4/5/2016
Fluke 336 97110538R Electrical Measurement 9/29/2015
Fluke 335 92008180 Electrical Measurement 11/4/2014
Fluke 335 12990071 Electrical Measurement 3/4/2016
Fluke 374 15460133 Electrical Measurement 4/18/2014
Fluke 374 20030351 Electrical Measurement 10/3/2017
Fluke 374 20030354 Electrical Measurement 4/17/2017
TSI 8322 55100720 Air Velocity Measurement 10/4/2017
Shortridge ADM-860C M05789 Digital Manometer 11/25/2015
Shortridge ADM-860C M06821 Digital Manometer 4/18/2017
Shortridge ADM-860C M07352 Digital Manometer 6/6/2016
Shortridge ADM-860C M09123 Digital Manometer 4/18/2016
Shortridge ADM-860C M09347 Digital Manometer 9/26/2015
Shortridge ADM-860C M10144 Digital Manometer 4/14/2017
Shortridge ADM-860C M10371 Digital Manometer 11/5/2015
Shortridge ADM-860C M11448 Digital Manometer 4/14/2017
Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015
Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 4/18/2017
Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015
REMARKS: Not all equipment shown was used on this project.
Project: Butters Restaurant
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
INSTRUMENT CALIBRATION REPORT
Page 1 of 9
Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017
Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 10/3/2017
Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017
Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 4/19/2018
Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 4/19/2018
Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 9/29/2016
Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 2/26/2018
Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 2/26/2018
Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 10/2/2016
Evergreen Telemetry S-PVF-1 1600322 Pressure Velocity Module 10/3/2016
Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700214 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700216 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/12/2017
Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/12/2017
Evergreen Telemetry RM-T-1 1700269 Radio Module 5/17/2017
Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016
Evergreen Telemetry RM-T-1 1600235 Radio Module 10/12/2016
Evergreen Telemetry RM-T-1 1600233 Radio Module 10/14/2016
Evergreen Telemetry RM-T-1 1600234 Radio Module 10/16/2016
Evergreen Telemetry RM-T-1 1700260 Radio Module 4/21/2017
Evergreen Telemetry RM-T-1 1700261 Radio Module 4/21/2017
Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 5/17/2017
Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/11/2016
Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/13/2016
Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/15/2016
Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/17/2016
Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017
Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017
Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017
Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017
Evergreen Telemetry S-DP-125 1700112 Water Press. Sensing Module 3/2/2017
REMARKS: Not all equipment shown was used on this project.
Project: Butters Restaurant
INSTRUMENT CALIBRATION REPORT (Continue)
Page 2 of 9
Project: Butters Restaurant
Symbol Description Symbol Description
A Airflow (L/S) NS Not Shown
AF Air Foil NT No Information Tag
ANA Access Not Available OD Outside Diameter
BI Backward Incline RPM Revolution Per Minute
CD Ceiling Diffuser SD Supply Diffuser
CFM Airflow (Cubic Feet / Minute) SNKL Snorkel
DD Direct Drive SP Static Pressure
Des Design SPD Static Pressure Drop
DWDI Double Width Double Inlet SR Supply Register
EF Exhaust Fan SWSI Single Width Single Inlet
EG Exhaust Grille T Temperature ( C )
ER Exhaust Register T Temperature ( F )
ESP External Static Pressure TSP Total Static Pressure
FC Forward Curve VFD Variable Frequency Drive
GPM Waterflow (Gallons / Minute) VS Variable Speed
HC Heat Coil W Waterflow (L/S)
HER Heat Exchanger
HRC Heat Recovery
Hz Hertz
ID Inside Diameter
