619 S College Ave - Special Inspections/Field Verification - 09/26/2016 (2)
Lawrence H. Finn & Associates, Inc. Ni 55 S. Elm Ave., Suite 220 — Eaton, CO 80615 ® Phone (970) 454-5351— Fax (970) 454-5391 2389 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 9/26/16 PROJECT Music District 2°d Floor TenantImprovements 619` 9 S. College Avenue Fort Collins, CO ARCHITECT Davis Davis Architects 141 S. College Avenue, Suite 102 Fort Collins, CO ENGINEER The Ballard Group, Inc. 4730 S. College Ave., Suite 203 Fort Collins, CO CONTRACTOR Poudre Valley Air 2416 Donella Ct. Fort Collins, CO Lawrence H. Finn & Associates, Inc. N- 2389 Roof Top Unit PROJECT: Music District 2nd Floor Tenant Improvements DATE: 9/26/2016 LOCATION: Fort Collins, CO CONTACT: Josh Behrendsen SYSTEM/UNIT: (E) RTU-04/(E) VAV-4-01 Unit Data Manufacturer Trane Model Number VCEF VAV Address 105 Box Inlet Size 20 In. K Factor - 1 1.02 (E) RTU-04/(E) VAV-4-01 Supply Outlet Summary Tested By: Josh Behrendsen Date: 9/22/2016 Term Box Test Data Max Des. CFM 2600 CFM Max Act. CFM 2625 CFM Min Des. CFM 1050 CFM Min Act. CFM 1061 CFM Heat Des. CFM 1470 CFM Heat Act. CFM 1492 CFM System/Unit Area Served Outlet Type Size LxW / D AKFactor Maximum Desi n Prelim Readin Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Stairs (E) SDA 48x2 Slot 350 286 356 82 102 Outlet-02 Stairs (E) SDA 48x2 Slot 350 287 354 82 101 Outlet-03 Hall (E) SDA 48x2 Slot 325 306 331 94 102 Outlet-04 Hall (E) SDA 48x2 Slot 325 286 322 88 99 Outlet-05 Hall (E) SDA 48x2 Slot 325 198 309 61 95 Outlet-06 Hall (E) SDA 48x2 Slot 325 253 339 78 104 Outlet-07 Hall (E) CD-1 24x24 300 305 303 102 101 Outlet-08 Hall (E) CD-1 24x24 300 260 311 87 104 Totals: - - 2600 2181 2625 84 101 SYSTEM/UNIT: (E) RTU-04/VAV-4-02 Unit Data Manufacturer Trane Model Number VCEF VAV Address 106 Box Inlet Size 20 In. K Factor - 1 1.26 (E) RTU-041VAV-4-02 Supply Outlet Summary Tested By: Josh Behrendsen Date: 9/22/2016 Term Box Test Data Max Des. CFM 2415 CFM Max Act. CFM 2425 CFM Min Des. CFM 970 CFM Min Act. CFM 977 CFM Heat Des. CFM 1450 CFM Heat Act. CFM 1445 CFM SystemiUnit Area Served Outlet Type Size LxW / D AK Factor Maximum Prelim Maximum % Prelim % Final Desi n Reading Final Deviation Deviation Outlet-01 S Phone Room CD-1 24x24 50 41 49 82 98 Outlet-02 N Phone Room CD-1 24x24 50 46 51 92 102 Outlet-03 East Tenant CD-2 24" RD 365 237 358 65 98 Space Outlet-04 East Tenant CD-2 20" RD 245 107 253 44 103 Space Outlet-05 East Tenant CD-2 24" RD 365 554 362 152 99 Space Outlet-06 East Tenant CD-2 20" RD 245 178 244 73 100 Space Outlet-07 East Tenant CD-2 24" RD 365 705 373 193 102 Space Outlet-08 East Tenant CD-2 24" RD 365 398 359 109 98 S ace Outlet-09 East Tenant CD-2 24" RD 365 418 376 115 103 S ace Totals: 2415' 2684 2425 111 100 L.H. Finn and Associates Final Report Panes 8 of 12 Lawrence H. Finn & Associates, Inc. � , 1B 2389 Roof Top Unit PROJECT: Music District 2nd Floor Tenant Improvements DATE: 9/26/2016 LOCATION: Fort Collins, CO CONTACT: Josh Behrendsen SYSTEM/UNIT: (E) RTU-04NAV-4-03 Unit Data Manufacturer Trane Model Number VCEF VAV Address 107 Box Inlet Size 12 in. K Factor - 1 1.5 (E) RTU-04NAV-4-03 Supply Outlet Summary Tested By: Josh Behrendsen Date: 9/22/2016 Term Box Test Data Max Des. CFM 360 CFM Max Act. CFM 367 CFM Min Des. CFM 145 CFM Min Act. CFM 148 CFM Heat Des. CFM 240 CFM Heat Act. CFM 244 CFM System/Unit Area Served Outlet Type Size LxW I D AK Factor Maximum Desi' n Prelim Readin Maximum Final %Prelim Deviation °� Final Deviation Outlet-01 Office 7 CD-1 24x24 180 242 184 134 102 Outlet-02 Office 6 CD-1 24x24 180 240 183 133 102 Totals: - 360 482 367 134 102 L.H. Finn and Associates Final Report Panes 9 of 12 GENERAL LEGEND a=sc, saea xxnsnev ____©____ 6 --+ ... + HVAC LEGEND s.aw ucxxwucx HVAC S[CIFNU OF MRAWN 4M Y® mre�eao w.unawu. a.rvw WAC LEGEND sxM o[soivnrx p W �7 � .. ^a+a+ •v,u roa wrirRmA.wr zrwn ® C:ID v✓ir uuu we g�] [G3 �] au[.rvmw ca Ll -I DRAWING INDEX ou+m ne®1 WW[6VOAb FVaC OENERFL NilFS: .ow�w mwi'�w,uv..wonwn v-s,.o.. v.. W IINPINf. f.