HomeMy WebLinkAbout825 Shields St - Special Inspections/Field Verification - 02/13/2020Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave., Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
2/13/20
PROJECT
825 S. Shields St. Tenant Improvement
825 S. Shield St.
Fort Collins, CO
***Updated Phase 1 Report***
ARCHITECT
Miller Design Works
1261 York Street
Denver, CO
ENGINEER
MEC
4640 Pecos Street
Unit F
Denver, CO
CONTRACTOR
Air Comfort, Inc
150 Rome Court
Fort Collins, CO
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 – Eaton, CO 80615
Phone (970) 454-5351 – Fax (970) 454-5391
PROJECT: 825 S. Shields St. Tenant Improvement
ADDRESS: 825 S. Shields St.
Fort Collins, CO
The data presented in this report is an exact record of the system performance
and was obtained in accordance with NEBB Standard Procedures. Any
variances from design quantities which exceed NEBB tolerances are noted
throughout the report.
The air distribution systems have been tested & balanced and final adjustments
have been made in accordance with NEBB “Procedural Standards for Testing,
Adjusting & Balancing of Environmental Systems” and the project specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:2/13/20
The hydronic distribution systems have been tested & balanced and final
adjustments have been made in accordance with NEBB “Procedural Standards
for Testing, Adjusting & Balancing of Environmental Systems” and the project
specifications.
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:2/13/20
SUBMITTED & CERTIFIED BY
NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc.
TAB SUPERVISOR: David C. Reichel
REG. NO.: 2389 SIGNATURE:
DATE: 2/13/20 CERTIFICATION EXPIRATION DATE: 3/31/2020
Table Of Contents
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Table Of Contents
1 Instrument Calibration Report.pdf............................................................................................................................ 1
2 Abbreviation Report.pdf............................................................................................................................................ 3
3 Fan Coil.................................................................................................................................................................... 4
3.1 F-01.................................................................................................................................................................... 4
3.2 F-02.................................................................................................................................................................... 4
3.3 F-03.................................................................................................................................................................... 5
3.4 F-04.................................................................................................................................................................... 5
3.5 F-05.................................................................................................................................................................... 6
3.6 F-06.................................................................................................................................................................... 7
3.7 F-07.................................................................................................................................................................... 8
3.8 F-08.................................................................................................................................................................... 9
3.9 F-09.................................................................................................................................................................... 10
3.10 F-10.................................................................................................................................................................. 11
3.11 F-11................................................................................................................................................................... 12
3.12 F-12.................................................................................................................................................................. 13
3.13 F-13.................................................................................................................................................................. 14
3.14 F-14.................................................................................................................................................................. 15
4 Fan Unit.................................................................................................................................................................... 16
4.1 EF-01.................................................................................................................................................................. 16
4.2 EF-02.................................................................................................................................................................. 16
4.3 EF-03.................................................................................................................................................................. 17
4.4 EF-04.................................................................................................................................................................. 17
5 6 - Mechanical Sheets............................................................................................................................................. 18
5.1 6 - Mechanical Sheets.PDF.pdf......................................................................................................................... 18
5.1.1 6 - Mechanical Sheets................................................................................................................................. 18
5.1.1.1 M00......................................................................................................................................................... 18
5.1.1.1.1 Layout1.............................................................................................................................................. 18
5.1.2 2018-07-12 PPRM FORT COLLINS - DELTA 2 REVISION - MECHANICAL S&S.PDF.pdf......................... 19
5.1.3 6 - Mechanical Sheets................................................................................................................................. 20
5.1.3.1 M21.........................................................................................................................................................
