HomeMy WebLinkAbout4786 Mcmurry Ave - Disclosures/Blower Door Test - 04/26/2018 (5)April 26th, 2018
TO: Keith Holmes, Harmonic Construction; Dave Lenort & Kenny McMillan, Brinkman Construction
FROM: Sarah Allison, Lightly Treading, Inc.
RE: Final Comprehensive Report – Air Tightness Blower Door, Duct Leakage & Mechanical Ventilation Testing
Air Tightness Testing:
We performed Air-Tightness testing using Energy Conservatory Blower Door technology on a a minimum of 20% of the
units in the building. A sampling of 23 units and 3 commercial spaces at Oakridge Crossing located at 4786 McMurry Ave,
Fort Collins were tested against City of Fort Collins air-leakage requirements. The test results are as follows:
Unit # Conditioned Floor
Area
Surface Area of
Unit
Fort Collins code
maximum air-leakage
@50pa (0.3CFM per
ft2
of surface area)
Tested air-
leakage @ 50 pa
Pass/Fail
120 529 ft2 2,074 ft2 622 CFM 585 CFM PASS
123 826 ft2 3,025 ft2 907 CFM 658 CFM PASS
130 529 ft2 2,074 ft2 622 CFM 507 CFM PASS
135 826 ft2 3,025 ft2 907 CFM 609 CFM PASS
150 529 ft2 2,074 ft2 622 CFM 617 CFM PASS
156 529 ft2 2,074 ft2 622 CFM 599 CFM PASS
210 826 ft2 2,773 ft2 832 CFM 544 CFM PASS
213 826 ft2 2,773 ft2 832 CFM 445 CFM PASS
228 529 ft2 1,971 ft2 591 CFM 475 CFM PASS
237 529 ft2 1,971 ft2 591 CFM 439 CFM PASS
241 826 ft2 2,773 ft2 832 CFM 579 CFM PASS
2
248 529 ft2 1,971 ft2 591 CFM 466 CFM PASS
251 826 ft2 2,773 ft2 832 CFM 509 CFM PASS
253 529 ft2 1,971 ft2 591 CFM 439 CFM PASS
302 826 ft2 2,773 ft2 832 CFM 766 CFM PASS
310 529 ft2 1,971 ft2 591 CFM 574 CFM PASS
315 529 ft2 1,971 ft2 591 CFM 551 CFM PASS
327 529 ft2 1,971 ft2 591 CFM 499 CFM PASS
337 826 ft2 2,773 ft2 832 CFM 673 CFM PASS
341 529 ft2 1,971 ft2 591 CFM 485 CFM PASS
342 529 ft2 1,971 ft2 591 CFM 438 CFM PASS
347 826 ft2 2,773 ft2 832 CFM 600 CFM PASS
350 529 ft2 1,971 ft2 591 CFM 487 CFM PASS
Location Conditioned Floor
Area
Surface Area of
Unit
Fort Collins core
maximum air-leakage
@50pa (0.25CFM per
ft2 of surface area)
Tested air-
leakage @ 50 pa
Pass/Fail
1st Floor
Commercial
Space
2,770 ft2 9,542 ft2 2,385 CFM 1,780 CFM PASS
Billiards Room 303 ft2 1, 242 ft2 310 CFM 247 CFM PASS
Computer Room 182 ft2 876 ft2 219 CFM 218 CFM PASS
- All residential units met and exceeded City of Fort Collins air-leakage requirement for multi-family new
construction; 0.30 CFM@50Pa/ ft2
- All commercial areas met and exceeded City of Fort Collins air-leakage requirements of 0.25 CFM@50Pa/ ft2
3
Multifamily Test & Balance Criteria Checklists:
- Local Exhaust (spot ventilation): all bath fans operating at a minimum of 50 cfm intermittent or 20 cfm
continuous.
- Whole House Ventilation: meets code minimum air flow & is within code minimum to +120% of design flow.
o Code minimum and the design flow was agreed upon 84 cfm at the following specific set hours per day
for individual units:
▪ 1 BR Units that need 9.6 hours of ventilation per day = 85 units
• 1st Floor: 159, 156, 155, 154, 153, 152, 151, 150, 149, 143, 142, 141, 139, 136, 134, 133,
132, 131, 130, 129, 128, 127, 126, 125, 123, 120
• 2nd Floor: 253, 250, 249, 248, 247, 246, 245, 244, 243, 239, 238, 237, 236, 235, 231, 229,
228, 227, 226, 225, 224, 223, 222, 221, 219, 217, 216, 212, 211, 208
• 3rd Floor: 350, 346, 345, 344, 343, 342, 341, 340, 339, 335, 334, 333, 332, 331, 327, 325,
323, 322, 321, 320, 319, 318, 317, 316, 315, 313, 310, 307, 306
▪ 2 BR Units that need 14.5 hours of ventilation per day = 2 units
• 1st Floor: 144, 135
▪ 2 BR Units that need 14.3 hours of ventilation per day = 1 unit
• 3rd Floor: 300
All units were tested against the City of Fort Collins standards for local exhaust and whole house ventilation. 100% of the
units passed above requirements and have been verified by Lightly Treading.
Please contact me with any questions.
Take care,
Sarah Allison
Technical Consultant
Lightly Treading, Inc.