HomeMy WebLinkAbout2720 Council Tree Ave - Special Inspections/Field Verification - 06/01/2016El
FORT COLLINUMIDWEST INC.
3818 PLATTE CT. FORT COLLINS, CO. 80526
PHONE (970) 223-5421 FAX (970) 225-2814
TESTING, ADJUSTING & BALANCING OF H.V.A.C. & HYDRONIC SYSTEMS
GENERAL INFORMATION
PROJECT
LOCATION .
ARCHITECT
MECHANICAL ENGINEER
MECHANICAL CONTRACTOR
BALANCING TECHNICIAN
DATE
INSTRUMENTS USED
VELGRID
FLOW HOOD
ANEMOMETER
SPEED INDICATOR
AMMETER
VOLTMETER
POWER HARMONICS ANALYZER
DIGITAL MICROMANOMETER
PRESSURE GAGE
PRESSURE GAGE -DIFFERENTIAL
ULTRASONIC FLOW METER
THERMOMETERS
IAQ METER CO2 & CO
ii'ko
HIMALAYAN BISTRO
FRONT RANGE VILLAGE, FORT COLLINS, CO.
WILLIAM C. HARRISON
JUNE 2016
SHORTRIDGE AIRDATA MULTIMETER
SHORTRIDGE AIRDATA MULTIMETER
SHIMPO DIGITAL TACHOMETER DT205B
FLUKE 36 TRUE RMS
FLUKE 36 TRUE RMS
SHORTRIDGE AIRDATA MULTIMETER
PROJECT ALTITUDE 5000'
SHORTRIDGE BAROMETRIC CORRECTION IS AUTOMATIC.
WILLIAM C. HARRISON IS A MEMBER OF THE ASSOCIATION OF ENERGY ENGINEERS,
AND IS A CERTIFIED TESTING, ADJUSTING AND BALANCING PROFESSIONAL.
i:. ... ..:. x.:. +.,� � .: .W ., .. ., of .-p.ve. }:Y:•�. 'hi �"4 �i.G''-:. �:y.�n ♦ r.�.�. �.rr�.r::��..ri�'
__. '.•.l•. •r- _.-.. ......, _.,� +.)..'s _.._.. •1.'R ..: _.--._"a_r.ri �.- •2.v.: _.-. �,:,.m' _-.. 'L:.v:c y,- �>-\.s __-_ .,',i.y'�_-_-. .�.,e �_. �ls�"�_"`�. �. ._�, __,_� ..�: ._.�..hFs _—_ ...... ___. :\
"7
•fY
$uGARMN coAsutTr*0
certifies that
William C Harrison
has compteted the prescr'bed stavwdards for certi f�cattov+. Lw the fvtol of
Tesem@-Adjust4wg--aLQ VLr,' @ of HvAc systems awd is herebd gramed the tf�tLe of
CERTIFIED TESTING -ADJUSTING -BALANCING PROFESSIONAL
:.;1S; Mt,ff,
CTABO
A Standard of Professional Achievement
Valid for Life
FORT COLLINS/MIDWEST, INC.
RECAP SHEET
PROJECT HIMALAYAN BISTRO
OPENING TYPE
SUPPLY
FCU-1
SUPPLY
FCU-2
TOTAL
SUPPLY
MAU-1
SUPPLY
FCU-1 MIN. O.S.A.
SUPPLY
FCU-2 MIN. O.S.A.
TOTAL O.S.A.
EXHAUST
KEF-1
EXHAUST
KEF-2
EXHAUST
KETTLE FAN
EXHAUST
MAIN BUILDING
TOTAL
REQ'D
CFM
1995
2000
3995
4990
475
475
5940
2000
2000
700
300
5000
FINAL REMARKS
CFM
1960
1920
3880
4930
450
495
5875
2154
2181
630 0 i
301
5266
PAGE 2
FORT COLLINS/MIDWEST, INC.
EQUIPMENT DATA
PROJECT HIMALAYAN BISTRO
(A) FAN UNIT #
FCU-1
MAKE
CARRIER
MODEL #
39SHK05-6G-19E
SERIAL #
201 OR33954
RATING
2000 CFM @ 0.50" ESP
(B) MOTOR
MARATHON
TYPE
NOT GIVEN
HORSEPOWER
1
MEAS. VOLTS (UL)
487/488/486
MEAS. VOLTS (L/G)
281/281/280
INITIAL AMPS
FINAL AMPS
1.3/1.4/1.4
(C) STARTER NONE
EXIST. THERMALS
REQ'D. THERMALS
REMARKS BUILT IN OVERLOAD PROTECTION
(D) SHEAVES
RATED PF/EFF
NOT GIVEN
RATED SPEED
1725
RATED VOLTS
208-230/460
RATED AMPS
3.6-3.8/1.9
PHASE
3
SERVICE FACTOR
1.15
FRAME
56
SIZE
EXIST AMP RATING
REQ'D AMP RATING
DRIVEN
AK64 H
BORE SIZE
3/4"
DRIVER
1VL40
BORE SIZE
5/8"
DRIVEN CHANGE
BELTS/SIZE
4L460
DRIVER CHANGE
BELT CHANGE
A40
INITIAL RPM
738
FINAL RPM
738
(E) STATIC PRESSURE IN INCHES
FILTER
IN -
0.016 OUT
NO ACC.