5.1.3.1.1 M2.1E................................................................................................................................................ 20
5.1.3.2 M22......................................................................................................................................................... 21
5.1.3.2.1 M2.2W................................................................................................................................................ 21
5.1.3.2.2 M2.2E................................................................................................................................................ 22
5.1.3.3 M31......................................................................................................................................................... 23
5.1.3.3.1 Layout1.............................................................................................................................................. 23
5.1.3.4 M32......................................................................................................................................................... 24
5.1.3.4.1 Layout1.............................................................................................................................................. 24
5.1.3.5 M33......................................................................................................................................................... 25
5.1.3.5.1 Layout1.............................................................................................................................................. 25
5.1.3.6 M41......................................................................................................................................................... 26
L.H. Finn and Associates
Updated Phase 1 Report
Table Of Contents
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
5.1.3.6.1 Layout1.............................................................................................................................................. 26
5.1.3.7 M42......................................................................................................................................................... 27
5.1.3.7.1 Layout1.............................................................................................................................................. 27
5.2 2018-07-15 PPRM FORT COLLINS - CD - M43 S&S........................................................................................ 28
L.H. Finn and Associates
Updated Phase 1 Report
Manufacturer Model Serial Application Cal. Date
Alnor HM-675 71841075 Hydronic Press. & Diff. Press. 12/18/2018
Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/7/2019
Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 5/13/2019
Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 11/6/2018
Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 7/7/2017
Cooper SH66A 92711016 Temperature Measurement 10/9/2017
Extech 461895 Q394479 Rotation Measurement 6/7/2018
Extech 461895 Q083481 Rotation Measurement 1/9/2014
Extech 461895 Q247569 Rotation Measurement 3/8/2016
Extech 461895 L268576 Rotation Measurement 11/11/2019
Extech 461895 Q331990 Rotation Measurement 11/9/2018
Extech 461895 Q477125 Rotation Measurement 9/25/2015
Extech 461895 Q477126 Rotation Measurement 4/5/2016
Extech 461895 Q527632 Rotation Measurement 10/3/2017
Extech 461895 Q590099 Rotation Measurement 4/17/2017
Extech RH390 9099221 Temperature / Humidity 4/9/2015
Fluke 335 96960004 Electrical Measurement 11/5/2015
Fluke 336 97110539R Electrical Measurement 4/5/2016
Fluke 336 97110538R Electrical Measurement 9/29/2015
Fluke 335 92008180 Electrical Measurement 11/4/2014
Fluke 335 72990071 Electrical Measurement 11/5/2018
Fluke 374 15460133 Electrical Measurement 4/18/2014
Fluke 374 20030351 Electrical Measurement 10/3/2017
Fluke 374 20030354 Electrical Measurement 6/4/2018
Fluke 324 41620416WS Electrical Measurement 11/11/2019
TSI 8322 55100720 Air Velocity Measurement 10/4/2017
Shortridge ADM-860C M05789 Digital Manometer 11/25/2015
Shortridge ADM-860C M06821 Digital Manometer 6/1/2018
Shortridge ADM-860C M07352 Digital Manometer 6/6/2016
Shortridge ADM-860C M09123 Digital Manometer 4/18/2016
Shortridge ADM-860C M09347 Digital Manometer 9/26/2015
Shortridge ADM-860C M10144 Digital Manometer 4/14/2017
Shortridge ADM-860C M10371 Digital Manometer 11/5/2015
Shortridge ADM-860C M11448 Digital Manometer 4/14/2017
Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015
Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 6/1/2018
Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015
REMARKS: Not all equipment shown was used on this project.
