HomeMy WebLinkAbout225 Green Leaf St - Disclosures/Mechanical - 07/19/2017City of Fort Collins Residential Mechanical Systems Performance Report Updated 3/7/2014 This form is a record of testing targets and results, with Pass/Fail outcomes For information on measurement tools CCCKYof and testing techniques, see the °Residential New Construction Mechanical Systems Testing Guide' The guide and Fort Collins this form may be periodically updated, check the Building Services web site for the current version �f This form must be completed and signed by an "Approved Agency,' and submitted to Building Services as a requirement for receiving a C O Color key Target Measured value Other or limit to compare with Pass Fail Caution ' data target or limit ADCF = Air Density Correction Factor, based on tool ADCF altitude (5000'), air temperature through tool Volumetric Flow (CFM 5000') = ADCF x Indicated flow (CFM) 11. House Data ``�"��'•� � � Date of 'Residential Address 225 Green Leaf"D� Unit- _ =*� 3/1/14 Mechanical Systems Budder '< " Design Submittal' Philgreen,QonstfUCtlOf)1 gj&information referenced ` _ by testing technicians ect'Ternp - HVAC contractor Per -� As -built changes mech design submi Testing dates) Rough Duct test 6/7/17 - FinaleTses 7%19/17 "'{' 77 ' Local.•Ventilation) Bath exhaust Testing tech (initials) N Flow ✓Flow box Pilot tube duct traverse Air temp ADCF ' tool Passive flow hood Other (note ttelow) through tool (F) Measured Airflow Design Minimum Airflow Requirement Indicated Volumetric Exhaust Pickup Location (CFM ow (CF (CFM 5000') Flow Flow Pass Fail 5000.) + Type of Operation (CFM) (CFM 5000') Back,bed 50 �/ 50Intermment 20 Continuous i ,60 66 ❑✓ ❑ 2nd f100r`bath ' ,% 50"- �50Intermment ❑20 Continuous t �95 108 ❑✓ ❑ Lowed bath 503 n < �/ 50 Internment 20 Continuous " 116 _ 128 ❑✓ ❑ 5o intermittent 20 Continuous ❑; ❑ ' , 50 Internment 20 Continuous . — ❑r ❑ 50 Intermittent20 Continuous El ❑ ❑50 Intertnment ❑ 20 Continuous Testing notes Kitchen exhaust N/A - hood does not vent to outside ❑ Testing tech (initials) NG I Oven fuel Gas ,/ Electric I Minimum airflow requirement (CFM 5000') +operation 0100 Intermittent Q 25 Continuous = Weasuredairtlow {{ Flow box ✓ Pilot tube traverse Interior=griller<, Air temp Flow .r r Tool s „,.a Passive flow hood -❑Flow grid 0 Exhaust duct through ADCF tool �. - location 72" j f_ t I Powered flow hood Ocher (note below) (Emni+or`cerm i ok 3t tool (F� -t I j Indicated flow 104 CFM Volumetric flow 114 CFM 5000' op;, I ' Testing notes _ t" Residential Mechanical Design Submittal , V20140307 Page 1 13. Whole -House Ventilation Systems other than sub -structural floor exhaust Testing tech (Initials) FNG i Code -minimum ventilation airflow 38 CFM 5000' Design ventilation29 CFM 5000' Exhaust -Dory based on CFA and g of BR airflow System Su t •oni type PP Y Y F3oclamimmurn) 8 to 46 CFM 5000' Balanced Target ventilation airflow range e_ (i2o% of design now) Measured 'Airflow -�---- I Air Temp Indicated 'Volumetric Measurement Method Tool Location Through ADCF Flow Flow Pass Fail Tool (F) (CFM) (CFM 5000') Total exhaust ❑ N/A ❑ Passive flow hood Flow box ❑ Pilot tube traverse m. AT FA ._ .2; 1._1 9'0 100 ✓❑ ❑ airflow ❑ Flow collar ❑ Other (note below) , � tt ; Total ❑ N/A ❑ Passive now hood ❑ ❑ supply ❑ Flow box ❑ Pilot tube traverse airflow Flow collar Other (note below) When supply airflow is circulated by au handler fan, fan speed for measurement Heating ❑; Looting I F Continuous lan ,Balanced airflow in balanced systems Average of measured CFM i supply + exhaust flows 5000, t Target flow range t� Fadt (average+/• 15%) 5CFM 0 o 00, 0Pass ' t T�eso�nfored builder to set fan to un f tm0r'QQRS, Ali r�. Sub-structural floor exhaust ❑ WA — no sub -structural floor exhaust system Testing tech (initials) ENG ( Design exhaust airflow (based on CFM Target airflow limas to CFM 5000' 1 { approved design) CFM 5000' (design +/- 15%) ,Measured airflow Flo Flow box Pilot tube traverse Tool Air temp tool ❑ Passive flow hood