Hoff Construction
1815 West 12 Street
Loveland, Colorado 80537
Attention Joel Reger
Subject Comprehensive Open Hole (COH)
Proposed Lyric Cinema
1209 North College Avenue
Fort Collins, Colorado
CTLIT Project Number FC06790-125
CTLIThompson, Inc previously provided a Geotechnical Investigation (Project
No FC06790-125, report dated January 26, 2015) We performed a comprehensive
open hole (COH) on March 1, 2017 to determine the foundation and floor subgrade
conditions Four test pits were excavated adjacent to the building footprint Materials
encountered to each test pit consisted of 2'/7 feet of import sand fill over native sandy
clay No organic or loose material was observed in the pits between the two materials
CTL conducted compaction testing on the sand fill during placement Based on
observations of the test pits and our testing, we believe the subsurface conditions
encountered are as anticipated for the foundation and floor subgrade
We appreciate the opportunity to work with you, on this project If you have any
questions regarding the information provided in this letter; please do not hesitate to
contact us
Sincerely,
r
400 North Link Lane Fort Collins, -Colorado 80524
Telephone 970-206-9455 1 fc(cDctithompson corn I www.ctit.com
CTLITHOMPSON Reinforcing Steel Report %portoate:3/130017
Fort Collins
400 North Link Lane
Fort Collins, CO80524
Phone 970-206-9455
Technician: England, Adam
Date: 03/08/2017
Placement Type Observed: Footing
Client:
Hoff Construction
1815 W 12h Street
Lowland, C080537
Project.
FC06790001-360
Proposed Lyric Cinema
1209 N College Aye
Ft Collins, CO
Placement Location: At the Lyric Lounge, we inspected the steel in the footing for the building foundation.
Items Checked- Bar Quantity and Spacing / Bar Size / Cover / Lap Length
Plans: CTL Thompson, no FC06790.000, dated 11-7-16
Remarks: We also checked bar grade and position.
Reinforcement was placed in general conformance with approved drawings and standard construction practice. Contractor
to ensure proper coverage is maintained at the time of concrete placement:
Yes
Reinlspection Required: No
Mar 24 2017 1:33 PM
Page 1 of 1
� CTLITHONIPSON Reinforcing Steel Report ReportDate• 3/21/2077
Fort Collins Client: Pro�ect
- 400 North Lmk Lane
FoR Collins,CO 80524 HoH Construcdon FC06790 001�60
Phone 97a20Cr9455 1815 W 12th Street Proposed Lync Cinema
Loveland,CO 80537 1209 N College Ave
Ft Colhns,CO
Technician: England,Adam
Date: 03/16/2017
Placement Type Observed: Column
Placement Location:
At the Lyric Cmema,we inspected the steel m the colums and foundatio�walls north wall,entry wall,north intenor wall,and tower
columns.
Items Checked: gar Size/Bar Quantity and Spaang/Lap Length/Cover
Plans• CTL Thompson, no. FC)6790,000,dated 9-14-16, pps.S1.0,S1 1, S3 0
Remarks:Also checked bar grade and position.
Reinforcement was placed in general conformance with approved drawings and standard construction practice.Contractor to
ensure proper coverage is maintained at the time of concrete placement•
Yes
Reinspection Required: No
`x Q�•REQ�s'T
�p THQ�,F,9
. ��� :
4 •
�'
y
��I. ,�
i
•�
bfJAi�
��� �� �e�7�;�� ��4
Page 1 of 1
� � CTLITHOMPSON Reinforcing Steel Report ReportDate:4/11/2017
Fort Collms .Chent: Pro�ect
- 400 North Link Lane
Fort Collins,CO 80524 Hoff ConstrucUon FC06790 001�60
Pnone 970.206-9455 1815 W 12th Stree[ Proposed Lync Cinema
Loveland,CO 80537 1209 N College Ave
Ft CoDins.CO
Technician: Giffin, Lee
Date: 03I31/2017
Placement Type Observed: Footing
i
Placement Location• At lhe Lyric Cinema,we inspected the rebar planned for inside walls.
Items Checked: Bar Size/Bar QuanUty and Spaang/Lap Length/Cover/Form Void
- Plans: CTL Thompson, no. FC06790,000,dated 11-7-16
Remarks: Also checked bar grade and position.
Reinforcement was placed in general conformance with approved drewings and standard construction practice.Contractor to
ensure proper coverage is mamtained at the time of concrete placement
Yes
Reinspection Required: No
4 Q� ��C�/S+
�,,..,..
_ � �•a,THo,�,�,�
.
�� .
3617 ;
.
.
. :
., �.
•. .