Project: 825 S. Shield St. Tenant Improvement
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
INSTRUMENT CALIBRATION REPORT
Page 1 of 28
Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017
Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 4/26/2019
Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017
Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 4/9/2018
Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 4/9/2018
Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 4/26/2019
Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 10/11/2019
Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 4/26/2019
Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 6/5/2018
Evergreen Telemetry S-PVF-1 1600322 Pressure Velocity Module 6/5/2018
Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 5/11/2017
Evergreen Telemetry S-PVF-1 1700214 Pressure Velocity Module 5/11/2017
Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 2/25/2019
Evergreen Telemetry S-PVF-1 1700216 Pressure Velocity Module 5/11/2017
Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/11/2017
Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/11/2017
Evergreen Telemetry S-PVF-1 1900188 Pressure Velocity Module 3/7/2019
Evergreen Telemetry S-PVF-1 1900138 Pressure Velocity Module 2/6/2019
Evergreen Telemetry RM-T-1 1700269 Radio Module 11/7/2019
Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016
Evergreen Telemetry RM-T-1 1600235 Radio Module 10/10/2016
Evergreen Telemetry RM-T-1 1600233 Radio Module 10/10/2016
Evergreen Telemetry RM-T-1 1600234 Radio Module 10/10/2016
Evergreen Telemetry RM-T-1 1700260 Radio Module 4/21/2017
Evergreen Telemetry RM-T-1 1700261 Radio Module 4/21/2017
Evergreen Telemetry RM-T-1 1900172 Radio Module 2/12/2019
Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 11/7/2019
Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/10/2016
Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/10/2016
Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/10/2016
Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/10/2016
Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017
Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017
Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017
Evergreen Telemetry PR-T-4-6 1900119 Temperature Probe (Insertion) 1/23/2019
Evergreen Telemetry PR-T-5 1900172 Temperature Probe 2/12/2019
Evergreen Telemetry S-H-3-5" 1900155 Humidity Sensor 3/8/2019
Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017
Evergreen Telemetry S-DP-250 1600125 Water Press. Sensing Module 5/22/2018
Fuji Porta Flow SO414581 Ultrasonic Water Flow Meter 9/26/2018
REMARKS: Not all equipment shown was used on this project.
Project: 825 S. Shield St. Tenant Improvement
INSTRUMENT CALIBRATION REPORT (Continue)
Page 2 of 28
Project: 825 S. Shield St. Tenant Improvement
Symbol Description Symbol Description
A Airflow (L/S) NA Not Applicable
AF Air Foil NI Not Installed
ANA Access Not Available NIC Not In Contract
BI Backward Incline NM Not Measurable
CD Ceiling Diffuser NPT No Pressure Tap
CFM Airflow (Cubic Feet / Minute) NR Not Readable
DD Direct Drive NS Not Shown
DWDI Double Width Double Inlet NT No Information Tag
EAT Entering Air Temperature OD Outside Diameter
EF Exhaust Fan RPM Revolution Per Minute
EG Exhaust Grille SD Supply Diffuser
ER Exhaust Register SNKL Snorkel
ESP External Static Pressure SP Static Pressure
EWT Entering Water Temperature SPD Static Pressure Drop
FC Forward Curve SR Supply Register
GPM Waterflow (Gallons / Minute) SWSI Single Width Single Inlet
HC Heat Coil T Temperature ( F )
HEX Heat Exchanger TSP Total Static Pressure
HRC Heat Recovery Coil VFD Variable Frequency Drive
Hz Hertz VS Variable Speed
ID Inside Diameter W Waterflow (L/S)
In. WC Inches of Water Column
LAT Leaving Air Temperature
LWT Leaving Water Temperature
REMARKS:
Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave, Suite 220 - Eaton, CO 80615
Phone (970) 454-5351 - Fax (970) 454-5391
ABBREVIATION REPORT
Page 3 of 28
