Date of Test: 5/3/2016
Customer: Landmark Homes
Test Results
1. Airflow at 50 Pascals
(50 Pa = 0.2 w.c.)
2. Leakage Areas
3. Building Leakage Curve:
4. Test Settings:
BUILDING LEAKAGE TEST
GS Services LTD
2000 S. College Ave #308
Fort Collins, CO 80525
Test File: Landmark Home 3839 Precision DrA-BD
Technician: Paul Higman
Project Number:
Building Address: 3839 Precision
UnitA
Fort Collins, CO 80528
1037 CFM50 (+/- 0.7 %)
2.94 ACH50
0.4412 CFM50/ft2 floor area
52.2 in2 (+/- 4.1 %) Canadian EgLA @ 10 Pa
18.5in2(+/-6.5%) LBLELA@4Pa
Flow Coefficient (C) = 14.3 ( +/-10.1 %)
Exponent (n) = 1.095 ( +/- 0.026 )
Correlation Coefficient = 0.99800
Test Standard: CGSB
Test Mode: Depressurization
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 19.6 CFM
0.06 ACH
2. Estimated Design Infiltration Rate: Winter: 36.8 CFM Summer: 23.1 CFM
0.10 ACH 0.07 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Digitally signed by:
Paul
Paul; Higman
D.k;SCN = Paul
Fligman C = U
igma;n -;
Date: 2016.05.06 06:
59 52-06'00'
GSSp'rW- es.
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit C - BDma
Building Information
Volume_ 21489
Surface Area
Floor Area 2223
. .. . ...... .
Height 9
#of Bedrooms
# of Occupants
Year of Construction
[Wind �S Shield
Heating and Cooling Cost and Efficiency Information
I Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Location Climate Information
'Ventilation Weather Factor 0.87
Energy Climate Factor 17.00
Heating Degree Days 6128
Cooling Degree Days 297
Design Winter Wind Speed 7.3 mph
Design Summer Wind Speed 9.4 mph
Design Winter Temp Diff 73 deg F
Design Summer Temp Diff 15 deg F
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (11 OV) Default
19028-7
Micromanometer Energy Conservatory DG700
GS; S^ere,
--� BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit C - BDma
Depressurization Test:
Environmental Data
Indoor Temperature (A°F) Outdoor Temperature (A°F) Altitude (ft)
61.0 57.0 5000.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-0.3
n/a
n/a
-60.5
-60.3
37.8
1118
1170
-1.6
Ring A
-54.8
-54.6
31.1
1016
1064
-2.3
Ring A
-48.7
-48.5
245.3
927
970
-1.0
Ring B
-42.1
-41.9
193.4
824
863
0.3
Ring B
-36.7
-36.5
165.6
763
799
5.0
Ring B
-30.5
-30.3
115.4
638
668
3.6
Ring B
-24.0
-23.8
70.0
498
521
0.3
Ring B
-18.3
-18.1
39.3
374
391
-3.9
Ring B
-0.1
n/a
n/a
Time Averaging Period: 10
Deviations from Standard RESNET Multi -Point Test - Test Parameters
None
S2iixCS BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit C - BDma
Comments
House WRT Garage = detached
BUILDING LEAKAGE TEST
`'; ` GS Services Ltd
er M c �r 2000 S. College Ave #308
. •: w. �• —" Fort Collins, CO 80525
-'` Email: BuildingPerformance@GSServices.com Website: GSServices.com
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Bordeaux - Unit D - BDma
Customer: Landmark Homes Technician:
Project Number:
Building Address: 3839 Precision Dr.
