HomeMy WebLinkAbout2327 Adobe Dr - Disclosures/Blower Door Test - 06/30/2017BUILDING LEAKAGE TEST Date of Test: 6/30/2017 Test File: 2327 Adobe Dr LC Homes V2.1 Multi Point Tectite Technician: Neal Girard - EnergyLogic, Inc. Project Number: 46748 Customer: LC Home Building Address: 2327 Adobe Dr Ft. Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 1126 CFM50 ( +/- 1.2 %) (50 Pa = 0.2 w.c.) 2.71 ACH50 2. Leakage Area: 61.9 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 94.0 ( +/- 19.8 %) Exponent (n) = 0.635 ( +/- 0.052 ) Correlation Coefficient = 0.99662 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 65.7 CFM 0.16 ACH 13.1 CFM per person 2. Estimated Design Infiltration Rate: Winter: 123.5 CFM 0.30 ACH Summer: 77.5 CFM 0.19 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 65.0 CFM Base Rate: 65.0 CFM BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 6/30/2017 Test File: 2327 Adobe Dr LC Homes V2.1 Multi Point Tectite Building Information Volume 24925 Surface Area Floor Area 2748 Height 20 # of Bedrooms 4 # of Occupants 5 Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 36002-7 11/15/2012 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 6/30/2017 Test File: 2327 Adobe Dr LC Homes V2.1 Multi Point Tectite Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 70.0 80.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -1.0 n/a n/a -61.1 -59.4 45.3 1220 1271 1.1 Ring A -56.1 -54.4 39.2 1138 1186 -0.3 Ring A -53.2 -51.5 35.0 1076 1122 -2.3 Ring A -47.6 -45.9 31.8 1027 1071 0.3 Ring A -44.7 -43.1 29.9 996 1038 1.3 Ring A -41.3 -39.7 26.1 932 971 -0.1 Ring A -37.1 -35.4 216.4 871 908 0.3 Ring B -33.3 -31.7 184.5 805 839 -0.5 Ring B -2.3 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 6/30/2017 Test File: 2327 Adobe Dr LC Homes V2.1 Multi Point Tectite Comments Connection to: Garage: -48.2 Pa Mechanicals: -50 Pa