Project: Lyric Cinema FC
1209 N. College Ave
BP# B1606966
GC: Hoff Const.
Special Inspections:
Theatre Stadium Seating
Framing
1815 West 12th Street I P.O. Box 7448 1 Loveland, CO 80537 1 Tel. 970.669.3255 1 Fax. 970.663.1566
www.hoffconstruction.com
CTLITNOtwPSON Visual Weld and Bolt Report Date ,oiaao,7
Observation
Fort Collins
400 North Link Lane
Fort Collins, CO 80524
Phone 970-206-9455
Technician: Pappert, Jack
Client
Hoff Construction
1815 W 12th Street
Loveland, CO 80537
Date: 09112/2017
Project
FC06790 001-390
Proposed Lync Cinema
1209 N College Ave
Ft Collins, CO
Type of Inspection,
Visual Weld (AWS D1 1 Table 6 1) / High Strength Bolt (AISC Spec for Structural Joints Using ASTM A325 or A490 Bolts, Sect 8,9)
Weld Locations,
At the Lyric Theater, we inspected the wood framing for the stadium seating area, including concrete slab attachments, joint splices,
and header assemblies We observed that the header stud packs need additions to meet the plan requirements and that the
structures in fire nser room interfere with the planned support joist Re -design of this area and re -inspection will be needed
Plans By: CTL Thompson, dated 5-4-17
At the time of our observation, the items observed met the quality standards listed above: No
Discrepancies were observed, see attached discrepancy list: Yes
Oct 5 2017 1:13 PM
Page 1 of 1
CTLITHOMPSON
Fort Collins
400 North Link Lane
Fort Collins, CO 80524
Phone 970-206-9455
Technician* Pappert, Jack
Test Performed: weld/bolt
Discrepancy: Yes
Discrepancy List
Client -
Hoff Construction
1815 W 12th Street
Loveland, CO 80537
Date: 09/12/2017
Protect
FC06790 001-390
Proposed Lyric Cinema
1209 N College Ave
Ft Collins, CO
Report Date 10/4/2017
Discrepancy Information
Item Number
Item Description
Status
500
For the wood framing for the stadium seating area, the header stud packs
need additions to meet plan requirements, and the structures in fire nser
room interfere with planned support joist Re -design of this area and re -
inspection will be needed
Notified Contractor: Yes
Oct 5 2017 1:14 PM
Page 1 of 1
CTLITHOMPSON Visual Weld and Bolt Report Date 10/4/2017
Observation
Fort Collins
400 North Link Lane
Fort Collins, CO80524
Phone 970-206-9455
Technician Pappert, Jack
Client
Hoff Construction
1815 W 12th Street
Loveland, CO 80537
Data: 09121 /2017
Project
FC06790 001-390
Proposed Lync Cinema
1209 N College Ave
Ft Collins, CO
Type of Inspection:
Visual Weld (AWS D1 1 Table 6 1) / High Strength Bolt (AISC Spec for Structural Joints Using ASTM A325 or A490 Bolts, Sect 8,9)
Weld Locations:
At the Lyric Theater, we re -inspected the discrepancy items from the 9-12-17 inspection 1) Stud packs were fixed per original header
schedule 2) Joist was adjusted per revised drawing in the fire riser room
Plans By: CTL Thompson, no FC06790 000, updated 9-13-17
At the time of our observation, the Items observed met the quality standards listed above: Yes
Discrepancies were observed, see attached discrepancy list: No
Oct 5 2017 1:15 PM