In. WC Inches of Water Column
NA Not Applicable
NI Not Installed
NIC Not In Contract
NM Not Measurable
NPT No Pressure Tap
NR Not Readable
REMARKS:
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
ABBREVIATION REPORT
Page 3 of 9
Roof Top Unit
PROJECT:
LOCATION:
Butters Restaurant
, CO
DATE:
CONTACT:
AUTHOR:
5/8/2018
Joe Marshall
Joe Marshall
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: RTU-01
Unit Data
Unit Manufacturer Lennox
Unit Model Number GCS16-048-120-5Y
Unit Serial Number 5603D 03426
Unit Discharge Horizontal
RTU-01/Supply Fan
Fan Type Forward Curve
Fan Size 10" ID
Fan Class 1
Fan Arrangement DWDI
Fan Discharge Horizontal
RTU-01/Filter Bank
Filter Manufacturer Purolator
Filter Type Pleated
Filter Quantity 1
Filter Size 20x25x1
Starter Data
RTU-01/Supply Fan
Installed Thermal Internal
Test Data
Total CFM Design 1800 CFM
Total CFM Actual 1672 CFM
Outside Air CFM Design 965 CFM
Outside Air CFM Actual 942 CFM
Return Air CFM Design 835 CFM
Return Air CFM Actual 730 CFM
RTU-01/Supply Fan
Fan RPM Actual Direct Drive RPM
Motor Volts 1 204 Volts
Motor Volts 2 205 Volts
Motor Volts 3 206 Volts
Motor Amps 1 4.7 Amps
Motor Amps 2 4.5 Amps
Motor Amps 3 4.5 Amps
Motor Data
RTU-01/Supply Fan
Motor Rated Volts 208-230 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 4.6 Amps
Sheave Data
RTU-01/Supply Fan
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Make-Up Air Unit
PROJECT:
LOCATION:
Butters Restaurant
, CO
DATE:
CONTACT:
AUTHOR:
5/8/2018
Joe Marshall
Joe Marshall
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: MUA-01
Unit Data
Unit Manufacturer FLO AIRE
Unit Model Number F2-D.250-G15
Unit Serial Number 1983522
Unit Discharge Vertical Down
MUA-01/Suppy Fan
Fan Type Forward Curve
Fan Size 12" ID
Fan Class 1
Fan Arrangement DWDI
Fan Discharge Vertical/Down
MUA-01/Filter
Filter Type Washable
Filter Quantity 3
Filter Size 20x25x2
Starter Data
MUA-01/Suppy Fan
Installed Thermal Adjustable
Rating (Amps) 11.3-16 Amps
Thermals Set at: 12.5
Test Data
Total CFM Design 2300 CFM
Total CFM Actual 2368 CFM
Outside Air CFM Design 2300 CFM
Outside Air CFM Actual 2368 CFM
Return Air CFM Design 0 CFM
Return Air CFM Actual 0 CFM
MUA-01/Suppy Fan
Fan RPM Actual 1004 RPM
Motor Volts 1 207 Volts
Motor Amps 1 9.9 Amps
Motor Data
MUA-01/Suppy Fan
Motor Manufacturer WEG
Motor Frame E56
Motor HP 2 HP
Motor RPM 1730 RPM
Motor Rated Volts 115/208-230 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 25.4/14.0-12.7 Amps
Motor Service Factor 1.15
Sheave Data
MUA-01/Suppy Fan
Motor Sheave Make Power Drive
Motor Sheave Model 1VL40
Energy Recovery Unit
PROJECT:
LOCATION:
Butters Restaurant
, CO
DATE:
CONTACT:
AUTHOR:
5/8/2018
Joe Marshall
Joe Marshall
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: ERU-01
Log: ERU-01 5/9/2018 Joe Marshall Exhaust air reduced to obtain proper building
pressure
Unit Data
Unit Manufacturer Renew Aire
Unit Model Number HE1XIN
Unit Serial Number C18 8662C
ERU-01/Exhaust Fan
Fan Type Forward Curve
Fan Size 8" ID
Fan Class 1
Fan Arrangement DWDI
Fan Discharge Horizontal
ERU-01/Supply Fan
Fan Type Forward Curve
Fan Size 8" ID
Fan Class 1
Fan Arrangement DWDI
Fan Discharge Horizontal
ERU-01/EF Filter
Filter Manufacturer Glasfloss
Filter Type Pleated
Filter Quantity 1
Filter Size 20x20x2
ERU-01/SF Filter
Filter Manufacturer Glasfloss
Filter Type Pleated
Filter Quantity 1
Filter Size 20x20x2
Starter Data
ERU-01/Exhaust Fan
Installed Thermal Internal
ERU-01/Supply Fan
Installed Thermal Internal
Test Data
SF Total CFM Design 965 CFM
SF Total CFM Actual 947 CFM
SF OA CFM Design 965 CFM
SF OA CFM Actual 947 CFM
EF Total CFM Design 865 CFM
EF Total CFM Actual 502 CFM
ERU-01/Exhaust Fan
Motor Volts 1 211 Volts
Motor Amps 1 1.6 Amps
ERU-01/Supply Fan
Motor Volts 1 211 Volts
Motor Amps 1 1.5 Amps
Energy Recovery Unit
PROJECT:
LOCATION:
Butters Restaurant
, CO
DATE:
CONTACT:
AUTHOR:
5/8/2018
Joe Marshall
Joe Marshall
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: ERU-01/Exhaust
Test Pressures
Pre Filter SP In -0.35 in. w.c.