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-01
Log: F-01 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 1200 CFM
Outside Air CFM Design 190 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1112 18 200
Outlet-02 1113 18 200
Outlet-03 1113 18 200
Outlet-04 1113 18 200
Outlet-05 1113 18 200
Outlet-06 1113 18 200
Totals: - - - 1200 0 0 0 0
F-01 Supply Outlet Summary
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-02
Log: F-02 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 1200 CFM
Outside Air CFM Design 220 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1309 18 175
Outlet-02 1309 18 175
Outlet-03 1309 18 175
Outlet-04 1309 18 175
Outlet-05 1309 18 175
Outlet-06 1309 18 175
Outlet-07 1309 18 175
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-03
Log: F-03 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 600 CFM
Outside Air CFM Design 65 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1114 5 240
Outlet-02 1109 5 200
Outlet-03 1104 5 160
Totals: - - - 600 0 0 0 0
F-03 Supply Outlet Summary
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-04
Log: F-04 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 600 CFM
Outside Air CFM Design 60 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1301 5 150
Outlet-02 1401 5 135
Outlet-03 1201 5 115
Outlet-04 1203 2 200
Totals: - - - 600 0 0 0 0
F-04 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-05
Log: F-05 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 600 CFM
Outside Air CFM Design 115 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1304 5 90
Outlet-02 1306 5 90
Outlet-03 1401 5 80
Outlet-04 1402 5 70
Outlet-05 1403 5 70
Outlet-06 1207 5 70
Outlet-07 1206 5 70
Outlet-08 1404 2 200
Totals: - - - 740 0 0 0 0
F-05 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1304 3 90
Inlet-B 1306 3 80
Inlet-C 1401 3 70
Inlet-D 1402 3 70
Inlet-E 1203 3 70
Inlet-F 1207 3 70
Inlet-G 1206 3 70
Inlet-H 1404 18 200
Totals: - - - 720 0 0 0 0
F-05 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/22/2020
SYSTEM/UNIT: F-06
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC2D040E171112
Unit Serial Number 3719A67664
Filter Type Pleated
Filter Qty 1
Filter Size 16x24x1
Test Data
Total CFM Design 600 CFM
Total CFM Actual 633 CFM
Outside Air CFM Design 70 CFM
Outside Air CFM Actual 75 CFM
Return Air CFM Design 530 CFM
Return Air CFM Actual 558 CFM
Motor Volts T1-T2 122 Volts
Amps T1 5.8 Amps
Fan RPM Actual High Speed RPM
Unit E.S.P. Actual 0.42 In. wc.
E.S.P. In -0.14 In. wc.
E.S.P. Out 0.28 In. wc.
Motor Data
Motor Manufacturer Broad-Ocean
Motor HP 1/2
Motor RPM 1050 RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 6.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1308 2 130 280 136 215 105
Outlet-02 1501 5 200 287 209 144 105
Outlet-03 1411 5 200 149 212 75 106
Outlet-04 1409 5 70 103 76 147 109
Totals: - - - 600 819 633 137 106
F-06 Supply Outlet Summary
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-07
Log: F-07 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 800 CFM
Outside Air CFM Design 65 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1406 2 130
Outlet-02 1406 2 75
Outlet-03 See Print 2 75
Outlet-04 1405 2 100
Outlet-05 1205 2 180
Outlet-06 1204 2 240
Totals: - - - 800 0 0 0 0
F-07 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1406 18 130
Inlet-B 1406 18 75
Inlet-C See Print 18 75
Inlet-D 1405 18 100
Inlet-E 1205 19 180
Inlet-F 1204 19 240
Totals: - - - 800 0 0 0 0
F-07 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 8 of 28
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-08
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC2D040E171112
Unit Serial Number 3119A60893
Filter Type Pleated
Filter Qty 1
Filter Size 18x25x3
Test Data
Total CFM Design 600 CFM
Total CFM Actual 593 CFM
Outside Air CFM Design 80 CFM
Outside Air CFM Actual 85 CFM
Return Air CFM Design 520 CFM
Return Air CFM Actual 508 CFM
Motor Volts T1-T2 121 Volts
Amps T1 3.4 Amps
Fan RPM Actual Medium High RPM
Unit E.S.P. Actual 0.66 In. wc.
E.S.P. In -0.03 In. wc.
E.S.P. Out 0.63 In. wc.