� ''• .. .�•�{''
ti �lA�
Apr 12 2017 6:53 AM
Page 1 of 1
�CT�ITHOMPSON Reinforcing Steel Report ReportDate 6��20,�
Fort Collins Client. Pro�ect•
400 North Link Lane
Fort Collins,CO 80524 HoH Construdion FC06790.001�60
Phone 970-2069455 1815 W 12th Street Proposed Lyric Cmema
Loveland,CO 80537 1209 N College Ave
Ft Col6ns,CO
Technician: Giffin,Lee
Date: 05/30/2017
Placement Type Observed: Slab on Grade
Placement Location:
At the Lync Cinema,we mspected the reinforang steel in the floor at the southeast comer of the buildmg,4 x 4 mch wire.
Items Checked: Bar Size!Bar Quantity and Spaang/Lap Length/Cover
Plans: CTL Thompson, no. FC06790.000,dated 9-14-16
Remarks:Also checked bar grade and position.
Reinforcement was placed in general conformance with approved drawings and standard construction prectice.Contractor to
ensure proper coverage is maintamed at the time of concrete placement
Yes
Reinspect�on Required: No
I O �ti/
.� o,,.....,,s�,
��y.rKo�,F
. 3617'
� '
. :
. .
. ;
i �.�
., ��
� ••.. ..�
tO�NA�
Jun 12 2017 8:30 AM
IPage 1 of 1
�
�CTLITHOMPSON Reinforcing Steel Report ReportDate. B/22/2017
Fort Collins Client: Pro�ect
400 North Link Lane
Fort Collins,CO 80524 HoH Construcdon FC06790.001�60
Phone 970-20fa9455 1815 W 12th Street Proposed Lync Cmema
Loveland,CO 80537 1209 N College Ave
Ft Collms,CO
Technfcian: England,Adam
Date: 08I15/2017
PlacementType Observed Other
Placement Location• At the Lync Cmema pro�ect,we inspected the steel in 6 light pole bases.
Items Checked: Bar Size/Bar Quantity and Spaang/Lap Length/Cover ,
Plans: CTL Thompson, no.FC06790-500 L2,no date groen
Remarks: We also checked bar grade and position.
Reinforcement was placed in general conformance with approved drav�nngs and standard construction practice.Contractor to
ensure proper coverage is maintained at the time of concrete placement.
Yes
Reinspection Required: No
.� ,a•RE���'r
�p.THp,�,�`
. ���
. :
. .
'�.. ,.
. ,.
. ,
•�•.. ...
��
� Page 1 of 1
' �{ CTLITHOMPSON Reinforcing Steel Report ReportDate•8/22/2017
FoR Collins Client: Pro�ect
• 400 North Link Lane
Fort Colhns,CO 80524 Hoff Construction FC06790.001�60
Phone 970.2069455 1815 W 12th Street Proposed Lync Cinema
Loveland,CO 80537 1209 N College Ave
Ft Colluis,CO
Technician: p�son,Todd
Date: 08/17/2017
Placement Type Observed: Footing '
Placement Location•
At the Lync pro�ect,we inspected the steel in the footmg base for the trash enclosure 2#4 bar only at bottom,at 90 degrees,#4 bar
at 16 mches on center and wet stabbed at hme of pour,top 2#4 to be set at bme of pour.
Items Checked: Bar Size I Bar Quantity and Spaang/Lap Length
Plans: CTL Thompson Structural Engineenng, no.FC06790.000,dated 11-7-16
Remarks:Also checked bar grade and position.
Reinforcement was placed in general conformance with approved drawmgs and standard construction practice.Contractor to
ensure proper coverage is maintained at the time of concrete placement:
Yes
Reinspection Required: No
;; a�•R����r
' ��,,rH�,a,�,F,9
3�r
: :
. .
. .
.,� ;
�'••.E. e•�',
Sit7NA�-
Aug 22 2017 5:40 PM
Page 1 of 1
' �-CTLITHOMPSON Reinforcing Steel Report ReportDate•8/31/2017
Fort Collins Client: Pro�ect•
• 400 North Lmk lane
Fort Collms,CO 80524 HoH Construdion FC06790 001�60
Phone 970-20fr9455 1815 W 12th Street Proposed Lync Cinema
Loveland,CO 80537 1209 N College Ave
Ft Colluis,CO
Technician: England,Adam
Date: 08/22/2017
Placement Type Observed: Slab on Grade
Placement Location: At the Lyric Cinema pro�ect,we inspected the south trash enclosure slab on grade.
Items Checketl: Bar Size/Bar Quantity and Spaang!Lap Length i Cover
Plans: CTL Thompson, no. FC06790-500 L2,dated 11-7-16
Remarks: We also checked bar grade and position.
Reinforcement was placed in generel conformance with approved drawings and standard construction practice.Contractor to
ensure proper coverage is maintained at the time of concrete placement
Yes
Reinspection Required. No
, � /