HomeMy WebLinkAbout244 N College Ave - Special Inspections/Field Verification - 11/29/2017A \l Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 — Eaton, CO 80615 • Phone (970) 454-5351 — Fax (970) 454-5391 2389 7-494/ CERTIFIED TEST, ADJUST, AND ` BALANCE REPORT DATE 11/29/17 PROJECT Da Vinci Body and Board Fitness Center The Exchange Fort Collins, CO ***Final Report*** ARCHITECT ALM2S 712 Whalers Way Fort Collins, CO ENGINEER The Ballard Group 4730 South College Avenue Fort Collins, CO CONTRACTOR Air Comfort, Inc. 150 Rome Fort Collins, CO Q 9z9 ? ;Its lied =ei r L' N O UM) MCI yZ� DA VINCI BODY BOARD FITNESS CENTER z BRINKMAN i S H § ' FORT COLLINS, CO s J r GRILLES, REGISTERS & DIFFUSERS SCHEDULE ew cane MANarAtll@A aYmaxo Trna arms «mc � an rArt aof °9 waaE wsu aen MATw.I •cuxioa T1}E nmH molar su- FAN SCHEDULE cm nawaAalYml w,aa rn es aA Mo,aM n caMma. °a,seM coos anmea xa Txve w vn Nn Tvve mMRla Rlr OIYUaY® 9RY6Yf �N Mma PpR�xPMglol . wuanpwnrW wrtnws VARIABLE AIR VOLUME TERMINAL SCHEDULE (ELECTRIC) RAM aoE INMia YoorLxa MAT LounoM MFT aQE Aaaaxmr Y �Cfn m lan I nAT (a.n 1a,n1 av w macs I rarAsam mWUle MW a1FIa UT rn uT rn WLn o H l 1Y M.rma 2012INTERNATIONAL MECHANICAL CODE - CHAPTER 4 MINIMUM OUTDOOR AIR REQUIREMENTS FOR MECHANICAL VENTILATION Hao° RM INIE waaa NEA Iffl ftwmmffA ° =WW pFN91Y V+M+aq ocweAxra r[oe,e alla°a11 Mlana AmA allaafll Mlvn aaA R1n Nn u m mnYaD YFC0.Eallaaal MYIaNIarwW ApFAQIIa°al Aeeaananevl ° 00 o m ►—ICI—!l—P--i 0 0 ELECTRIC VAV TERMINAL CONTROL DIAGRAM (VAV-3-1 N) L n EXPOSED DUCT REGISTER DETAIL u EXPOSED DUCT HANGER DETAIL 7 Z ~ O u z c L J Q Y J O Zu Q m m� } O c Q m L% Z Q 61 4 MVAcoeruaxcownas Axosarwnes i Lawrence H. Finn & Associates, Inc. • ' . 55 S. Elm Ave, Suite 220—Eaton, CO 80615 2389 Phone (970) 454-5351 —Fax (970)454-5391 PROJECT. Da Vinci Body and Board Fitness Center ADDRESS Fort Collins, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any , variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB "Procedural Sfandards for Testing, Adjusting & Balancing of Environmental Systems" and the project specifications. NEBB TAB FIRM Lawrence H. Finn & Associates, Inc. REG NO � 2389 CERTIFIED BY David C. Reichel DATE 11/29/17 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB "Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems" and the project specifications. NEBB TAB FIRM Lawrence H. Finn & Associates,Inc. REG NO � 2389 CERTIFIED BY David C. Reichel DATE 11/29/17 SUBMITTED &CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR• David C. Reichel REG N0.: 2389 SIGNATURE: iti� �S DATE 11/29/17 CERTIFICATION EXPIRATION DATE: 3/31/2018 � ' Lawrence H. Finn & Associates Inc. N E} B B � � a ' 2389 Table Of Contenfs PROJECT: Da Vinci Body Board Fitness Center DATE: 11/29/2017 LOCATION: Fort Collins,CO ' CONTACT: Joe Marshall AUTHOR: Joe Marshall Table Of Contents 1 Instrument Calibration Report pdf .. . ... .. . ... .. . . ... .. . . .. 1 2 Abbrewation Report.pdf... .............................................. ........ .. .. .... .. ..... .. .. ..................... 3 3 Air Handling Unit. . . .. .. .. .. .. ......... ..... . . . . . . . .. 