HomeMy WebLinkAbout3339 W Elizabeth St - Disclosures/Blower Door Test - 06/09/2016BUILDING LEAKAGE TEST Date of Test: 6/9/16 Customer: Richmond American CO Test Results 1. Airflow at 50 Pascals: (50 Pa = 0.2 w.c.) 2. Leakage Areas: 3. Building Leakage Curve: Test File: 3339 W Elizabeth st Technician: Michael Broussard Project Number: Building Address: 3339 W Elizabeth st Fort Collins, CO 1763 CFM50 (+/- 7.8 %) 3.00 ACH50 185.9 in2 (+/- 29.4 %) Canadian EgLA @ 10 Pa 100.2 in2 (+/- 49.2 %) LBL ELA @ 4 Pa Flow Coefficient (C) = 146.1 ( +/- 79.3 %) Exponent (n) = 0.637 ( +/- 0.218 ) Correlation Coefficient = 0.82507 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 6/9/16 Test File: 3339 W Elizabeth st Building Information Volume 36232 Surface Area FloorArea Height # of Bedrooms # of Occupants Year of Construction Wind Shield Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Location Climate Information Ventilation Weather Factor j 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F I.Pes�n Summer Temp Diff 15 deg F Equipment Information Type i Manufacturer Model Serial Number Custom Calibration Date! ..... . ..... Fan Tn-Energy Conservatory Model 3(110V) BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 6/9/16 Test File: 3339 W Elizabeth st Depressurization Test: Indoor Temperature (OF) i 82.0 Data Points Environmental Data Outdoor Temperature (OF) 42.0 Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration 0.9 n/a n/a -49.1 48.4 97.7 1776 1709 -1.1 Ring A -45.0 44.4 82.3 1633 1571 -3.9 Ring A -39.0 -38.4 67.5 1482 1426 -4.3 Ring A -33.7 -33.0 87.0 1678 1614 19.2 Ring A -29.2 -28.5 39.9 1146 1103 -10.6 Ring A -24.2 -23.6 31.5 1022 983 -10.0 Ring A -2.2 n/a n/a Deviations from Standard CGSB - Test Parameters - Correlation coefficient (0.825) outside of acceptable limits. - % Error for one or more of the data test points is greater than 6%. - Test data was not collected at all 8 recommended target building pressures. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 6/9/16 Test File: 3339 W Elizabeth st Comments -47.6 pascals to garage=passed