Unit D
Fort Collins, CO CO
Test Results
1. Airflow at 50 Pascals: 971 CFM50 (+/- 2.8 OX
(50 Pa = 0.2 w.c.) 2.99 ACH50
2. Leakage Area:
3. Building Leakage Curve:
4. Test Settings:
5. Accuracy Level
53.4 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 20.6 (+/- 20.5 %)
Exponent (n) = 0.984 ( +/- 0.057 )
Correlation Coefficient = 0.99834
Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
Standard Level of Accuracy Test
'Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1., Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
44.6 CFM
0.14 ACH
Winter: 65.1 CFM Summer: 47.7 CFM
0.20 ACH 0.15 ACH
Digitally signed by: Paul
Paul
Higman
1J1N-.1tN = Paul Higman C
igman =us
-.Date. 2016.05.06 07:56:.
49 -06'00'
.Gs. S
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Bordeaux - Unit D - BDma
Building Information
[Wdurne
Surface Area
Floor Area
Height
# of Bedrooms
# of Occupants
Year of Const ruction
[Wind Shield
Heating and Cooling Post and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Location Climate Information
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
j
297
Design Winter Wind Speed
7.3 - mph
Design Summer Wind Speed
9.4 mph
i Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
j
15 deg F
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration Datel
Fan Energy Conservatory Model 3 (110V) Default
Micromanometer Energy Conservatoryl 69700 19028-7
GS `Ser pes
1 BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Bordeaux - Unit D - BDma
Depressurization Test:
Environmental Data
Indoor Temperature (A°F) Outdoor Temperature (A°F) Altitude (ft)
68.0 57.0 h__5000.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure. Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-1.6
n/a,
n/a
-60.8
-59.5
36.9
-56.0
-54.7
29.9
-49.4
-48.1
211.3
-43.8
-42.5
173.1
-37.5
-36.2
137.6
-31.0
-29.7
90.0
-25.7
-24.4
59.9
-19.4
-18.1
30.5
-1.0
n/a
n/a
Time Averaging Period: 10
None
1104
1162
0.8
Ring A
997
1049
-1.1
Ring A
861
906
-3.0
Ring B
780
821
-0.8
Ring B
696
732
3.7
Ring B
564
593
2.1
Ring B
461
485
1.3
Ring B
330
347
-2.8
Ring B
Deviations from Standard RESNET Multi -Point Test - Test Parameters
s +
GS S2Y�TIS BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Bordeaux - Unit D - BDma
Comments
House WRT Garage = detached
BUILDING LEAKAGE TEST
GS Services Ltd
S ` S �iVs 2000 S. College Ave #308
-�-:w - Fort Collins, CO 80525
Email: BuildingPerformance@GSServices.com Website: GSServices.com
Date of Test: 5/2/2016
Customer: Landmark Homes
;.;
Test File: Landmark - 3839
Technician:
Project Number:
Precision Dr.-="Ch6nin `Blanc - Unit E - BD1
Building Address: 3839 Precision Dr.
Unit E
Fort Collins, CO 80528
Test Results
1. Airflow at 50 Pascals: 1131 CFM50 (+/- 1.5 %)
(50 Pa = 0.2 w.c.) 2.77ACH50
2. Leakage Area:
3. Building Leakage Curve:
4. Test Settings:
5. Accuracy Level
62.2 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 85.9 (+/- 10.4 %)
Exponent (n) = 0.659 ( +/- 0.029 )
Correlation Coefficient = 0.99904
Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 51.9 CFM
0.13ACH
2. Estimated Design Infiltration Rate: Winter: 75.8 CFM Summer: 55.6 CFM
0.19 ACH 0.14 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Pau I Digitally signed by:
Paul Higman
.�..Dk;6N = Paul
���
Higman C = US
igman..
Date. 2016.05.06 08:
' . 00.20-06'00'
5.ws
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Chenin Blanc - Unit E - BDI
.Building Information
Volume
24476
Surface Area
Floor Area
2532
Height
9
# of Bedrooms
2
2015
# of Occupants
Year of Construction
M
Wind Shield
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
. . ... . .. ............
