HomeMy WebLinkAbout215 E Foothills Pkwy - Special Inspections/Field Verification - 09/19/20173 »olv1 Lawrence H. Finn & Associates, Inc. Hi 55 S. Elm Ave., Suite 220 — Eaton, CO 80615 Phone (970) 454-5351 — Fax (970) 454-5391 2389 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 9/19/17 PROJECT Xfinity Fort Collins 215 East Foothills Parkway Fort Collins, CO ***Final Report*** ARCHITECT Ware Malcomb 1600 Champa Street Denver, CO ENGINEER Thompson Engineering 1615 California Street Denver, CO CONTRACTOR Poudre Valley Air 2416 Donella Court Fort Collins, CO I""" Lawrence H. Finn & Associates, Inc. NiE, e8 2389 'Roof Top Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: RTU-02/SPP-01 Tested By: Duston West Date: 9/19/2017 Test Pi`essures >' . -� Pre Filter SP In -0.55 in. w.c. Pre Filter SP Out ANA in. w.c. Supply Fan SP In -0.72 in. w.c. Supply Fan SP Out 0.27 in. w.c. Cooling Coil SP In ANA in. w.c. Cooling Coil SP Out -0.72 in. w.c. Static Pressure.Proflle fl,r� rd -0.55 -0.72 0.27 RTU-02 Supply Outlet Summary System/Unit, = - Area Served Outlet Type . Size LxW /'_D AK Factor Maximum Design Prelim , . Reading Maximum ... Final, %Prelim Deviation. % Final' Deviation Outlet-01 See Print 1 24x24 300 392 293 131 98 Outlet-02 See Print 1 2424 300 380 291 127 97 Outlet-03 See Print 1 2424 300 402 301 134 100 Outlet-04 See Print 1 2424 300 423 286 141 95 Outlet-05 See Print 1 24x24 300 357 293 119 98 Outlet-06 See Print 1 24x24 1 300 1 399 299 133 1 100 Outlet-07 See Print 1 2424 300 454 297 151 99 Outlet-08 See Print 1 24x24 300 410 279 137 93 Totals: „ F e y� •._,; , „ _ 2400 321T ;x2338 —jr 8,4 m97 - L. H. Finn and Associates Final Report Page 7 of 14 Lawrence H. Finn & Associates, Inc. NIE' BIB 2389 Roof Top Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: RTU-03 Unit Data Unit Manufacturer York Unit Model Number ZYG04E4C1AA1B112A2 Unit Serial Number N1G7927739 Unit Discharge Vertical/Down RTU-03/Supply Fan Fan Type Forward Curve Fan Size 9" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Vertical/Down RTU-03/Filter Bank Filter Type Disposable Filter Quantity 2 Filter Size 16x25x2 :4Starter"Data RTU-03/Supply Fan Installed Thermal Internal �� •=-aTest Data Total CFM Design 1200 CFM Total CFM Actual 1294 CFM Outside Air CFM Design 240 CFM Outside Air CFM Actual 253 CFM Return Air CFM Design 960 CFM Return Air CFM Actual 1041 CFM RTU-03/Supply Fan Fan RPM Actual 1116 RPM Motor Volts 1 487 Volts Motor Volts 2 486 Volts Motor Volts 3 485 Volts Motor Amps 1 1.6 Amps Motor Amps 2 1.6 Amps Motor Amps 3 1.7 Amps Tested By: Duston West Date: 9/19/2017 Motor Data RTU-03/Supply Fan Motor Manufacturer Marathon Motor Frame 56Y Motor RPM 1725 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 5.2/2.6 Amps Motor Service Factor 1.15 Sheave Data - RTU-03/Suooly Fan Motor Sheave Make Browning Motor Sheave Model Adjustable Motor Sheave Diam. 4" in. Motor Sheave Bore 5/8 in. Motor Operating Diameter 3 1/4 in. Fan Sheave Make Power Drive Fan Sheave Model AK46 Fan Sheave Diam. 4 1/2 in. Fan Sheave Bore 3/4 in. Number of Belts 1 Belt Size A40 Sheave Center Line 15 1/2 in. Test Pressures CA Damper Pos Actual 20 % RA Damper Pas Actual 80 % Unit External SP Actual 0.73 in. we RTU-03/Supply Fan Fan TSP