4 3 1 (E)AHU . . . . . . . ... . .. . . . .. . ... .. . . . . . . 4 3 2 (E)AHU/VAV-3-1 N . .. . .. . .... ....... . . . .. . . .. . . . ... . .. 4 4 Fan Unit .. . . . . . . . .. . ... .............................. . ... . . .... ................ . 5 4.1 EF-7N. . . . . .. . ....... . ........................................ ... .. . ... ............ ... . 5 . ... 5 Prints.pdf. . ... . . . .. .. . . . . . .. . . . .. . . .. . ..... ... .. . .. . ..... . 6 L.H. Fmn and Associates Final Report � � � Lawrence H. Finn & Associates, Inc. 55 S Elm Ave, Suite 220-Eaton,CO 80615 • Phone (970)454-5351 - Fax(970)454-5391 2389 INSTRUMENT CALIBRATION REPORT Pro'ect: Da Vinci Bod and Board Fitness Center Manufacturer Model Serial A lication Cal Date Alnor HM-680 70552109 H dronic Press. & Diff Press 1/16/2014 Alnor HM-680 70750150 H dronic Press & Diff Press. 12/14/2015 Alnor HM-680 70838501 H dronic Press & Diff Press 11/30/2015 Alnor HM-680 71021246 H dronic Press &Diff. Press. 4/5/2016 Alnor HM-680 71043011 H drornc Press. & Diff Press 6/10/2015 Alnor HM-680 91139097 H dronic Press. & Diff. Press 7/7/2017 Cooper SH66A 92711016 Tem erature Measurement 10/9/2017 Extech 461895 Q394479 Rotation Measurement 4/17/2017 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 3/8/2016 Extech 461895 Q331990 Rotation Measurement 11/4/2014 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 10/3/2017 Extech 461895 Q590099 Rotation Measurement 4/17/2017 Extech RH390 9099221 Tem erature/Humidit 4/9/2015 Fluke 335 96960004 Electncal Measurement 11/5/2015 Fluke 336 97110539R Electncal Measurement 4/5/2016 Fluke 336 97110538R Electncal Measurement 9/29/2015 Fluke 335 92008180 Electncal Measurement 11/4/2014 Fluke 335 12990071 Electrical Measurement 3/4/2016 Fluke 374 15460133 Electncal Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 10/3/2017 Fluke 374 20030354 Electncal Measurement 4/17/2017 TSI 8322 55100720 Air Veloa Measurement 10/4/2017 Shortndge ADM-860C M05789 Di ital Manometer 11/25/2015 Shortndge ADM-860C M06821 Di ital Manometer 4/18/2017 Shortridge ADM-860C M07352 Di ital Manometer 6/6/2016 Shortndge ADM-860C M09123 Di ital Manometer 4/18/2016 Shortridge ADM-860C M09347 Di ital Manometer 9/26/2015 Shortndge ADM-860C M10144 Di ital Manometer 4/14/2017 Shortndge ADM-860C M10371 Di ital Manometer 11/5/2015 Shortndge ADM-860C M11448 Di ital Manometer 4/14/2017 Shortndge HDM-300 W02060 H dronic Press & Diff Press 10/5/2015 Shortridge HDM-250 W09198 H drornc Press. & Diff Press 4/18/2017 Shortndge HDM-250 W98020 H drornc Press & Diff Press 4/8/2015 REMARKS. Not all equipment shown was used on this pro�ect. " Page 1 of 8 � • INSTRUMENT CALIBRATION REPORT(Continue) Pro'ect: Da Vinci Bod and Board Fitness Center Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017 Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 9/27/2016 Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 9/28/2016 Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 9/29/2016 Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 9/30/2016 Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 10/1/2016 Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 10/2/2016 Evergreen Telemetry S-PVF-1 1600322 Pressure Veloaty Module 10/3/2016 Evergreen Telemetry S-PVF-1 1700213 Pressure Veloaty Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700214 Pressure Veloaty Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 5/12/2017 Evergreen relemetry S-PVF-1 1700216 Pressure Veloc�ty Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/12/2017 Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/12/2017 Evergreen Telemetry RM-T-1 1700269 Radio Module 5/17/2017 Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1600235 Radio Module 10/12/2016 Evergreen Telemetry RM-T-1 1600233 Radio Module 10/14/2016 Evergreen Telemetry RM-T-1 1600234 Radio Module 10/16/2016 EvergreenTelemetry RM-T-1 1700260 RadioModule 4/21/2017 EvergreenTelemetry RM-T-1 1700261 Rad�oModule 4/21/2017 Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 5/17/2017 Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/11/2016 Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/13/2016 Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/15/2016 Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/17/2016 Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017 Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017 Evergreen Telemetry S-DP-125 1700112 Water Press Sensing Module 3/2/2017 REMARKS• Not all eqwpment shown was used on this pro�ect Page 2 of 8 n Lawrence H. Finn & Associates, Inc. ' S5 S Elm Ave,Surte 220-Eaton,CO 80615 • Phone (970)454-5351 - Fax(970)454-5391 2389 ABBREVIATION REPORT , i � Project: Da Vinci Body and Board Fitness Center S mbol Descri tion S mbol Descri tion A AirFlow US NS Not Shown AF Air Foil NT No Information Ta ANA Access Not Avadable OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceilin Diffuser SD Su I Diffuser CFM Airflow Cubic Feet/Minute SNKL Snorkel DD Direct Dnve SP Static Pressure Des Desi n SPD Static Pressure Dro DWDI Double Width Double Inlet SR Su I Re ister EF Exhaust Fan SWSI Sin le Width Sin le Inlet EG Exhaust Grille T Tem erature C ER Exhaust Re ister T Tem erature F ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Fre uenc Dnve GPM Waterflow Gallons/Mmute VS Vanable S eed HC Heat Coil W Waterflow L/S HER Heat Exchan er HRC Heat Recove Hz Hertz ID Inside Diameter In.WC Inches of Water Column NA Not A licable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Ta NR Not Readable REMARKS Page 3 of 8 r L�wrence H. Finn & Associates, Inc. N�E� B B 2389 Air Handling Unit PROJECT: Da Vina Body Board Fitness Center DATE: 11/29/2017 LOCATION: Fort Collins, CO CONTACT: Joe Marshall � AUTHOR: Joe Marshall (E)AHU Return Inlet Summary System/Unit Area Served Outlet Type Size LzW!D AK Faetor Maximum Prelim Maximpm. =."