[N[R[I NOTY vae.m VECHANICAI OENEPAE NOTES ��atie..aal.. ✓u. wr-u.. w✓. u...0 �w NVgC IN�IIAiION NOIEc' I U_ R G7 0 U Fn�--a cJ L uxWa GEEP�/Lrgif] M-0 Page 10 of 12 Lawrence H. Finn & Associates, Inc. Ni 55 S. Elm Ave, Suite 220 — Eaton, CO 80615 2389 Phone (970) 454-5351— Fax (970) 454-5391 PROJECT: Music District 2na Floor Tenant Improvements ADDRESS: 619 S. College Avenue Fort Collins, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB "Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems" and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:9/26/16 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB "Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems" and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:9/26/16 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE:0,."Zf ,< DATE: 9/26/16 CERTIFICATION EXPIRATION DATE: 3/31/2018 Table of Contents Instrument Calibration Report .................................................................................................................................. 2 AbbreviationReport ................................................................................................................................................. 3 RoofTop Unit.......................................................................................................................................................... 4 Prints...................................................................................................................................................................... 10 Panes 1 of 12 Lawrence H. Finn & Associates, Inc. �- 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 N400 Phone (970) 454-5351 - Fax (970) 454-5391 2389 INSTRUMENT CALIBRATION REPORT Proiect: Music District - 2nd Floor Tenant Improvements Manufacturer Model Serial Application Cal. Date Alnor HM-680 70552109 H dronic Press. & Diff. Press. 1/16/2014 Alnor HM-680 70750150 H dronic Press. & Diff. Press. 12/14/2015 Alnor HM-680 70838501 H dronic Press. & Diff. Press. 11/30/2015 Alnor HM-680 71021246 H dronic Press. & Diff. Press. 4/5/2016 Alnor HM-680 71043011 H dronic Press. & Diff. Press. 6/10/2015 Alnor HM-680 91139097 H dronic Press. & Diff. Press. 4/10/2015 Cooper SH66A 92711016 Temperature 4/10/2015 Extech 461895 Q394479 Rotation Measurement 10/12/2015 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 3/8/2016 Extech 461895 Q331990 Rotation Measurement 11/4/2014 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 4/8/2015 Extech 461895 Q590099 Rotation Measurement 10/12/2015 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 11/5/2015 Fluke 336 97110539R Electrical Measurement 4/5/2016 Fluke 336 97110538R Electrical Measurement 9/29/2015 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 335 12990071 Electrical Measurement 3/4/2016 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 4/8/2015 Fluke 374 20030354 Electrical Measurement 10/23/2015 Shortrid a ADM-860C M05789 Digital Manometer 11/25/2015 Shortrid a ADM-860C M06821 Digital Manometer 10/12/2015 Shortrid a ADM-860C M07352 Digital Manometer 6/6/2016 Shortrid a ADM-860C M09123 Digital Manometer 4/18/2016 Shortrid a ADM-860C M09347 Digital Manometer 9/26/2015 Shortrid a ADM-860C M10144 Digital Manometer 11/18/2014 Shortrid a ADM-860C M10371 Digital Manometer 11/5/2015 Shortrid a ADM-860C M11448 Digital Manometer 4/15/2016 Shortrid a HDM-300 W02060 H dronic Press. & Diff. Press. 