Actual 0.87 in. we L.H. Finn and Associates Final Report Page 8 of 14 �m^Y 1 Lawrence H. Finn & Associates, Inc. NitE 2389 Roof Top Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: RTU-03/SPP-01 Tested By: Duston West Date: 9/19/2017 Test Pressures Pre Filter SP In -0.49 in. w.c. Pre Filter SP Out ANA in. w.c. Supply Fan SP In -0.63 in. w.c. Supply Fan SP Out 0.24 in, w.c. Cooling Coil SP In ANA in. w.c. Cooling Coil SP Out -0.63 in. w.c. +? Y 5S- i J Ei W ,„ e a Static„pressure+Profile: - `T a. . 0.87 pp� RTU-03 Supply Outlet Summary System/Unit , '..Area Served Outlet Type s . r1 Size LxVll I ff AK Factor Maxlmum Desi' n` Prelim `=Readin 'Maximum "Final' %Prelim Deviailon %Final .Deviatio"n" Outlet-01 See Print 1 24x24 250 378 270 151 108 Outlet-02 See Print 1 24x24 150 204 158 136 105 Outlet-03 See Print 1 2424 250 306 276 122 110 Outlet-04 See Print 1 2424 100 91 107 91 107 Outlet-05 See Print 1 24x24 200 198 216 99 108 Outlet-06 See Print 1 24x24 100 102 107 102 107 Outlet-07 See Print 1 2424 75 109 79 145 105 Outlet-08 See Print 1 24x24 75 104 81 139 108 Totals: .,- I - 1 1200 1 11492.,_1-1'1, 1294. 1 124 108 L.H. Finn and Associates Final Report Page 9 of 14 Lawrence H. Finn & Associates, Inc. NEB gYB 2389 Fan Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: EF-01 Unit.Data Fan Manufacturer Twin City Fan Fan Model Number T200 Fan Type Forward Curve Fan Size 6" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 75 CFM Total CFM Actual 226 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 119 Volts Motor Amps 1 1.4 Amps SP In Actual 0.0 in. we SP Out Actual ANA in. we Total SP Actual NM in. we Log: Tested By: Duston West Date: 9/19/2017 Motor Data Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.8 Amps Sheave Data Motor Sheave Make Direct Drive =F-01 9/19/2017 Duston West Lowest Obtainable Airflow, unit is single speed direct drive, with no speed controller installed. =F-01 9/19/2017 Duston West Motor info taken from unit tag. L.H. Finn and Associates Final Report Page 10 of 14 Lawrence H. Finn & Associates, Inc. Fan Unit PROJECT: Xfinity Fort Collins LOCATION: Fort Collins, CO SYSTEM/UNIT: EF-02 Unit Data r Fan Manufacturer Twin City Fan Fan Model Number T100 Fan Type Forward Curve Fan Size 6" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data ' Total CFM Design 150 CFM Total CFM Actual 120 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 119 Volts Motor Amps 1 0.8 Amps SP In Actual 0.0 in. we SP Out Actual ANA in. we Total SP Actual NM in. we Log: DATE: 9/19/2017 CONTACT: Duston West AUTHOR: Joe Marshall Tested By: Duston West Date: 9/19/2017 NE B'IB 2389 Motv'r Data , rd Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.1 Amps Sheave Data Motor Sheave Make Direct Drive EF-02 9/19/2017 Duston West Maximum obtainable airflow unit is single speed direct drive. EF-02 9/19/2017 Duston West Motor info taken from unit tag. L.H. Finn and Associates Final Report Page 11 of 14 Inc. B Lawrence H. Finn & Associates, EY;; BIB 2389 Fan Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: TF-01 Unit Data . Fan Manufacturer Twin City Fan Fan Model Number T150 Fan Type Forward Curve Fan Size 6" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal f.StavtBr Date' "'4 .IA 