Flow collar location throughF] Powered flow hood Other (note below) tool (F) Indicated flow CFM Volumetnc flow CFM 5000' i u •'� V I� ADCF � Pass ❑ Fail `l5. I ! Z, Heating + Cooling Duct Leakage WA No ductwork Testing notes No ductwork outside conditioned space (Intl multiple Sys) NGF Testno tech (initials) Duct leakagelny, _ Energy,rater,' (name, data source compatesting date) 'N_ea(� House conditioned floor area 1533 Au temp 82 1' 11 ± _ (miude lull besemerdsf ADCF )� through tool (F)82 .'i� 9' Residential Mechanical Design Submittal V20140307 Page 2 For multiple systems, attach one page per system System 4FTI Which parts o1 house does it serves Installed equipment Be clear about which AC components are installed at time of testing) Testing tech (initials Furnace or Boiler AC or Heat Pump Condenser AC or Heat Pump Coil J Manufacturer /' O F-dd(,'� r n - Model !< ( Filter Type `�'Electrastaglc' '�"s _ Basic fiberglass ?+� w- ;.:" BasicYpleated - '2Other,"` " 3" ` �- Thickness a MERV❑ (inches) .(optional) brand High -attic pleated , Y Testing tech (initials) Static oressures sting ❑ Goofing ❑ Cont tan for multi -stage equipment Humidifier damper 04, Opeyy (Heating) Fla sad°(Cooling) L14re—gisters open ClZen'e dedampers open SP1 DP Filter (SP1 - SP2) Cooling- Measured air rrflloow--through indoor coil Design cooling aidiowl ' pa�'�" CFM 5000' (high stage) lt,i i Measured airflow FlowgndK plate size20 Air temp through to01 (F)1 i Measured airflow, no ad)adjustment/correctionCFM t Testing notes (Same location ' L. tot NSOP 7FSOP1 Cod �� ! )-SP4) - - otai ESP t WA -- no AC installed Testing tech (initials) _ T7 Target airflow limits to 2 Q CFM 5000' (design +1- 150/6) J - - q TFSOP❑ Flow Resistance ADCF J Qp� NSOP 1 t f Correction Factor Indicated airflow n r CFM Volumetric airflow CFM s (. CiMeasured AF z FRCF IrxlkalaE AF x AOCF Fad Heating Gas manifold pressure thigh stage) manifold IWC Target P //�J' Manifold 0pressure WC 9 �V OEM spec 50limits (spec +/- 5%) /v Heating- Temperature rise I ) y OEM temperature nse limits F ' (high stage) to Supply ReturnMeasured temps (F) We I =J — air _ Testing tech (inibais) Measured c QPas _ s, pressure _ ` Fail -r Testing tech (initialsl(�6y _ I f no AiS14 ta: r � l�Ie-�.� r:�rn• Temp �P u []Caution top o within tOF nse b ass Fad of top of range ' V20140307 Page 3 Residential Mechanical Design Submittal 4 � - _ Testing l3 ^• tech h (maais)w Testing app tihand targets � ANo complete AC system ❑,N/A House completed November- April pretaak g ConVecter respo WWa for testing in warm weather) ❑TXV Subcooling + SH check ❑Non-TXV Superheat ❑OEM-specdic Approach ❑Other OEM -specific (docianentatron requued) 3 ;Temperatures Condenser Non-TXV Return a Target Target Target t (F) entering air temp air wet -bulb temp superheat subcoohng approach Subcooling f Discharge Condenser Ligmd Actual ❑TXV Pass Actual SC within +/- 1 i pressure ❑ saturation 7❑F ineF sulxwolmgOF 3 F of target SC. 2 F min PSI (soar chart) temp (Corm T iq fine T) [:]TXV Fail 1Superheat - { ( Suction Evaporator Suction Actual ❑Non-TXV Pass ActualSH y pressure❑ saturation T�F Ime❑F super heat❑F ❑Non-TXV F otntarg T1SH ..._.- j (PSI) (soon chart) temp (Sunun9T e�apT) Non-TXV Fad !_ TXV checks ❑;Pass Field -installed TXV installed in accordance with OEM instructions ❑Caution Actual SH outside mfgr range fApproach f Ugwd line Actual appmach�F ❑Approach Pass Actual approach within +/- 1 F of target approach I � temp (Nq One T - condenser FAT) ❑ Approach Fad Room Register air flows Tasting tech (inivals) NG _ All registers are cut through finish materials and moving air rl(� Pass ❑Fad Y (Remainder of register air flow section under development, not yet being enforced) t Pressure balance Testing tech (initials) NG Room Room -to -Core Measured (match names on plans, include Pressure Drop Pressure Pass Fall basement it there is a door) Target Range (Pa) Drop (Pa) Back bed -3 to +3 -2 0» ❑ Front bed 3to+3 _� 1❑,'❑ 3 to +3 ❑ ❑ -3 to +3 ❑ ❑ -3 to +3 ❑ ❑ -3 to +3 ❑ ❑ n ' s r° -3 to +3 ❑ ❑ y -3 to +3 ❑ ❑ 3 to +3 ❑ ❑ -3 to +3 ❑ ❑ Residential Mechanical Design Submittal V20140307 Page 4 8. Combustion Safety I Combustion safety testing WA -- no natural -draft combustion appliances - Testing tech (initials) NG (Appliance Types table must be completed for every home) e Appliance types = Appliance Combustion TYoe WA Draft -hood Natural -draft Induced -draft Natural raft Power- vent Direct- vent Powered sealed- combustion , Electric Furnace Al ❑ ❑ . 