Pre Filter SP Out -0.42 in. w.c.
Return Fan SP In -1.26 in. w.c.
Return Fan SP Out 0.21 in. w.c.
Heat Exchanger SP In -0.42 in. w.c.
Heat Exchanger SP Out -1.26 in. w.c.
Static Pressure Profile
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: ERU-01/Supply
Test Pressures
Pre Filter SP In -0.21 in. w.c.
Pre Filter SP Out -0.36 in. w.c.
Supply Fan SP In -1.14 in. w.c.
Supply Fan SP Out 0.09 in. w.c.
Heat Exchanger SP In -0.36 in. w.c.
Heat Exchanger SP Out -1.14 in. w.c.
Static Pressure Profile
L.H. Finn and Associates
Final Report Page 7 of 9
Fan Unit
PROJECT:
LOCATION:
Butters Restaurant
, CO
DATE:
CONTACT:
AUTHOR:
5/8/2018
Joe Marshall
Joe Marshall
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: (E) EF-02
Log: (E) EF-02 5/8/2018 Joe Marshall Fan is not in scope of work. Airflow shown for
building pressure only
Test Data
Total CFM Design NS CFM
Total CFM Actual 136 CFM
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: (E) EF-03
Log: (E) EF-03 5/8/2018 Joe Marshall Fan is not in scope of work. Airflow shown for
building pressure only
Test Data
Total CFM Design NS CFM
Total CFM Actual 152 CFM
Tested By: Joe Marshall
Date: 5/8/2018
SYSTEM/UNIT: KEF-01
Unit Data
Fan Manufacturer NAKS
Fan Model Number 36B
Fan Serial Number 20180112
Fan Type Backward Incline
Fan Class 1
Fan Arrangement SWSI
Fan Discharge Upblast
Starter Data
Installed Thermal Internal
Test Data
Total CFM Design 2500 CFM
Total CFM Actual 2512 CFM
Fan RPM Actual 1504 RPM
Motor Volts 1 212 Volts
Motor Amps 1 2.8 Amps
SP In Actual ANA in. wc
SP Out Actual 0.0 in. wc
Total SP Actual NM in. wc
Motor Data
Motor Manufacturer Century
Motor Frame K56
Motor HP 1 HP
Motor RPM 1725 RPM
Motor Rated Volts 115/208-230 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 12.6/6.3-6.2 Amps
Motor Service Factor 1.25
Sheave Data
FLAG NOTES:
REBALANCE EXISTING RTU TO 1800 CFM. MC TO PROVIDE AND INSTALL
NEW 7-DAY PROGRAMMABLE T'STAT. EXISTING RTU: LENNOX GCS16-
048-120-5Y, HORIZONTAL DISCHARGE. EXISTING DUCTWORK SHALL BE
REMOVED AND REPLACED WITH NEW IN ACCORDANCE TO HVAC SPECS.
SEE SHEET H0.1, TYPICAL.
1
EXTERIOR DUCTWORK SHALL BE FABRICATED AND INSULATED IN
ACCORDANCE TO HVAC SPECS. SEE SHEET H0.1, TYPICAL.
