HomeMy WebLinkAbout227 Osiander St - Disclosures/Blower Door Test - 09/06/2017(Dn e r g y L o g 1 C BUILDING LEAKAGE TEST
1
an a I ys Is. Ins I ht. answers.
Date of Test: 9/6/2017 Test File: 227 Multi Point Tectite
Customer: Erik Haagenson Technician: Neal Girard - EnergyLogic, Inc.
Project Number: 48414
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building -Leakage Curve:
4. Test Settings:
5. Accuracy Level
Building Address: 227 Osiander St.
Ft. Collins, CO 80524
651 CFM50 (+/- 0.8 %)
1.44 ACH50
35.8 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 22.0 (+/- 13.4 %)
Exponent (n) = 0.866 ( +/- 0.035 )
Correlation Coefficient = 0.99918
Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
38.0 CFM
0.08 ACH
9.5 CFM per person
Winter: 71.4 CFM Summer: 44.8 CFM
0.16 ACH 0.10 ACH
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate: 58.0 CFM
Base Rate: 58.0 CFM
QnergyLogic
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 9/6/2017 Test File: 227 Multi Point Tectite
Building Information
Volume
27066
Surface Area
Floor Area
2796
Height
20
# of Bedrooms
3
# of Occupants
4
Year of Construction
2017
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Location Climate Information
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
297
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
9.4 mph
Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
15 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
-
Micromanometer
Energy Conservatory
DG700
36002-7
11/15/2012
QneFgyLogic
_�r:..:.. ....... ,.._.,.
- BUILDING LEAKAGE TEST Page 3 of 4
Date of Test:9/6/2017 Test File: 227 Multi Point Tectite
Depressurization Test:
Environmental Data
Indoor Temperature(°F) Outdoor Temperature(°F)' Altitude(ft)
70.0 90.0 5000A �
Data Points
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) %Error Configuration
-1 0.0 n/a n/a
-70.0 -59.5 127.1 669 756 -0.0 Ring B
-65.6 -55.1 113.2 632 714 0.9 Ring B
-62.0 -51.5 98.3 589 666 -0.3 Ring B
-57.7 -47.2 84.3 546 617 -0.4 Ring B
-54.3 -43.8 74.4 513 580 -0.0 Ring B
-49.7 -39.2 61.2 466 527 -0.2 Ring B
-45.9 -35.4 50.2 422 478 -1.2 Ring B
-42.8 -32.3 44.8 399 451 1.3 Ring B
-11.0 n/a n/a
Time Averaging Period: 0
Deviations from Standard RESNET Multi-Point Test-Test Parameters
None
QnergyLogic
...�..:.. ........ .....
� BUILDING LEAKAGE TEST Page 4 of 4 � �=� ,.
Date of Test: 9/6/2017 Test File:227 Multi Point Tectite
Comments
Connection to:
Garage: NA
Mechanicals: NA
� .
1 