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Type
Fan
Location Climate Information
Ventilation Weather Factor
Energy Climate Factor
Heating Degree Days
Cooling Degree Days
Design Winter Wind Speed
Design Summer Wind Speed
Design Winter Temp Diff
Design Summer. Temp Diff
Equipment Information
Manufacturer
Energy Conservatory
Micromanometer I Energy Conservatory
Model 3 (11 OV)
DG700
Serial Number
19028-7
17.00
6128
297
7.3 mph
9.4 mph
73 deg F
15 deg F
Custom Calibration Date
Default
9/9/2014
5,.YeS BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Chenin Blanc - Unit E - BD1
Depressurization Test:
Environmental Data
Indoor Temperature (A°F) I Outdoor Temperature (A°F) Altitude (ft)
52.0 -_ 57.0 5000.0
Data Points
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
1.0
n/a
n/a
-58.8
-60.3
47.8
-53.3
-54.7
41.3
-47.0
-48.5
34.5
-40.8
-42.2
30.3
-35.1
-36.5
233.4
-28.8
-30.2
175.4
-22.8
-24.2
127.9
-15.6
-17.0
85.3
1.8
n/a
n/a
Time Averaging Period: 0
None
1253
1285
0.5
Ring A
1166
1195
-0.4
Ring A
1068
1095
-1.1
Ring A
1003
1028
1.6
Ring A
904
927
0.9
Ring B
785
805
-0.8
Ring B
671
688
-1.9
Ring B
549
563
1.2
Ring B
Deviations from Standard RESNET Multi -Point Test - Test Parameters
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 5/3/2016 Test File: Landmark Home 3839 Precision DrA-BD
Building Information
Volume
21150
1 Surface Area
2350
Height
20
# of Bedrooms
2
# of Occupants
. Year of Construction
-
Wind Shield
2013
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
I Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Location Climate Information
[V—entilation WeatherFactor0.8-7—
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
29
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
9.4 mph
Design Winter Temp Diff
Design Summer Temp Diff
73 deg F
15 deg F
Equipment Information
Type Manufacturer Model Serial Number Custom Calibration
Fan Energy Conservatory Model 3 (110V) 9876 Default
Micromanometer Energy Conservatory D9700 .... ..
`S.� BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Chenin Blanc - Unit E - BD1
/ Comments
House WRT Garage =detached ✓/
S``S-�rV�G@�S BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 5/3/2016 Test File: Landmark Home 3839 Precision DrA-BD
Depressurization Test:
Environmental Data
Indoor Temperature (A°F) Outdoor Temperature (A°F)
71.0 78.0
Data Points - Data Entered Manually
Nominal
Baseline Adjusted
Fan
Nominal
Adjusted
Building Pressure
Building Pressure
Pressure
Flow
Flow
Fan
(Pa)
(Pa)
(Pa)
(cfm)
(cfm)
% Error
Configuration
-0.3
n/a
n/a
-60.2
-60.0
46.5
1236
1244
-1.7
Ring A
-55.0
-54.8
39.5
1142
1150
0.3
Ring A
-50.5
-50.3
33.1
1048
1055
1.1
Ring A
-45.1
-44.9
26.6
941
947
2.8
Ring A
-40.0
-39.8
182.2
800
805
-0.3
Ring B
-35.4
-35.2
143.2
710
715
1.2
Ring B
-30.1
-29.9
88.1
558
562
-4.9
Ring B
-25.5
-25.3
65.8
483
486
-1.1
Ring B
-20.1
-19.9
40.1
378
380
0.7
Ring B
-0.1
n/a
n/a
Deviations from Standard CGSB - Test Parameters
- n value
(1.095) outside of acceptable limits.
GS Sexxces BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 5/3/2016 Test File: Landmark Home 3839 Precision DrA-BD
Comments .
House WRT Garage = detached garage ✓
BUILDING LEAKAGE TEST
GS Services Ltd
2000 S. College Ave #308
--�—�- T-` - Fort Collins, CO 80525
Email: BuildingPerformance@GSServices.com Website: GSServices.com
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit B - BDma
Customer: Landmark Homes Technician:
Project Number:
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve:
4. 'Test Settings:
5. Accuracy Level
Building Address: 3839 Precision Dr.