2
RUN 16"Ø EXHAUST DUCT THROUGH ROOF TO GOOSENECK WITH
0.5"x0.5" GALVANIZED WIRE MESH.
3
ERV IS MULTI-POSE STYLE. UNIT SHALL BE INSTALLED ABOVE CEILING.
LAY UNIT HORIZONTALLY WITH FACE (ACCESS DOORS) INSTALLED
THROUGH CEILING GRID. DOORS SHALL BE 1" BELOW CEILING. UNIT MAY
BE PAINTED IF DESIRED.
4
RUN 16"Ø OA INTAKE DUCT THROUGH ROOF TO GOOSENECK WITH
0.5"x0.5" GALVANIZED WIRE MESH. INTAKE SHALL BE A MINIMUM 10'-0"
FROM ANY EXHAUST, VENT OR FLUE.
5
RELOCATE EXISTING EQUIPMENT FROM ORIGINAL RESTAURANT. PROVIDE
AND INSTALL NEW PITCHED CURB FOR LEVEL INSTALLATION.
6
8 NEW GREASE HOOD. SEE SHEET H8.2.
DO NOT REUSE EXISTING MAKE-UP AIR CONTROL. PROVIDE, INSTALL,
WIRE AND CONTROL THE MAU WITH NEW SYSTEM. EQUIPMENT SHALL
MONITOR DISCHARGE AIR TEMPERATURE AND SHALL ALSO FEATURE
ROOM TEMPERATURE OVERRIDE. THE SYSTEM SHALL CONTROL THE FAN
OPERATION, DIRECT FIRED BURNER AND EVAPORATIVE COOLER
OPERATION AS WELL AS EVAP COOLER FILL AND DRAIN.
9
RELOCATED MAKE-UP AIR UNIT. FLOAIRE F2-D.250-G15, 208/1Ø VOLTS,
2 HP, DIRECT FIRED, WITH EVAP SECTION. BALANCE AS SHOWN ON
PLAN.
10
11 - - NOT USED ---
RUN 6"Ø EXHAUST DUCT FROM FAN THROUGH ROOF TO ROOF CAP.
DISCHARGE SHALL BE MIN 10' FROM ANY OA INTAKE.
12
WATER HEATER FLUE AND CA TO BE RUN BY PC. SEE PLUMBING PLANS
FOR FURTHER INFORMATION.
13
NEW KITCHEN HOOD EXHAUST FAN KEF-1, SEE SHEET H8.2. RUN
14"x14" GREASE DUCT UP FROM HOOD THROUGH ROOF TO KITCHEN
EXHAUST FAN.
7
GREASE DUCTWORK (RECTANGULAR): DUCTWORK SHALL BE
CONSTRUCTED OF STEEL OF NOT LESS THAN 16 GAUGE. JOINTS,
SEAMS AND PENETRATIONS SHALL BE MADE WITH A CONTINUOUS
LIQUID-TIGHT WELD OR BRAZE MADE ON THE EXTERNAL SURFACE OF
THE DUCT SYSTEM. JOINTS, DUCT SLOPING AND CLEANOUTS SHALL
BE IN ACCORDANCE WITH THE MECHANICAL CODE. PRIOR TO
CONCEALMENT OF DUCT, A LEAKAGE TEST SHALL BE PERFORMED IN
THE PRESENCE OF A CODE OFFICIAL.
RECTANGULAR GREASE DUCTWORK INSULATION: PROVIDE TWO
LAYERS OF BLANKET WRAP INSULATION WITH A MINIMUM NOMINAL
THICKNESS OF 1.5" EACH, COMPOSED OF MINERAL WOOL FIBERS AND
FIBERGLASS WITH A DENSITY OF 1.4 POUNDS PER SQUARE FOOT.
BLANKET WRAP SHALL BE FULLY ENCAPSULATED WITH A
POLYPROPYLENE/FOIL SCRIM. SYSTEM AND INSTALLATION SHALL
COMPLY WITH REQUIREMENTS OF ASTM E 2336, LOCAL BUILDING
CODES AND AUTHORITY HAVING JURISDICTION. 3M FIRE BARRIER
DUCT WRAP 15A OR APPROVED.
