Loading...
HomeMy WebLinkAbout1921 Charles Brockman Dr - Disclosures/Blower Door Test - 07/17/2018BUILDING LEAKAGE TEST Date of Test: 7/17/2018 Test File: 1921 Charles Brockman Dr LC Homes TECTITE Technician: Zach Kimbrough - EnergyLogic Project Number: 51472 Customer: LC Home Building Address: 1921 Charles Brockman Dr Ft Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 962 CFM50 ( +/- 0.7 %) (50 Pa = 0.2 w.c.) 2.10 ACH50 2. Leakage Area: 52.9 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 56.1 ( +/- 5.3 %) Exponent (n) = 0.726 ( +/- 0.015 ) Correlation Coefficient = 0.99980 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 56.1 CFM 0.12 ACH 11.2 CFM per person 2. Estimated Design Infiltration Rate: Winter: 105.6 CFM 0.23 ACH Summer: 66.2 CFM 0.14 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 7/17/2018 Test File: 1921 Charles Brockman Dr LC Homes TECTITE Building Information Volume 27561.25 Surface Area Floor Area 3031.3 Height 20 # of Bedrooms 4 # of Occupants 5 Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 26986-7 8/2/2010 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 7/17/2018 Test File: 1921 Charles Brockman Dr LC Homes TECTITE Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 73.0 75.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -2.4 n/a n/a -62.0 -59.6 32.1 1032 1085 -0.7 Ring A -56.4 -53.9 27.8 961 1011 -0.6 Ring A -50.6 -48.1 229.0 896 942 0.6 Ring B -43.9 -41.5 183.9 804 845 0.5 Ring B -38.7 -36.3 150.1 727 764 0.2 Ring B -32.8 -30.3 116.7 642 675 0.7 Ring B -26.5 -24.0 81.4 537 564 -0.2 Ring B -20.6 -18.2 53.8 437 460 -0.6 Ring B -2.4 n/a n/a Time Averaging Period: 0 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 7/17/2018 Test File: 1921 Charles Brockman Dr LC Homes TECTITE Comments Garage: -47 PA Mech: -50 PA