Motor Data
Motor Manufacturer Broad-Ocean
Motor HP 1/2
Motor RPM 1050 RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 6.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1502 20 300 156 294 52 98
Outlet-02 1502 20 300 163 299 54 100
Totals: - - - 600 319 593 53 99
F-08 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/22/2020
SYSTEM/UNIT: F-09
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC2D040E171112
Unit Serial Number 3519A60178
Filter Type Pleated
Filter Qty 1
Filter Size 18x25x3
Test Data
Total CFM Design 600 CFM
Total CFM Actual 638 CFM
Outside Air CFM Design 80 CFM
Outside Air CFM Actual 86 CFM
Return Air CFM Design 520 CFM
Return Air CFM Actual 552 CFM
Motor Volts T1-T2 122 Volts
Amps T1 2.7 Amps
Fan RPM Actual Medium High Speed RPM
Unit E.S.P. Actual 0.31 In. wc.
E.S.P. In -0.11 In. wc.
E.S.P. Out 0.2 In. wc.
Motor Data
Motor Manufacturer Broad-Ocean
Motor HP 1/2
Motor RPM 1050 RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 6.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1505 20 300 316 316 105 105
Outlet-02 1505 20 300 322 322 107 107
Totals: - - - 600 638 638 106 106
F-09 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/22/2020
SYSTEM/UNIT: F-10
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC2D040E171112
Unit Serial Number 3519A60893
Filter Type Pleated
Filter Qty 1
Filter Size 18x25x3
Test Data
Total CFM Design 600 CFM
Total CFM Actual 614 CFM
Outside Air CFM Design 80 CFM
Outside Air CFM Actual 83 CFM
Return Air CFM Design 520 CFM
Return Air CFM Actual 531 CFM
Motor Volts T1-T2 121 Volts
Amps T1 2.9 Amps
Fan RPM Actual Medium High Speed RPM
Unit E.S.P. Actual 0.24 In. wc.
E.S.P. In -0.02 In. wc.
E.S.P. Out 0.22 In. wc.
Motor Data
Motor Manufacturer Broad-Ocean
Motor HP 1/2
Motor RPM 1050 RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 6.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1506 20 300 268 303 89 101
Outlet-02 1506 20 300 273 311 91 104
Totals: - - - 600 541 614 90 102
F-10 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/22/2020
SYSTEM/UNIT: F-11
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC2D040E171112
Unit Serial Number 3119A60843
Filter Type Pleated
Filter Qty 1
Filter Size 18x25x3
Test Data
Total CFM Design 600 CFM
Total CFM Actual 593 CFM
Outside Air CFM Design 150 CFM
Outside Air CFM Actual 155 CFM
Return Air CFM Design 450 CFM
Return Air CFM Actual 438 CFM
Motor Volts T1-T2 121 Volts
Amps T1 3.3 Amps
Fan RPM Actual Medium High Speed RPM
Unit E.S.P. Actual 0.21 In. wc.
E.S.P. In -0.13 In. wc.
E.S.P. Out 0.08 In. wc.
Motor Data
Motor Manufacturer Broad-Ocean
Motor HP 1/2
Motor RPM 1050 RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 6.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1508 2 300 575 298 192 99
Outlet-02 1508 2 300 27 295 9 98
Totals: - - - 600 602 593 100 99
F-11 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/22/2020
SYSTEM/UNIT: F-12
Log: F-12 1/15/2020 Emerson Moore Unit toltal based on Outlet summation.
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC2D040E171112
Unit Serial Number 3519A60136
Filter Type Pleated
Filter Qty 1
Filter Size 18x25x3
Test Data
Total CFM Design 610 CFM
Total CFM Actual 612 CFM
Outside Air CFM Design 60 CFM
Outside Air CFM Actual 155 CFM
Return Air CFM Design 450 CFM
Return Air CFM Actual 438 CFM
Motor Volts T1-T2 123 Volts
Amps T1 2.2 Amps
Fan RPM Actual Medium High Speed RPM
Unit E.S.P. Actual 0.21 In. wc.
E.S.P. In -0.13 In. wc.
E.S.P. Out 0.08 In. wc.