15
14
1
2
20"x16"
16"x22"
12"x24"
ERV-1
3
4
5
G-1
16"Ø
R-1
885
22"x16"
16"x12"
D-1
10"Ø
310
D-1
10"Ø
310
D-1
10"Ø
305
D-1
10"Ø
305
D-1
10"Ø
260
D-1
10"Ø
260
16"x14"
10"ø
10"ø 10"ø
10"ø
10"ø
10"ø
6"ø
7
6
8
T
MAU
9
9
6 10
12
15
EF-1
22"x10"
22"x10"
D-7
934
D-7
933
D-7
933
13
14
KEF-1
22"x18"
223 Linden St., Suite 204
Fort Collins, CO 80524
Phone: 970-556-0570
Front-desk@int-mech.com
DRAWN
BY:
CHECKED
BY:
JOB
NUMBER:
DATE:
FILE
NAME:R-12-025-M001
H2.1
HVAC PLAN
Author
12/23/13
Checker
BUTTERS RESTAURANT
FORT COLLINS, CO
14-000
0'
HVAC
PLAN 4' 8'
1 FEB 2018
Page 9 of 9
Motor Sheave Make Power Drive
Motor Sheave Model Adjustable
Motor Sheave Diam. 3 1/4 in.
Motor Operating Diameter 3 in.
Motor Sheave Bore 5/8 in.
Fan Sheave Make Power Drive
Fan Sheave Diam. 3 3/4 in.
Fan Sheave Bore 5/8 in.
Number of Belts 1
Belt Size 4L240 in.
Sheave Center Line 7 in.
L.H. Finn and Associates
Final Report Page 8 of 9
Motor Data
ERU-01/Exhaust Fan
Motor HP 3/4 HP
Motor RPM 1625 RPM
Motor Rated Volts 115/208-230 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 9.0/4.5-4.5 Amps
Motor Service Factor 1.0
ERU-01/Supply Fan
Motor HP 3/4 HP
Motor RPM 1625 RPM
Motor Rated Volts 115/208-230 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 9.0/4.5-4.5 Amps
Motor Service Factor 1.0
Sheave Data
ERU-01/Exhaust Fan
Motor Sheave Make Direct Drive
ERU-01/Supply Fan
Motor Sheave Make Direct Drive
L.H. Finn and Associates
Final Report Page 6 of 9
Motor Sheave Diam. 3 3/4 in.
Motor Sheave Bore 7/8 in.
Motor Operating Diameter 3 3/4 in.
Fan Sheave Make Power Drive
Fan Sheave Model AK66
Fan Sheave Diam. 6 1/2 in.
Fan Sheave Bore 1 in.
Number of Belts 1
Belt Size AX50
Sheave Center Line 18 in.
Test Pressures
Fan Static Pressure In Actual -0.82
Fan Static Pressure Out Actual ANA
External Static Pressure In
Actual
0.0
External Static Pressure Out
Actual
ANA
Filter/Coil Static Pressure In -0.0
Filter/Coil Static Pressure Out -0.82
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 Kitchen D-7 24x24 934 584 812 63 87
Outlet-02 Kitchen D-7 24x24 933 498 814 53 87
Outlet-03 Kitchen D-7 24x24 933 1632 823 175 88
Totals: - - - 2800 2714 2449 97 87
MUA-01 Supply Outlet Summary
L.H. Finn and Associates
Final Report Page 5 of 9
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 Dining SR 14x6 310 226 281 73 91
Outlet-02 Dining SR 14x6 310 238 284 77 92
Outlet-03 Dining SR 14x6 305 243 286 80 94
Outlet-04 Dining SR 14x6 305 237 284 78 93
Outlet-05 Dining SR 14x6 260 313 246 120 95
Outlet-06 Dining SR 14x6 260 321 244 123 94
Outlet-07 Office CD 12x12 50 184 47 368 94
Totals: - - - 1800 1762 1672 98 93
RTU-01 Supply Outlet Summary
L.H. Finn and Associates
Final Report Page 4 of 9