HomeMy WebLinkAbout217 Cordova Rd - Disclosures/Blower Door Test - 07/20/2017 (2)BUILDING LEAKAGE TEST Date of Test: 7/20/2017 Test File: Multi Point Tectite 39 unit 2 Technician: Trevor Donnelly- EnergyLogic Project Number: 46134 Customer: Cottage Builders Building Address: 217 International Boulevard Unit 2 Fort Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 1149 CFM50 ( +/- 1.4 %) (50 Pa = 0.2 w.c.) 4.14 ACH50 2. Leakage Area: 63.2 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 75.4 ( +/- 25.0 %) Exponent (n) = 0.696 ( +/- 0.065 ) Correlation Coefficient = 0.99561 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: 217 Cordova Road BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 7/20/2017 Test File: Multi Point Tectite 39 unit 2 Building Information Volume 16649 Surface Area Floor Area Height # of Bedrooms # of Occupants Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 7170-5 10/9/2008 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 7/20/2017 Test File: Multi Point Tectite 39 unit 2 Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 75.0 90.0 5000.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -1.8 n/a n/a -61.6 -59.8 45.5 1223 1311 0.7 Ring A -59.2 -57.4 42.7 1185 1271 0.4 Ring A -53.2 -51.4 35.8 1088 1166 -0.5 Ring A -49.9 -48.1 32.6 1039 1114 -0.3 Ring A -45.7 -43.9 259.5 953 1022 -2.6 Ring B -42.2 -40.4 249.4 935 1002 1.2 Ring B -39.1 -37.3 225.8 890 954 1.7 Ring B -35.2 -33.4 184.3 805 863 -0.5 Ring B -1.8 n/a n/a Time Averaging Period: 0 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 7/20/2017 Test File: Multi Point Tectite 39 unit 2 Comments Connection to: Garage: no garage Mechanicals: -50 Pa