HomeMy WebLinkAbout1206 Gold Dr - Disclosures/Blower Door Test - 09/20/2017BUILDING LEAKAGE TEST Date of Test: 9/20/2017 Test File: 1206 Gold Drive 3 Tectite Technician: Matthew Anthony Project Number: Customer: Building Address: 36 1206 Gold Drive 3 Ft Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 1215 CFM50 ( +/- 1.2 %) (50 Pa = 0.2 w.c.) 4.27 ACH50 2. Leakage Area: 66.8 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 84.5 ( +/- 8.5 %) Exponent (n) = 0.681 ( +/- 0.023 ) Correlation Coefficient = 0.99941 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 69.8 CFM 0.25 ACH 11.6 CFM per person 2. Estimated Design Infiltration Rate: Winter: 110.7 CFM 0.39 ACH Summer: 73.5 CFM 0.26 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com) BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 9/20/2017 Test File: 1206 Gold Drive 3 Tectite Building Information Volume 17085 Surface Area 4252 Floor Area 1786 Height 19 # of Bedrooms 5 # of Occupants 6 Year of Construction 2017 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) 30115 Default Micromanometer Energy Conservatory DG700 13013-7 10/25/2016 You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com) BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 9/20/2017 Test File: 1206 Gold Drive 3 Tectite Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 68.0 59.0 4940.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -2.1 n/a n/a -62.4 -60.3 57.3 1368 1390 0.6 Ring A -56.5 -54.4 49.1 1270 1290 0.2 Ring A -49.2 -47.2 39.3 1139 1157 -1.0 Ring A -45.4 -43.3 35.4 1082 1099 -0.3 Ring A -38.5 -36.5 27.4 955 971 -1.0 Ring A -31.2 -29.2 199.8 837 851 1.1 Ring B -26.0 -23.9 153.5 735 747 1.5 Ring B -19.4 -17.4 93.8 576 585 -1.1 Ring B -2.0 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com) BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 9/20/2017 Test File: 1206 Gold Drive 3 Tectite Comments None You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)