DROP
HEAT COIL
IN
DROP
COOL COIL
IN
NO ACC. OUT -
0.339
DROP 0.323
FAN
IN -
0.339 OUT
0.718
RISE 1.057
(F) MINIMUM O.S.A.
REQ'D
0.545 SQ. FT. X
872
FPM = 475
CFM
FINAL
0.545 SQ. FT. X
826
FPM = 450
CFM
PAGE 3
FORT COLLINS/MIDWEST, INC.
EQUIPMENT DATA
PROJECT
HIMALAYAN BISTRO
(A) FAN UNIT #
FCU-2
MAKE
CARRIER
MODEL #
39SHK05-6G-16E
SERIAL #
201 OR33955
RATING
2000 CFM @ 0.50" ESP
(B) MOTOR
MARATHON
RATED PF/EFF
NOT GIVEN
TYPE
NOT GIVEN
RATED SPEED
1725
HORSEPOWER
1
RATED VOLTS
208-230/460
MEAS. VOLTS (L/L)
487/488/485
RATED AMPS
3.6-3.8/1.9
MEAS. VOLTS (L/G)
281/281/281
PHASE
3
INITIAL AMPS
SERVICE FACTOR
1.15
FINAL AMPS
1.4/1.4/1.4
FRAME
56
(C) STARTER
NONE
SIZE
EXIST. THERMALS
EXIST AMP RATING
REQ'D. THERMALS
REQ'D AMP RATING
REMARKS
BUILT IN OVERLOAD PROTECTION
(D) SHEAVES
DRIVEN AK64 H
BORE SIZE
3/4"
DRIVER 1VL44
BORE SIZE
5/8"
DRIVEN CHANGE
BELTS/SIZE
41-460
DRIVER CHANGE
BELT CHANGE
AX42
INITIAL RPM 1000
FINAL RPM
807
(E) STATIC PRESSURE IN INCHES
FILTER
IN -
0.036 OUT
NO ACC.
DROP
HEAT COIL
IN
0
DROP
COOL COIL
IN
NO ACC. OUT -
0.423
DROP
0.387
FAN
IN -
0.423 OUT
0.202
RISE
0.625
(F) MINIMUM O.S.A.
REQ'D
0.545 SQ. FT. X
872
FPM =
475 CFM
FINAL
0.545 SQ. FT. X
908
FPM =
495 CFM
PAGE 5
FORT COLLINSIMIDWEST, INC.
EQUIPMENT DATA
PROJECT HIMALAYAN BISTRO
(A) FAN UNIT #
MUA-1
MAKE
CAPTIVE AIR
MODEL #
A4-E1000-920
SERIAL #
NOT GIVEN
RATING
6000 CFM @ 0.750" W.C.
(B) MOTOR
WEG
TYPE
NOT GIVEN
HORSEPOWER
3.0
MEAS. VOLTS (UL)
484/485/487
MEAS. VOLTS (UG)
280/278/280
INITIAL AMPS
5.3/5.3/5.4
FINAL AMPS
5.3/5.3/5.4
(C) STARTER ALLEN BRADLEY
EXIST. THERMALS 4.5-6.3
REQ'D. THERMALS
REMARKS
(D) SHEAVES
RATED PF/EFF
82.5/0.72
RATED SPEED
1730
RATED VOLTS
208-230/460
RATED AMPS
8.70-9.50/4.75
PHASE
3
SERVICE FACTOR
1.15
FRAME
E56
SIZE 193-K
EXIST AMP RATING 4.75
REQ'D AMP RATING
DRIVEN
2BK 90 (H)
BORE SIZE
HX 1 7/16"
DRIVER
2VP42
BORE SIZE
7/8"
DRIVEN CHANGE
BELTS/SIZE
BX80X2
DRIVER CHANGE
BELT CHANGE
INITIAL RPM
603
FINAL RPM
603
(E) STATIC PRESSURE IN INCHES
FILTER NONE
HEAT ELEMENT
IN - 0.385 OUT - 0.612
DROP 0.227
COOL MEDIA
IN - 0.027 OUT - 0.385
DROP 0.360
FAN
IN - 0.612 OUT 0.312
RISE 0.924
(F) REMARKS
PAGE 7
No Text
No Text
No Text