Unit B
Fort Collins, CO 80528
1026 CFM50 (+/- 2.3 %) /
2.86 ACH50 �
56.4 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 32.6 (+/- 16.7 %)
Exponent (n) = 0.881 ( +/- 0.046 )
Correlation Coefficient = 0.99862
Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
47.1 CFM
0.13 ACH
Winter: 68.7 CFM Summer: 50.4 CFM
0.19 ACH 0.14 ACH
Pau I Digitally signed
bye,.Paul Higman
D,IVcCN = Paul
Higman C = US
igma-;:.
Dafe: 2016.05.06
b726:19-06'00'
V
GS Seryzes
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit B - BDma
Building Information
Volume 21489
Surface Area
FloorArea--- 2223
Height 9
# of Bedrooms 2
# of Occupants
Year of Construction 2015
Mind Shield M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
�Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
II Cooling SEER
Location Climate Information
VentilationWeather Factor
I Energy Climate Factor
Heating Degree Days
Cooling Degree Days
Design Winter Wind Speed
Design Summer Wind Speed
Design Winter Temp Diff
Design Summer Temp Diff
Equipment Information
0.87
.-.1-7.00
6128
297
7.3 mph
9.4 mph
73 deg F
15 deg F
Type Manufacturer Model Serial Number Custom Calibration Date
Fan Energy Conservatory Model 3 (11 0\/) Default
Micr omanometer Energy Conservatory DG70 0 19028-7
y•
G S "es BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit B - BDma
Depressurization Test:
Environmental Data
Indoor Temperature (A°F) Outdoor Temperature (AOF) Altitude (ft)
70.0 57.0 _ 5000.0
Data Points - Data Entered Manually
Nominal
Baseline Adjusted
Fan
Nominal
Adjusted
Building Pressure
Building Pressure
Pressure
Flow
Flow Fan
(Pa)
(Pa)
(Pa)
(cfm)
(cfm) % Error Configuration
-1.0
n/a
n/a
-60.5
-59.4
38.1
-55.3
-54.2
33.9
-49.2
-48.1
27.5
-43.0
-41.9
210.4
-36.9
-35.8
157.8
-31.0
-29.9
116.9
-25.1
-24.0
77.9
-19.1
-18.0
42.7
-1.2
n/a
n/a
Time Averaging Period: 10
None
1121
1162
-2.7
Ring A
1060
1099
-0.2
Ring A
957
992
0.1
Ring A
859
890
1.5
Ring B
745
772
1.1
Ring B
642
666
2.1
Ring B
525
544
1.3
Ring B
390
404
-3.0
Ring B
Deviations from Standard RESNET Multi -Point Test - Test Parameters
@rVI& BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit B - BDma
�omments
House WRT Garage = detached
BUILDING LEAKAGE TEST
GS Services Ltd
erv'^ ~'J' 2000 S. College Ave #308
Fort Collins, CO 80525
Email: Building Performance@GSServices.com Website: GSServices.co_m_ .
Date of Test: 5/2/2016 Test File: Landmark - 3839 Precision Dr. - Merlot - Unit C - BDma
Customer: Landmark Homes Technician:
Project Number:
Building Address: 3839 Precision Dr.
Fort Collins., CO
Test Results
1. Airflow at 50 Pascals: 1007 CFM50 (+/- 3.5 %)
(50 Pa = 0.2 w.c.) 2.81 ACH50
2. Leakage Area: 55.4 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 30.9 (+/- 25.6 %)
Exponent (n) = 0.890 (+/- 0.071 )
Correlation Coefficient = 0.99685
4. Test Settings: Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 46.2 CFM
0.13 ACH
2. Estimated Design Infiltration Rate: Winter: 67.5 CFM Summer: 49.5 CFM
0.19 ACH 0.14 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Digitally signed by: Paul
Paul Higman
DNCN = Paul Higman C
Higman:- us_
>� Date. 2016.05.06 07:41:
:'51--06'00'