10/5/2015 Shortrid a HDM-250 W09198 H dronic Press. & Diff. Press. 10/12/2015 Shortrid a HDM-250 W98020 H dronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Panes 2 of 12 Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 ® Phone (970) 454-5351 - Fax (970) 454-5391 2389 ABBREVIATION REPORT PrniPrt- Mnsir. District - 2nd Floor Tenant Improvements Symbol Description Symbol -T-Description A Airflow US NS Not Shown AF Air Foil NT No Information Tag ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceiling Diffuser SD Supply Diffuser CFM Airflow Cubic Feet / Minute SNKL Snorkel DID Direct Drive SP Static Pressure Des Design SPD Static Pressure Drop DWDI Double Width Double Inlet SR Supply Register EF Exhaust Fan SWSI Single Width Single Inlet EG Exhaust Grille T Temperature C ER Exhaust Register T Temperature F ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Frequency Drive GPM Waterflow Gallons / Minute VS Variable Speed HC Heat Coil W Waterflow L/S HER Heat Exchanger HRC Heat Recovery Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Panes 3 of 12 Lawrence H. Finn &Associates, Inc. NIE It 2389 Roof Top Unit PROJECT: Music District 2nd Floor Tenant Improvements DATE: 9/26/2016 LOCATION: Fort Collins, CO CONTACT: Josh Behrendsen SYSTEM/UNIT: (E) RTU-02 Unit Data Unit Manufacturer Trane Unit Model Number YHC102F3RZA09CED1A1A6 Unit Serial Number 155110522L Unit Discharge Vertical/Down (E) RTU-021Filter Bank Filter Manufacturer Airguard Filter Type Pleated Filter Quantity 4 Filter Size 20x25x2 (El RTU-021Sunply Fan Fan Type ANA Starter.Data (E) RTU-021Supply Fan Installed Thermal VFD Test Data Total CFM Design 3655 CFM Total CFM Actual 3689 CFM Outside Air CFM Design 680 CFM Outside Air CFM Actual 687 CFM Return Air CFM Design 2985 CFM Return Air CFM Actual 3002 CFM (E) RTU-02/Supply Fan Fan RPM Actual 7.3 Volts DC RPM Motor Volts 1 209 Volts Motor Volts 2 210 Volts Motor Volts 3 209 Volts Motor Amps 1 4.3 Amps Motor Amps 2 4.5 Amps Motor Amps 3 4.7 Amps Duct SP Set Point 1.0 in. we Tested By: Josh Behrendsen Date: 9/23/2016 Motor Data (E) RTU-02/Supply Fan Motor Manufacturer ANA Motor HP 3.8 HP Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.5 Amps Sheave Data (E) RTU-02/Supply Fan Motor Sheave Make Direct Drive Test Pressures Fan SP In Actual -0.7 in. we Fan SP Out Actual 1.0 in. we External SP In Actual -0.40 in. we External SP Out Actual 1.0 in. we OA Damper Pos Actual 23 % RA Damper Pos Actual 77 % Unit External SP Actual 1.7 in. we Filter/Coil SP In -0.4 in. we Filter/Coil SP Out -0.7 in. we Log: 9/23/2016 Keith Finn Motor information taken from unit tag. L.H. Finn and Associates Final Report Panes 4 of 12 Lawrence H. Finn & Associates, Inc. �jlB 2389 Roof Top Unit PROJECT: Music District 2nd Floor Tenant Improvements DATE: 9/26/2016 LOCATION: Fort Collins, CO CONTACT: Josh Behrendsen SYSTEM/UNIT: (E) RTU-02NAV-2-01 Unit Data Manufacturer Trane Model Number VCEF VAV Address 108 Box Inlet Size 8 In. K Factor - 1 1.41 (E) RTU-02NAV-2-01 Supply Outlet Summary Tested By: Josh Behrendsen Date: 9/22/2016 Term Box Test Data Max Des. CFM 740 CFM Max Act. CFM 720 CFM Min Des. CFM 300 CFM Min Act. CFM 287 CFM Heat Des. CFM 445 CFM Heat Act. CFM 439 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Readina Maximum Final %Prelim Deviation % Final Deviation Outlet-01 Office 5 CD-1 24x24 125 220 126 176 101 Outlet-02 Office 4 CD-1 24x24 235 326 223 139 95 Outlet-03 Office 3 CD-1 24x24 136 133 131 99 97 Outlet-04 Office 3 CD-1 24x24 135 138 135 102 100 Outlet-05 Office 2 CD-1 24x24 110 166 105 151 95 Totals: 740 983 720 133 97 