RE: Variance Request regarding use of Two-hour Rated Fire Walls with NFPA 13R fire sprinkler systems
Bucking Horse Apartments Buildings, A, A2 & B
Fort Collins, Colorado
Project No.1529
Dear Mike
Based on our meeting on June 12, 2017, the intent of this letter is to request a variance of the following Local Amendment
that allows the use of two-hour rated Fire Wall(s) in multi -family R-2 apartment buildings with a NFPA 13R sprinkler
systems to be compartmentalized into areas of 6 units with or less in hue of using a full NFPA 13 sprinkler system The
variance request is as follows and would apply to type A, A2 and B apartment buildings previously submitted and
approved for building permits
1 We are requesting approval of a two-hour fire rating that extends from the foundation to the underside of roof
deck with the use of a two-hour rated double wall system between the units as well as between the units and
breezeways While these double two-hour rated walls do not meet the "Structural Stability" aspect of Fire Walls,
they do provide two hours of protection against fire and exceed the 2012 IBC code without the local NFPA 13
Oamendment that allows for only one -hour rated fire partitions between units with use of a NFPA 13R fire
sprinkler system At the attic spaces, the two-hour fire rating is maintained with the use of two gable end trusses
with two layers of 5/8" type 'X' on each side (four layers total) in conjunction with 4' width of fire resistive
plywood on each side of the gable end roof trusses In conditions where there is an offset between the two-
hour rated gable end trusses and rated walls, a two-hour rated horizontal ceding assembly is being used to
maintain the rating In conditions where the roof structure has over framing, the two-hour fire rated gable end
trusses and 4' wide fire treated plywood will terminate at the primary roof sheathing/structure and will not
extend up to the bottom of over framing and associated sheathing
2 We are requesting the use of 20-minute rated entry doors where located within the two-hour fire rating as this
G is the door rating that is required with the 2012 IBC without the local NFPA 13 amendment where a 20-minute
Y!— door is required at 1 hour rated fire partitions and corridors in R-2 Apartment Buildings with NFPA 13R sprinkler
systems
3 We are requesting that exterior walls are not required to be rated per section 706 5 1 where two -rated Fire
J, Walls intersect exterior walls since this is not a requirement of the 2012 IBC without the local NFPA 13
Amendment
Please feel free to contact me if you have any questions or comments regarding this Variance Request and thank you for
your consideration in this matter