HomeMy WebLinkAbout5132 Stillwater Creek St - Violations/Building Code - 07/02/2020F®rt Collins City o f Planning, Development, and Transportation
Community Development &50 Neighborhood Services
281 N. College Ave. - PO Boxx58
Fort Collins, CO 80522
970.416.2740
970.224.6134 - fax
kgov.com/nbs
Building Code Correction
Date: 7/2/2020
Property Owner: SADDLEBROOK TOWNHOMES HOA
C/O FAITH PROPERTY MANAGEMENT
Address: 300 BOARDWALK DR. B6
FORT COLLINS, COLORADO 80525
Reference Address: SADDLEBROOK TOWNHOMES, FORT COLLINS, CO.
(MULTIPLE ADDRESSES)
This letter is to inform you that the above referenced properties are in violation of the following
sections of the International Codes as adopted by the City of Fort Collins:
The 2018 International Residential Code Sections R105.1, and amendments adopted by the City
of Fort Collins regarding the installation of electrical lighting at the above referenced properties
without permits in place prior to construction. The 2017 National Electrical Code regarding the
definition of Service Equipment, Article 230 Part VI regarding Service Disconnecting Means,
and section 230.82 regarding Equipment Connected To The Supply Side Of Service Disconnect
all regarding the use of a meter and its disconnect location as a house panel instead of installing a
sub panel for a house panel on each building. Permits must now be obtained by the date listed
below in order to avoid fees being accessed. Also consider this Code'Correction a Stop Work
Order.
The following list of addresses are buildings that will require permits for the installation of
House Panels and the refeed of already installed electrical lighting are:
5124 Stillwater Creek Dr
5133 Stillwater Creek Dr
5121 Stillwater Creek Dr
5108 Stetson Creek Ct.
5125 Stetson Creek Ct.
5126 Stetson Creek Ct.
5132 Stetson Creek Ct.
2130 Copper Creek Dr.
2142 Copper Creek Dr.
2218 Copper Creek Dr.
2120 Copper Creek Dr.
2138 Copper Creek Dr.
2202 Copper Creek Dr.
2220 Copper Creek Dr.
2133 Copper Creek Dr.
Page 2
Should there be any other buildings in the complex that have additional lighting installed and the
lighting is being powered from the Service Equipment Disconnecting Means on that building
they should be included in the permit process for house panel and lighting installation.
These Code violations shall be corrected by: 8/2/2020
If you can not comply within the time limit specified, please contact this office and explain any
mitigating circumstances.
Samuel W. Hancock
City of Fort Collins
Lead Building Inspector
1-970-416-2348
shancock@fcgov.com