/o Prelim< %Final � ' � Desi n Readin �Final�� �De'viation Deviation Inlet-A See Pnnt RG-1 30x16 1800 1736 1736 96 96 � Totals:� • - - 1800 1738 1736 > `�� 86 = 96 SYSTEM/UNIT: (E)AHUNAV-3-1N Tested By. Joe Marshall Date 11/29/2017 ' '� �Unit Data . . Term Box Test Data;� � � . � Manufacturer Pnce Max Des CFM 1800 CFM Model Number SDVS Max Act CFM 1843 CFM Box Inlet Size 14 In Min Des CFM 540 CFM K Factor-1 1 0 Min Act CFM 553 CFM Heat Des CFM 900 CFM Heat Act CFM 912 CFM (E)AHUNAV-3-1N Supply Outlet Summary SystemNnit ;Area Served � Outlet Type Size LxW J�� AK Factor Maximum •�=Prelim � Maxlmum, „°!o Prehm� ;`>%Final � - - �` ' -° - Desl n �Readin _ Final' - =Deviation Deviati�on� Outlet-01 See Print SR-1 18x6 300 326 307 109 102 Outlet-02 See Print SR-1 18x6 300 339 301 113 100 OuUet-03 See Pnnt SR-1 18x6 300 341 311 114 104 OuUet-04 See Pnnt SR-1 18x6 300 311 302 104 101 OuUet-05 See Pnnt SR-1 18x6 300 336 309 112 103 OuUet-06 See Pnnt SR-1 18x6 300 315 313 105 104 ° Totals: , - - 1800 1968 1843 �".109,K;,�= �^.�102 -3� L H Finn and Associates Final Report Page a or a � ' Lawrence H. Finn & Associates, Inc. N E� B B 2389 Fan Unit PROJECT: Da Vmci Body Board Fitness Center DATE: 11/29/2017 LOCATION• Fort Collins, CO CONTACT: Joe Marshall AUTHOR: Joe Marshall SYSTEMIUNIT: EF-7N Tested By Joe Marshall Date. 11/29/2017 � ' � ` � Unh Data' � _ ' `Motor�Data �°�'� � ,' Fan Manufacturer Greenheck Motor Manufacturer Van Green Fan Model Number G-103-VG-4-X Motor RPM 300-1750 RPM Fan Serial Number 15226232 Motor Rated Volts 115/208-230/277 Volts Fan Type Backward Incline Motor Phase 1 Fan Class 1 Motor Hertz � 60 Hz Fan Arrangement SWSI Motor FL Amps 2 85/1 7/1 5 Amps Fan Discharge Downblast _ '� _ SheaveData'�'��" ` ; _ � � � Starter Data " � r � Motor Sheave Make Direct Dnve Installed Thermal Internal . , �_,.,. �< Test Data � � "°�� � Total CFM Design 500 CFM Total CFM Actual 518 CFM Fan RPM Actual Medium High Speed RPM Motor Volts 1 119 Volts Motor Amps 1 2 2 Amps SP In Actual ANA in wc SP Out Actual 0 0 in wc � , L.H. F�nn and Assoc�ates F�nal Report Page 5 of 8 r , GENERALLEGEND HVACLEGEND DA VINCISHEETINDEX .eev sr�ea o[sc� .mr arm ocx..nox s'�T �¢a�wnc,uumxwmwo�eerm� scuF .� m.,� .. � .a,�,� � .e ��v p ..�.a�mi o rac wn¢ve rn+nw � ww��u� �CINNIGLGENEMLHOTES wrttauic.mR�ua �rc .cna�omnuiu O y�y�� � I�A«T �rr rr�s Q mwn ona�mi�nmors �mncir�anv�w�u���o�muemwv �/ �rr r�mim O r�anru� � Inu.0 iV n '"°' � 2.�..�P : •.a.r�..s.�.. .�. oa.�T s..00�.o.R,a... ~ m B .m.�.o.._A� � � ,�,��.......�� . .,a �����,.,...RA�.�, W ... �,...�., � t� �,.......,..�..,�....��..� ' .m.,.�, ..,,m.a..e..,..o.�.,..�.,�r.,.�...a ' V � �. � � �.,.,,�. ' .�.... a ....,.a.,a,A.,..m,�...a.. 2 y� . ..,. � m..m.�� � .m. ..e..s,�..,.. .W.......,,.b�.�,�...,..� W . ... � wo..�.�.�. � e o.�W.,a ,e.., �. .... Z � M �'� ....�.o�....,b o.. 3 ...�..a..a.�.,��R...:nA�"�""'� s.��.�.�aq�..�. Q Z N � w.rmo�runr�wrrw a�ac�rr�o�.muwno �e�o .wra.�muma�a Q a J L}� , w�we� .ms •av�a+.e.maMEOMNIGLNv�CxOfE9•'miwm.vw.o.o�vm O m u Ll �w � � t�orons am m� r waiv �mmo� r 0 — O �ie'vr� � �.�'�����„ rm���mvnv�rwrtxwu�nw�v��c•M1, m wr � '^��^�, ' r+rr�r���a.�vmr wuMrnmvionYrnoc*�rc�uuvn.um " V � . • wwn�im�w.�e��rwoa.smov.�rnm�nm�x •� � n e o~oa�.owrva��w�wr� srsena.ra�emwuoor2�uauam � n w�n ...rtn.r�wuim'r � � ��Y rYevrr.Wwu�mwn�ea�naar�w+�tawuxuinso � M/AC IN5IMPOH NpTEi A - Ip�)�1 OpVA�� 5 MFOI.WKAIIfGFN�5Y1D �.. GFMER4 NOI[5 q� �� � . , , , , _ , . --`..°`�'� � MP0.0 I I --- "J a � .r..,