Loading...
HomeMy WebLinkAbout2261 E Drake Rd - Special Inspections/Field Verification - 02/17/2017�bi(oo454 ELITE E BALANCING 2029 Kinnikinnick Dr. • Erie, CO 80516 •Phone: (720) 523-0209 • Fax: (720) 523-0225 • http://www.elitebalancing.com Certified Test, Adjust, and Balance Report Blue Federal Credit Union Address: Date: Job Number: Mechanical Engineer: Mechanical Contractor: Submitted & Certified By: Elite Balancing LLC Certification Number: 3502 2261 E Drake e U Fort Collins, CO 2/17/2017 2017-667 Boulder Engineering Air Comfort Certification Exp Date: March 31, 2018 NEBB Qualified Certified Professional: Kevin Shaw 0 ;0� 46, N 3502 00.331ns 28FEB 17 1:53PM The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMEMTAL SYSTEMS. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test -Adjust -Balance Report Project Summary. Revision Number Date Description 1 2/17/17 Final Report Issued Elite Balancing, LLC 1 /10 ELITE NE BiB BALANCING 4i B Roof Top Unit PROJECT: Blue Federal Credit Union LOCATION: Fort Collins, CO PROJECT #: 2017-667 SYSTEWUNIT: RTU-01 Unit Data Unit Manufacturer Carrier Unit Model Number 48HCFD08B2M5AOBOAO Unit Serial Number 3916P72675 Design Min OSA 226 CFM Total Connected Airflow 3000 CFM Starter Data RTU-01/Supply Fan Starter Manufacturer Factory Installed Actual Supply Airflow Actual Outside Airflow Actual Return Airflow RTU-01/Supply Fan Actual RPM Volts Test Data 230 CFM 2765 CFM 880 RPM 212/212/211 Volts 4.3/4.7/4.2 Amps RTU-01 Supply Outlet Summary DATE: 2/17/2017 CONTACT: Kevin Shaw Tested By: Josh Drake Date: 2/14/2017 Motor Data RTU-01/Supply Fan Motor Manufacturer Marathon Motor HP 4.2 HP Motor RPM 1725 RPM Motor Rated Volts 208-2301460 Volts Motor Phase 3 Motor FL Amps 6.9-6.7/3.4 Amps Motor Service Factor 1.15 Motor Frame 56HZ Sheave Data RTU-01/Supply Fan Motor Sheave Model VL44 Motor Sheave Bore 5/8 in. Fan Sheave Model AFD74 Fan Sheave Bore 1 in. Number of Belts 1 Belt Size A48 Sheave Center Line 17 in. Test Pressures Filter SP In -0.42 in. we Filler SP Out NAC in. we Cooling Coil SP In NAC in. we Cooling Coil SP Out -0.60 in. we Fan SP In -0.60 in. we Fan SP Out 0.72 in. we System/Unit . Outlet Type Size AK Factor Design Velocity Final Velocity Design Airflow Prelim Alrflow' Final Airflow % Final Diff. Outlet-01 S 18X12 600 245 550 92 Outlet-02 S 18X12 600 245 545 91 Outlet-03 A3 12 400 515 380 95 Outlet-04 A3 8 150 190 165 110 Outlet-05 A3 8 175 255 190 109 Outlet-06 A3 8 175 290 190 109 Outlet-07 A3 8 175 275 185 106 Outlet-08 A3 8 225 230 245 109 Outlet-09 A4 8 250 305 270 108 Outlet-10 A4 10 250 280 275 110 Totals: 3000 2830 2995 100 Elite Balancing, LLC 5/10 ELITE E� ,-B BALANCING E; fiB Roof Top Unit PROJECT: Blue Federal Credit Union DATE: 2/17/2017 LOCATION: Fort Collins, CO CONTACT: Kevin Shaw PROJECT #: 2017-667 SYSTEM/UNIT: RTU-02 Unit Data Unit Manufacturer Carrier Unit Model Number 48HCFA06B2M5AOBOAO Unit Serial