Motor Data
Motor Manufacturer Broad-Ocean
Motor HP 1/2
Motor RPM 1050 RPM
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 6.4 Amps
Sheave Data
Motor Sheave Make Direct Drive
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1504 5 75 104 76 139 101
Outlet-02 1503 5 75 66 74 88 99
Outlet-03 1601 17 115 175 117 152 102
Outlet-04 1601 17 115 162 114 141 99
Outlet-05 1601 17 115 114 113 99 98
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-13
Log: F-13 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 600 CFM
Outside Air CFM Design 60 CFM
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 1106 2 80
Outlet-02 1107 2 50
Outlet-03 1102 8 260
Outlet-04 1103 2 210
Totals: - - - 600 0 0 0 0
F-13 Supply Outlet Summary
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1106 18 130
Inlet-B 1103 18 210
Inlet-C 1102 2 260
Totals: - - - 600 0 0 0 0
F-13 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 14 of 28
Fan Coil
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: F-14
Log: F-14 1/15/2020 Emerson Moore Unit to be balanced on phase 2.
Test Data
Total CFM Design 1200 CFM
Outside Air CFM Design 230 CFM
System/Unit Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01 50
Outlet-02 100
Outlet-03 100
Outlet-04 140
Outlet-05 140
Outlet-06 140
Outlet-07 140
Outlet-08 115
Outlet-09 115
Outlet-10 75
Outlet-11 85
Totals: - - - 1200 0 0 0 0
F-14 Supply Outlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 15 of 28
Fan Unit
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: EF-01
Log: EF-01 1/22/2020 Emerson Moore Multiple EF-01s on site. Recorded values shown as
range of operation between identical fans.
Unit Data
Fan Manufacturer Greenheck
Fan Model Number SP-A125-QD
Fan Arrangement DWDI
Fan Discharge Vertical/Up
Starter Data
Installed Thermal Internal
Test Data
Total CFM Design 80 CFM
Total CFM Actual 78-86 CFM
Fan RPM Actual Direct Drive RPM
Motor Volts 1 120-122 Volts
Motor Amps 1 0.1 Amps
SP In Actual 0.0 in. wc
SP Out Actual ANA in. wc
Total SP Actual NM in. wc
Motor Data
Motor Manufacturer Greenheck
Motor RPM 1100 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 0.18 Amps
Sheave Data
Motor Sheave Make Direct Drive
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: EF-02
Log: EF-02 2/11/2020 Emerson Moore Fan slowed down to design CFM after installation of
Speed Control.
Unit Data
Fan Manufacturer Greenheck
Fan Model Number SP-A200-QD
Fan Serial Number 16016915
Fan Type Forward Curve
Fan Arrangement DWDI
Fan Discharge Vertical/Up
Starter Data
Installed Thermal Internal
Test Data
Total CFM Design 150 CFM
Total CFM Actual 155 CFM
Fan RPM Actual Low Speed RPM
Motor Volts 1 121 Volts
Fan Unit
PROJECT:
LOCATION:
825 S. Shields St. Tenant Improvement
Fort Collins , CO
DATE:
CONTACT:
AUTHOR:
2/13/2020
Emerson Moore
Emerson Moore
Tested By: Emerson Moore
Date: 1/15/2020
SYSTEM/UNIT: EF-03
Log: EF-03 1/15/2020 Emerson Moore Fan to be tested on Phase 2.