9s [ Installed Thermal Internal Test Datav, Total CFM Design 100 CFM Total CFM Actual 106 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 119 Volts Motor Amps 1 0.7 Amps SP In Actual 0.0 in. we SP Out Actual ANA in. we Total SP Actual NM in. we Tested By: Duston West Date: 9/19/2017 Motor Data Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.3 Amps Sheave Data Motor Sheave Make Direct Drive Log: I TF-01 9/19/2017 Duston West Motor info taken from unit tag. L.H. Finn and Associates Final Report Page 12 of 14 ',AU [VoN: 9 WS 9C, T S NOT 19 02- E N Z—P Page 14 of 14 No Text No Text No Text No Text No Text Lawrence H. Finn & Associates, Tnc. ��� 55 S. Elm Ave, Suite 220-Eaton,CO 80615 ° Phone (970)454-5351 - Fax (970)454-5391 2389 ABBREVIATION REPORT Project: Xfinity Fort Collins S mbol Description Symbol Description A Airflow L/S NS Not Shown AF Air Foil NT No Information Ta ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceilin Diffuser SD Su I Diffuser CFM AirFlow Cubic Feet/Minute SNKL Snorkel DD Direct Drive SP Static Pressure Des Desi n SPD Static Pressure Dro DWDI Double Width Double Inlet SR Su I Re ister EF Exhaust Fan SWSI Sin le Width Sin le Inlet EG Exhaust Grille T Tem erature C ER Exhaust Re ister T Tem erature F ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Fre uenc Drive GPM Waterflow Gallons/Minute VS Variable S eed HC Heat Coil W Waterflow LIS HER Heat Exchan er HRC Heat Recove Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicabie NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Page 3 of 14 C�""; i � Lawrence H. Finn & Associates, Inc. NE�; B"�B 2389 Roof Top Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: RTU-01 Tested By: Duston West Date: 9/19/2017 _� .. ,_. �;r �� . . :�. .. , ,� _ ` Unit Data , °;":' ` Motor Data ° Unit Manufacturer � York � RTU-01/Suoolv Fan � � � �� �� W Unit Model Number ZYG07F4C1AA1B112A2 Motor Manufacturer Marathon Unit Serial Number N1G7918335 Motor Frame 56HZ Unit Discharge Vertical/Down Motor RPM 1725 RPM RTU-01/Suoolv Fan Motor Rated Volts 208-230/460 Volts Fan Type Forward Curve Motor Phase 3 Fan Size 12"ID Motor Hertz 60 Hz Fan Class 1 Motor FL Amps 9.2-9.6/4.8 Amps Fan Arrangement DWDI Motor Service Factor 1.15 Fan Discharge Vertical/Down , a ,�� � _ RTU-01/Filter Bank " , ` , ,a;, ,, ,;:•,,;'.��` Sheave Date » ��„r, „, �,': ,e, e . , ...__ . .> � ; � � Filter Type Disposable RTU-01/Suaaly Fan Filter Quantity 4 Motor Sheave Make Power Drive Filter Size 16x20x2 Motor Sheave Model VL40 Motor Sheave Diam. 3 3/4 in. �� ��.StaKerData,`� � Motor Sheave Bore 7/8 in. , . _� _� RTU-01/Sunulv Fan Motor Opereting Diameter 3 1/2 in. Installed Thermal Internal Fan Sheave Make Power Drive ,. . Fan Sheave Model AK74 Test Data Fan Sheave Diam. 7 1/2 in. Total CFM Design 2400 CFM Fan Sheave Bore 1 in. Total CFM Actual 2307 CFM Number of Belts � Outside Air CFM Design 504 CFM Belt Size A48 Ou[side Air CFM Actual 521 CFM Sheave Center Line 18 in. Return Air CFM Design 1896 CFM Return Air CFM Actual 1786 CFM �e���' ' �� ` �Teat Pressures�..