Number 3916CB8239 Design Min OSA 315 CFM Total Connected Airflow 2000 CFM Starter Data RTU-02/Sunply Fan Starter Manufacturer Factory Installed Actual Supply Airflow Actual Outside Airflow Actual Return Airflow RTU-02/SuoDIv Fan Actual RPM Volts Test Data 330 CFM 1745 CFM 1545 RPM 212/212/211 Volts 4.5/4.5/4.7 Amps RTU-02 Supply Outlet Summary Tested By: Josh Drake Date: 2/14/2017 Motor Data RTU-021SuoDly Fan Motor Manufacturer Marathon Motor HP 2.9 HP Motor RPM 1725 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor FL Amps 8.4-8.3/4.2 Amps Motor Service Factor 1.15 Motor Frame 56HZ Sheave Data RTU-02/SuDDIv Fan Motor Sheave Model 1VP40 Motor Sheave Bore 718 in. Fan Sheave Model AFD44 Fan Sheave Bore 5/8 in. Number of Betts 1 Belt Size AX38 Sheave Center Line 14 in. Test Pressures Filter SP In -0.76 in. we Filler SP Out NAC in. we Cooling Coil SP In NAC in. we Cooling Coil SP Out -0.88 in. we Fan SP In -0.88 in. we Fan SP Out 0.36 in. we System/Unit Outlet -T a Size AK Factor Design Velocity' Final Velocitv Design Airflow Prelim Airflow Final Airflow % Final DIM Outlet-01 S 18X6 350 140 355 101 Outlet-02 A4 12 400 330 410 103 Outlet-03 A3 8 200 170 220 110 Outlet-04 A3 8 250 180 260 104 Ouflet-05 A3 8 250 140 260 104 Outlet-06 A3 8 1 125 165 125 100 Outlet-07 A3 8 175 135 180 103 Outlet-08 A3 8 150 170 165 110 Outlet-09 B 6 50 60 50 100 Ouflet-10 B 6 50 70 50 100 Totals: 2000 1560 2075 104 Elite Balancing, LLC 6/10 ELITE NE BiB BALANCING be u Fan Unit PROJECT: Blue Federal Credit Union DATE: 2/17/2017 LOCATION: Fort Collins, CO CONTACT: Kevin Shaw PROJECT #: 2017-667 SYSTEM/UNIT: EF-1 Men Unit Data Fan Manufacturer Panasonic Fan Model Number FV-05-11VK1 Fan Serial Number 606 Design Airflow 75 CFM Design ESP 0.25 in. we Starter Data Starter Manufacturer None Test Data Actual Airflow 100 CFM Actual RPM Direct Drive RPM Volts 121 Volts Amps 0.1 Amps Fan SP In Atmosphere in. we Fan SP Out NAC in. we Tested By: Josh Drake Date: 211412017 Motor Data Motor Manufacturer No tag Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 0.27 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Model Direct Drive Log: EF-1 Men 2/14/2017 Josh Drake Left fan on medium speed. On low speed fan only does 60 CFM. SYSTEM/UNIT: EF-1 Woman Unit Data Fan Manufacturer Panasonic Fan Model Number FV-05-11 VK1 Fan Serial Number 606 Design Airflow 75 CFM Design ESP 0.25 in" we - Starter Data Starter Manufacturer None Test Data Actual Airflow 105 CFM Actual RPM Direct Drive RPM Volts 121 Volts Amps 0.1 Amps Fan SP In Atmosphere in. we Fan SP Out NAC in. we Tested By: Josh Drake Date: 2/14/2017 Motor Data - Motor Manufacturer No tag Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 0.27 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Model Direct Drive ����2ovY►-� Log: EF-1 Woman 2/14/2017 Josh Drake Left fan on medium speed. On low speed fan only does 65 CFM. Elite Balancing, LLC 700