HomeMy WebLinkAbout5917 Cross Creek Dr - Disclosures/Blower Door Test - 11/27/2018BUILDING LEAKAGE TEST Date of Test: 11/27/2018 Customer. RAH Test File: 5917 Cross Creek dr bd Technician: Michael Broussard Project Number: Building Address: 5917 Cross Creek dr Fort Collins, Colorado Test Results 1. Airflow at 50 Pascals: 2140 CFM50 (+/- 24.2 %) (50 Pa = 0.2 w.c.) 2.69 ACH50 2. Leakage Area: 117.7 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 457.1 (+/- 963.3 %) Exponent (n) = 0.395 (+/- 2.432) Correlation Coefficient = 0.89977 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Reduced Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 11/2712018 Test File: 5917 Cross Creek dr bd Building Information Volume 47705 Surface Area Floor Area Height # of Bedrooms # of Occupants Year of Construction Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Equipment Information Type 1Manufacturer Model Serial Number Custom Calibration Datej Fan Energy Conservatory Model 3 (110V) I _ P BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 11/27/2018 Test File: 5917 Cross Creek dr bd Depressurization Test: Environmental Data indoor Temperature (OF) Outdoor Temperature (OF) Altitude (ft) 69.0 46.0 5500.0 Data Points -Automated Test (TT 4.0.53.0) Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration -1.6 n/a n/a -60.7 -58.2 16B.4 2315 2243 -1.3 Ring A -55.4 -52.8 167.9 2312 2239 2.4 Ring A -49.5 -47.0 142.5 2134 2067 -1.1 Ring A -3.5 n/a n/a Time Averaging Period: 0 Deviations from Standard RESNET Multi -Point Test - Test Parameters - Fewer than 8 data points were taken. ` n value outside of normally accepted limits. ` correlation coefficient outside of normally accepted limits. ` n value and/or correlation coefficient limits are not officially part of the RESNET Multi -Point Test Standard. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 11/27/2018 Test File: 5917 Cross Creek dr bd -47.8pascals to gar -Passed Comments M