0_ht..5 3e®ii ®=.'Q E:a ;v° :� _.. _ ❑ Furnace ri2 ❑ ❑ dp617 ^ ONE MRS KM,❑ ❑ Bader #1 ❑ ❑ :—am7m O ®, ® � ® ® Q ® ®,� �C ew v0' WOOL,, ,�(":e - Y'.,. �. ❑ Baler #2 ❑ ❑c®. Water heater #1 El ^❑,'- ',�,,°r Pfi ❑- , '; �'❑ Water heater #2 ❑ ❑� ' n � :'nth'❑f°`° - " s ❑' Fireplace fit ❑ ❑ ® ,.; ® ' 6® ff.';Uw—s' Fireplace #2 ' ' ❑ 0 ®p a �f ®� =a®: ❑ ° Other ❑ a `Q �k®® .. ❑ ❑ r^ Worst -case depressurization performance 'House setup` These doors are closed a of bath fans on _ Vented range hood on 1 Clothes dryer on ��` � ; ,_,, 1114 „'+' t _Air handler on 1 Other fans on ' OtheP setup notes-;` ' Outdoor tempereture=F Appiancf t Locatior CAZ pressure 1 ( BPI depressurization limit (Pa wrt outside) Measured net CAZ depressurization (Pa wn outside) t I t OK (less negative) i Caution (more negative) Spillage i` I BPI maximum hmrt (seconds Measured spillage duration (seconds Pass = duration not exceeding hind Draft pressure BPI limit (Pa wil CAZ jt Measured (Pa wit CAZ Pass = pressure more negative than Irma CO concentration In undiluted flue gas l BPI maximum limit (ppm % Measured CO (ppm I i Pass = CO level not exceeding hind 1 ( Caution = CO level 25 to 100 ppm �f ( Testing f notes � t ❑ JOK J[Uj Caution ❑ JOK ❑� Caution ❑ OK liffli Caution 60 60 60 ❑ IPass ❑ IFail ❑ jPass I ❑ Iall ❑ jPass 1 ❑ Fad ❑ IPass 1, ❑ IFail ❑ Pass , ❑ IFail I ❑' Pass_ _ _❑ Fad- 100 100 100 r ❑ Pass Pass ❑ Fad ❑ Pass __ ❑ Fad IMICaution U Caution MiCaution Residential Mechanical Design Submittal by V20140307 Page 5 35 i ram_ 9 ,9. System Controls Testing tech (initials) NG System Controls Operating Per Design Intent Local exhaust (all fans) ❑ 1 WA I [Z] Pass ❑ Fail Whole -house ventilation ❑ WA Q Pass ❑ Fail Sub -structural Floor exhaust WA ❑ Pass ❑ Fad Heating (all systems) ❑ WA Q Pass ❑ Fail Cooling (all systems) ❑ WA ❑� Pass ❑ I Fail Testing Notes 1 Signatures Technician #1 performing inspection and testing documented on this report (Approved Agency) 11 certify that the tests referenced above, in sections beating my initials, were performed in accordance with protocols specified by the City of Fort 611ins Budding Services Department, and that the reported results are accurate to the best of my knowledge I Name (print) Tale Company Signature and Date ? u mqs-ra,3'Y`N�IM3±{3�V�� JY4°'u°ah Y-Sr.Lhi Yri�4'Y�,' tlatrM o �+,.F v�=b� Neal Girard Energy Rater��� F ,.a��.,� s,- k Energy Logic, Inc '8%23/17 t_ d _ � Al y ' Technician k2 performing Inspection and testing documented on this report (Approved Agency) p,pI certify that the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the City of Fort Collins Budding Services Department, and that the reported results are accurate to the best of my knowledge Name (print) p.r � Title Company Signature and Date �4 ! .�� S 'l / m •' e44y Y Y^�ot",tc��.n.il asrr „�OT 6 Rai tJ/n 'y �#k *.— r� r`,�'C'�n "7±',�, "� a�, �.{« w � 7 - 4 w °' `w� ' aly�i.•.� ZS�'? �y�'�->/'/q/���Sj'�'�j/��a,��� �'y5"'red& �''� E �..• ���'�3 b+�'` J1p � � v,� � . E r� HVAC Contractor (City of Fort Collins license holder) I certify that I have reviewed this report and that the lest results are an accurate representation of the performance of the installed mechanical systems Name (print) Title Company USignature and Date V11AIS 55tt y� f 1 R Y 11 � _ n ] vA��tk�*R �R,,�,r�. �i�/.ay'... <c� �{ `�`v:M: ,M„♦.Y:nn�S���wyEn 1 Zvi f "Gr�i\/ L„�,y P Cmk• °w .w Me'+n u..� Fp r �i �L�♦b �iMTh&i��"b<x��Wi� eryt�'1 �u�M�M�'OYMIi6'ri :hiuu ` r Residential Mechanical Design Submittal V20140307 Page 6