HomeMy WebLinkAbout1229 Peony Way - Disclosures/Blower Door Test - 09/19/2016BUILDING LEAKAGE TEST
Date of Test: 9/19/2016
Customer: RAH
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve
Test File: 1229 Peony way
Technician: Michael Broussard
Project Number:
Building Address: 1229 Peony way
Fort Collins, CO
1560 CFM50 (+/-1.3 %)
2.97 ACH50
85.8 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 113.9 (+/- 38.8 %)
Exponent (n) = 0.669 ( +/- 0.099 )
Correlation Coefficient = 0.99883
4. Test Settings: Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates .
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 9/19/2016 Test File: 1229 Peony way
Building Information Location Climate Information
Volume 31519 Ventilation Weather Factor 0.87
SurfaceArea Energy Climate Factor 17.00
FloorArea � Heating Degree Days 6128
Height Cooling Degree Days 297
#of Bedrooms Design Winter Wind Speed 7.3 mph
#of Occupants Design Summer Wind Speed 9.4 mph
Year of Construction Design Winter Temp Diff 73 deg F
Wind Shield M Design Summer Temp Diff 15 deg F
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency%
Cooling Fuel Cost
Cooling SEER
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (110V) -
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 9/19/2016 Test File: 1229 Peony way
Depressurization Test:
Environmental Data
Indoor Temperature(°F) Outdoor Temperature (°F) Altitude(ft)
72.0 68.0 5500.0
Data Points
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-0.3 n/a n/a
-60.1 -59.9 91.2 1716 1768 0.5 Ring A
-54.4 -54.2 78.2 1593 1641 -0.3 Ring A
-49.6 -49.3 68.5 1493 1538 -0.6 Ring A
-41.8 -41.6 55.2 1343 1384 0.4 Ring A
-0.2 n/a n/a
Time Averaging Period: 0
Deviations from Standard RESNET Multi-Point Test-Test Parameters -
• - Fewer than 8 data points were taken.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 9/19/2016 Test File: 1229 Peony way
Comments
-48.9pascals to garage=Passed .