Loading...
HomeMy WebLinkAbout1045 Linden Gate Ct - Disclosures/Blower Door Test - 12/15/2020BUILDING LEAKAGE TEST Date of Test: 12/15/2020 Test File: 1045 Linden Gate Ct 2.97ACH 12.15.2020 Technician: Greydon Studer - EnergyLogic Project Number: Customer: Building Address: 1045 Linden Gate Ct Fort Collins, CO 80524 Test Results at 50 Pascals: cfm50 Airflow 2639 (+/- 6.0 %) ACH50 2.97 Leakage Areas: 238.8 in² (+/- 15.1 %) Canadian EqLA @ 10 Pa 118.0 in² (+/- 25.2 %) LBL ELA @ 4 Pa Building Leakage Curve: Flow Coefficient (C) = 150.7 (+/- 40.8 %) Exponent (n) = 0.732 (+/- 0.113) Correlation Coefficient = 0.99647 Test Standard: E779-10 Test Mode: Depressurization 4 5 6 7 8 9 10 20 30 40 50 60 70 Building Pressure (Pa) 400 500 600 700 800 900 1000 2000 3000 4000 Building Leakage (cfm) Depressurize ____ BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 12/15/2020 Test File: 1045 Linden Gate Ct 2.97ACH 12.15.2020 Building Information Volume (ft³) 53233 Surface Area: (ft²) Floor Area: (ft²) Height (ft) 20 Year of Construction 2020 Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 12/15/2020 Test File: 1045 Linden Gate Ct 2.97ACH 12.15.2020 Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) Pre-Test 62.0 30.0 Post-Test 62.0 30.0 Average 62.0 30.0 5000.0 Data Points - Data Entered Manually (TTE 5.0.8.4) Nominal Building Pressure (Pa) Baseline adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -2.0 n/a n/a -60.0 -58.5 39.9 3062 2959 -0.1 Open -50.0 -48.5 31.5 2728 2636 2.2 Open -40.0 -38.5 146.0 2159 2087 -4.3 Ring A -30.0 -28.5 107.6 1861 1798 2.8 Ring A -20.0 -18.5 52.6 1313 1269 -0.5 Ring A -1.0 n/a n/a Deviations from Standard ASTM E779-10 - Test Parameters - Pressurization test not included. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 12/15/2020 Test File: 1045 Linden Gate Ct 2.97ACH 12.15.2020 Comments House to Garage -49p BUILDING LEAKAGE TEST Date of Test: 12/30/2020 Test File: 1045 Linden Gate Ct. ADU 2.18 ACH 12.30.2020 Technician: Sam Chaney/ EnergyLogic Project Number: Customer: Bluestone Phone: Fax: Building Address: 1045 Linden Gate Ct Fort Collins, CO 80524 Test Results at 50 Pascals: cfm50 Airflow 325 (+/- 4.2 %) ACH50 2.18 Leakage Areas: 29.9 in² (+/- 11.8 %) Canadian EqLA @ 10 Pa 14.9 in² (+/- 19.6 %) LBL ELA @ 4 Pa Building Leakage Curve: Flow Coefficient (C) = 19.3 (+/- 31.4 %) Exponent (n) = 0.722 (+/- 0.086) Correlation Coefficient = 0.99788 Test Standard: E779-10 Test Mode: Depressurization 4 5 6 7 8 9 10 20 30 40 50 60 70 Building Pressure (Pa) 50 60 70 80 90 100 200 300 400 500 Building Leakage (cfm) Depressurize ____ BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 12/30/2020 Test File: 1045 Linden Gate Ct. ADU 2.18 ACH 12.30.2020 Building Information Volume (ft³) 8940 Surface Area: (ft²) Floor Area: (ft²) Height (ft) 20 Year of Construction 2020 Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 12/30/2020 Test File: 1045 Linden Gate Ct. ADU 2.18 ACH 12.30.2020 Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) Pre-Test 69.0 21.0 Post-Test 69.0 21.0 Average 69.0 21.0 5000.0 Data Points - Data Entered Manually (TTE 5.0.8.4) Nominal Building Pressure (Pa) Baseline adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration 0.0 n/a n/a -20.0 -20.0 60.2 175 165 -1.7 Ring C -30.0 -30.0 117.8 247 232 3.5 Ring C -40.0 -40.0 163.2 292 275 -0.6 Ring C -50.0 -50.0 32.6 341 321 -1.2 Ring B -60.0 -60.0 43.6 394 371 0.1 Ring B 0.0 n/a n/a Deviations from Standard ASTM E779-10 - Test Parameters - Pressurization test not included. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 12/30/2020 Test File: 1045 Linden Gate Ct. ADU 2.18 ACH 12.30.2020 Comments 45 pa house to garage connection