�� " � ��� � ����.,d= "�,���. .; RTU-01/Suoaly Fan OA Damper Pos Actual 20% Fan RPM Actual 684 RPM RA Damper Pos Actual 80% Motor Volts 1 485 Volts Unit External SP Actual 0.70 in.wc Motor Volts 2 486 Volts RTU-01/Suoolv Fan Motor Volts 3 485 Volts Fan TSP Actual 0.80 in.wc Motor Amps 1 3.4 Amps Motor Amps 2 3.5 Amps Motor Amps 3 3.4 Amps L.H. Finn andAssociates Final Report Page 4 of 14 � � L�wt��nce H. Finn & Associates, Inc. N E� B�B 2389 Roof Top Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEMIUNIT: RTU-011SPP-01 Tested By: Duston West Date: 9/19/2017 Test Preseures °��:, . ' �'` Pre�Filter SP In -0 48 in.w.a � � Pre Filter SP Out ANA in.w.c. Supply Fan SP In -0.58 in.w.c. Supply Fan SP Out 022 in.w.c. Cooling Coil SP In ANA in.w.c. Cooling Coil SP Out -0.58 in.w.c. StatiaPressureProfile _; 4 . &C� � � t r`'� \! .(' ,r� f' \ �`�,,. ,` � � � ; ���� `� t�� ����-�-� * .� w --c, . f� _� . s� o . �� RTU-01 Supply Outlet Summary S stemlUmt � Area3e►ved, Out1eY+T e SizeLxWlp AKFactor M�9ximum � ��"Prelf�n rl 'Maximum `%Prelim' "'Io„Final'��. � ���.'%��_ � �p �� esi n � �� Readin Final ,, •iDeviatlon .Deviation; Outlet-01 See PriM �� 1 � 24x24 300 398 297 133 99 Outlet-02 See Print 1 24x24 300 397 291 132 97 Outlet-03 See Print 1 24x24 300 397 279 132 93 Outlet-04 See Print 1 24x24 300 421 283 140 94 Outlet-OS See Print 1 24x24 300 365 296 122 99 Outlet-06 See Print 1 24x24 300 360 286 120 95 Outlet-07 See Print 1 24x24 300 424 277 141 92 Outlet-08 See Print 1 24x24 300 389 298 130 99 Totalsi .,. ��.- ` . . __ � - � - ��2400 '� 3151 ,23Q7',.,-.` z�, 131.�, ' `rz96_ L.H. Finn and Associates Final Report Page 5 of 14 r-=°� � L�wrence H. Finn & Associ�tes, Inc. �'E: g'B 2389 Roof Top Unit PROJECT: Xfinity Fort Collins DATE: 9/19/2017 LOCATION: Fort Collins, CO CONTACT: Duston West AUTHOR: Joe Marshall SYSTEM/UNIT: RTU-02 Tested By: Duston West Date: 9/19/2017 Unit Data Motor Data . Unit Manufacturer York RTU-02/Suooly Fan Unit Model Number ZYG07F4C1AA16112A2 Motor Manufacturer Marathon Unit Serial Number N1G7918336 Motor Frame 56HZ Unit Discharge Vertical/Down Motor RPM 1725 RPM RTU-02/Suooly Fan Motor Rated Volts 208-230/460 Volts Fan Type Forward Curve Motor Phase 3 Fan Size 12"ID Motor Hertz 60 Hz Fan Class 1 Motor FL Amps 9.2-9.6/4.8 Amps Fan Arrangement DWDI Motor Service Factor 1.15 Fan Discharge Vertical/Down RTU-02IFilter Bank `4 �Sheave Data = Filter Type Disposable RTU-021Suuolv Fan Filter Quantity 4 Motor Sheave Make Power Drive Filter Size 16x20x2 Motor Sheave Model VL40 Motor Sheave Diam. 3 3/4 in. '9 � ``'. Starter iData Motor Sheave Bore 7/8 in. � A � _ - � , ,�� . : RTU-02/Suonlv Fan Motor Operating Diameter 3 1/2 in. Installed Thermal Internal Fan Sheave Make Power Drive Fan Sheave Model AK74 ��x,�������# ' ' "'�Test Date d�,����a Fan Sheave Diam. 7 1/2 in. Total CFM Design 2400 CFM Fan Sheave Bore 1 in. Total CFM Actual 2339 CFM Number of Belts � Outside Air CFM Design 480 CFM Belt Size A48 Outside Air CFM Actual 501 CFM Sheave Center Line 18 in. Return Air CFM Design 1920 CFM Return Air CFM Actual 1839 CFM Test Pressures RTU-02/Suooly Fan OA Damper Pos Actual 20% Fan RPM Actual 690 RPM RA Damper Pos Actual SO% Motor Volts 1 485 Volts Unit Extemal SP Actual 0.82 in.wc Motor Volts 2 486 Volts RTU-02/Suoolv Fan Motor Volts 3 485 Volts Fan TSP Actual 0.99 in.wc Motor Amps 1 3.7 Amps Motor Amps 2 3.8 Amps Motor Amps 3 3.6 Amps L.H. Finn andAssociates Final Report Page 6 of 14