October 23, 2020
FR Development, Inc.
Attn: Chris Wilson
Re: LVL Beam – Model B3
836 Cherokee Drive
Fort Collins, Colorado
Project No. 215200
Gentlemen:
A representative of Weeks & Associates reviewed the Multi-ply LVL beam framing in
the upper floor at the referenced project. We understand that the (3) 11 7/8” LVL beam
in the upper floor was installed such that (1) 11 7/8” TJI 210 I-joist was placed in
between the plies. The resulting beam is such that the stud post above falls over (2) 11
7/8” LVL plies adjacent to each other and the (1) 11 7/8” TJI 210 I-joist. The beam
should be fixed by adding an additional (1) 11 7/8” LVL next to the existing 2-ply side of
the beam. This new LVL ply is to be fastened to the existing beam with (18) 3 ½” SDS
screws within 12” of the stud point load above. Place in 3 rows, 3” min. spacing and 2”
min. edge distance, centered below the point load. Fasten the remaining length of the
LVL with (2) 10d common nails at 12” on center.
If we can be of further assistance please contact us.
Sincerely,
Weeks & Associates, Inc.
Patrick Sanders, P.E. Gary G. Weeks, P.E.
Staff Engineer Structural Engineer