HomeMy WebLinkAbout2330 Adobe Dr - Disclosures/Blower Door Test - 08/13/2018BUILDING LEAKAGE TEST
Date of Test: 8/13/2018 Test File: 2330 Adobe Dr 2.15ACH 8.13.18
Technician: Greydon Studer EnergyLogic
Project Number:
Customer:
Building Address: 2330 Adobe Dr
Fort Collins, CO 80525
Test Results
1. Airflow at 50 Pascals: 987 CFM50 ( +/- 2.1 %)
(50 Pa = 0.2 w.c.) 2.15 ACH50
2. Leakage Area: 54.3 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 59.1 ( +/- 19.8 %)
Exponent (n) = 0.719 ( +/- 0.053 )
Correlation Coefficient = 0.99666
4. Test Settings: Test Standard: RESNET Multi-Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 8/13/2018 Test File: 2330 Adobe Dr 2.15ACH 8.13.18
Building Information
Volume 27561
Surface Area
Floor Area
Height
# of Bedrooms
# of Occupants
Year of Construction 2018
Wind Shield M
Location Climate Information
Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) Default
Micromanometer Energy Conservatory DG700
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 8/13/2018 Test File: 2330 Adobe Dr 2.15ACH 8.13.18
Depressurization Test:
Environmental Data
Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft)
69.0 70.0 5000.0
Data Points - Data Entered Manually
Nominal
Building Pressure
(Pa)
Baseline Adjusted
Building Pressure
(Pa)
Fan
Pressure
(Pa)
Nominal
Flow
(cfm)
Adjusted
Flow
(cfm) % Error
Fan
Configuration
-2.5 n/a n/a
-72.0 -69.4 45.6 1224 1277 2.3 Ring A
-66.0 -63.4 35.3 1080 1127 -3.7 Ring A
-60.0 -57.4 32.6 1040 1085 -0.4 Ring A
-54.0 -51.4 27.9 963 1005 -0.1 Ring A
-48.0 -45.4 240.5 918 958 4.1 Ring B
-42.0 -39.4 172.2 778 812 -2.3 Ring B
-36.0 -33.4 142.8 709 740 0.3 Ring B
-30.0 -27.4 109.3 621 648 1.3 Ring B
-24.0 -21.4 72.9 508 530 -1.1 Ring B
-2.7 n/a n/a
Time Averaging Period: 5
Deviations from Standard RESNET Multi-Point Test - Test Parameters
- The Time Averaging Period is less than 10 seconds.
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 8/13/2018 Test File: 2330 Adobe Dr 2.15ACH 8.13.18
Comments
CAZ -48
House to Garage -48
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)