SYSTEM/UNIT: (E) RTU-02NAV-2-02 Unit Data Manufacturer Trane Model Number VCEF VAV Address 109 Box Inlet Size 14 In. K Factor - 1 1.31 (E) RTU-021VAV-2-02 Supply Outlet Summary Tested By: Josh Behrendsen Date: 9/22/2016 Term Box Test Data Max Des. CFM 2000 CFM Max Act. CFM 1962 CFM Min Des. CFM 800 CFM Min Act. CFM 794 CFM Heat Des. CFM 1200 CFM Heat Act. CFM 1188 CFM System/Unit Area Served Outlet Type Size lxW / D AK Factor. Maximum Prelim Maximum ;"/u Prelim % Final Design Readina Final Deviation Deviation Outlet-01 West Tenant CD-2 24" RD 495 457 491 92 99 Space Outlet-02 West Tenant CD-2 24" RD 490 516 473 105 97 Space Outlet-03 West Tenant CD-2 24" RD 490 556 479 113 98 Space Outlet-04 West Tenant CD-2 14" RD 175 192 168 110 96 Space Outlet-05 West Tenant CD-2 14" RD 175 145 174 83 99 Space Outlet-06 West Tenant CD-2 14" RD 175 163 177 93 101 Space Totals. - 2000 2029 1962 101 98 L.H. Finn and Associates Final Report Pnnn5nf12 Lawrence H. Finn & Associates, Inc. 23$9 Roof Top Unit PROJECT: Music District 2nd Floor Tenant Improvements DATE: 9/26/2016 LOCATION: Fort Collins, CO CONTACT: Josh Behrendsen SYSTEM/UNIT: (E) RTU-02NAV-2-03 Unit Data Manufacturer Trane Model Number VCEF VAV Address 110 Box Inlet Size 10 In. K Factor - 1 1.32 (E) RTU-02NAV-2-03 Supply Outlet Summary Tested By: Josh Behrendsen Date: 9/22/2016 Term Box Test Data Max Des. CFM 915 CFM Max Act. CFM 921 CFM Min Des. CFM 370 CFM Min Act. CFM 373 CFM Heat Des. CFM 550 CFM Heat Act. CFM 558 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Office 1 CD-1 24x24 285 346 281 121 99 Outlet-02 Office 1 CD-1 24x24 285 358 292 126 102 Outlet-03 West Tenant Space CD-2 20" RD 345 493 348 143 101 Totals: 915 1197 921 131 101 L.H. Finn and Associates Final Report Pana6inf19 iB Lawrence H. Finn & .Associates, Inc. ' 2389 Roof Top Unit PROJECT: Music District 2nd Floor Tenant Improvements DATE: 9/26/2016 LOCATION: Fort Collins, CO CONTACT: Josh Behrendsen SYSTEM/UNIT: (E) RTU-04 Unit Data Unit Manufacturer Trane Unit Model Number YHD150G3RVA2ECM Unit Serial Number 155010650D Unit Discharge Vertical/Down u RTU-04/Filter Bank Filter Manufacturer Airguard Filter Type Pleated Filter Quantity 8 Filter Size 20x2Ox2 (E) RTU-041Suvply Fan Fan Type Forward Curve Fan Size 16"ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal Starter Data (E) RTU-04/Supply Fan Installed Thermal VFD Test Data Total CFM Design 5375 CFM Total CFM Actual 5318 CFM Outside Air CFM Design 720 CFM Outside Air CFM Actual 724 CFM Return Air CFM Design 4655 CFM Return Air CFM Actual 4594 CFM (E) RTU-041Supply Fan Fan RPM Actual 792 RPM Motor Volts 1 210 Volts Motor Volts 2 211 Volts Motor Volts 3 211 Volts Motor Amps 1 11.0 Amps Motor Amps 2 10.9 Amps Motor Amps 3 11.2 Amps VFD Speed 60.0 HZ Duct SP Set Point 1.25 in. we Tested By: Josh Behrendsen Date: 9/23/2016 Motor Data Motor Manufacturer Marathon Motor Frame 56HZ Motor HP 5 HP Motor RPM 3450 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 13.4-12.6/6.3 Amps Motor Service Factor 1.15 Sheave Data (E) RTU-04/Supply Fan Motor Sheave Make Browning Motor Sheave Model Adjustable Motor Sheave Diam. 3 3/4 in. Motor Sheave Bore 7/8 in. Motor Operating Diameter 3 3/4 in. Fan Sheave Make Browning Fan Sheave Model BX14 Fan Sheave Diam. 14 in. Fan Sheave Bare 1 3/16 in. Number of Belts 1 Belt Size BX71 Sheave Center Line 22 114 in. Test Pressures Fan SP In Actual -0.45 in. we Fan SP Out Actual 1.7 in. we External SP In Actual -0.40 in. we External SP Out Actual 1.70 in. we OA Damper Pas Actual 19 % RA Damper Pos Actual 81 % Unit External SP Actual 2.10 in. we Filter/Coil SP In -0.40 in. we Filter/Coil SP Out -0.50 in. we L.H. Finn and Associates Final Report Pane 7 of 12