Test Data
Total CFM Design 150 CFM
Tested By: Emerson Moore
Date: 2/13/2020
SYSTEM/UNIT: EF-04
Unit Data
Fan Manufacturer Greenheck
Fan Model Number SP-A700-QD
Fan Serial Number 15997155
Fan Type Forward Curve
Fan Arrangement DWDI
Fan Discharge Horizontal
Starter Data
Installed Thermal Internal
Test Data
Total CFM Design 600 CFM
Total CFM Actual 588 CFM
Fan RPM Actual Direct Drive RPM
Motor Volts 1 122 Volts
Motor Amps 1 3.1 Amps
SP In Actual 0.0 in. wc
SP Out Actual ANA in. wc
Total SP Actual NM in. wc
Motor Data
Motor Manufacturer Fasco
Motor RPM 1100 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 3.5 Amps
Sheave Data
Motor Sheave Make Direct Drive
L.H. Finn and Associates
Updated Phase 1 Report
Page 17 of 28
GENERAL NOTES
1.ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES, LOCAL CODES, AND OWNER'S STANDARDS
INDICATED BY THE CONSTRUCTION DOCUMENTS.
2.MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS
ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS AND
FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES,
AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE OWNER.
3.CONTRACTOR SHALL COORDINATE WORK INDICATED WITH PLUMBING, ELECTRICAL, STRUCTURAL, AND ARCHITECTURAL DIVISIONS. VERIFY
FIT OF MECHANICAL SYSTEMS PRIOR TO FABRICATION. COORDINATE ALL CHASE, SLEEVE, AND SLAB SAWCUT/COREDRILL REQUIREMENTS
BEFORE CONSTRUCTION.
4.PROVIDE ALL EQUIPMENT SCHEDULED OR INDICATED ON THE DRAWINGS BUT NOT INCLUDED WITHIN THE SPECIFICATIONS INCLUDING ANY
REQUIRED BUT NOT LISTED MISC ITEMS NEEDED TO PROVIDE COMPLETELY OPERATIONAL SYSTEMS AS INDICATED WHETHER SPECIFICALLY
CALLED FOR OR NOT. INSTALLATION SHALL CONFORM TO MANUFACTURERS RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE
SUBMITTALS FOR ALL PROPOSED EQUIPMENT AND MATERIALS TO BE UTILIZED. PROVIDE OPERATION AND MAINTENANCE MANUAL FOR ALL
SYSTEMS AND EQUIPMENT AT END OF PROJECT.
5.ELECTRICAL CHARACTERISTICS OF MECHANICAL EQUIPMENT SHALL BE VERIFIED WITH ELECTRICAL DRAWINGS AND ELECTRICAL
CONTRACTOR PRIOR TO EQUIPMENT ORDER RELEASE. ADDITIONAL ELECTRICAL WORK RESULTING FROM EQUIPMENT SUBSTITUTION IS THE
RESPONSIBILITY OF THIS CONTRACTOR.
6.ITEM DESIGNATIONS INDICATED HEREON ARE FOR PURPOSES OF THESE DOCUMENTS ONLY. CONTRACTOR SHALL VERIFY WITH OWNERS
REPRESENTATIVE ACTUAL "TAGGING" INFORMATION TO BE PROVIDED FOR EACH ITEM OF MECHANICAL EQUIPMENT PRIOR TO NAMEPLATE
ORDER RELEASE.
7.PROVIDE 18" X 18" MINIMUM ACCESS DOOR IN INACCESSIBLE CEILINGS AND WALLS FOR EQUIPMENT AND VALVES REQUIRING ACCESS OR
ADJUSTMENT. COORDINATE LOCATIONS AND SUBMIT TO ARCHITECT FOR APPROVAL PRIOR TO BEGINNING WORK.
7.DUCT SIZES INDICATED ARE OUTSIDE DIMENSIONS, BRANCH RUN-OUT DUCTS TO DIFFUSERS AND GRILLES TO BE SAME SIZE AS DIFFUSER
OR GRILLE CONNECTION SIZE UNLESS OTHERWISE NOTED.
8.LENGTH OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO 5'-0" MAX. HORIZONTAL RUN WITH ONLY ONE 90^ ELBOW PERMITTED. SECURE
FLEXIBLE DUCTWORK WITH SCREWS & DRAWBANDS PER SMACNA STANDARDS.
9.PROVIDE CEILING OPERATORS FOR INACCESSIBLE MVD'S WHERE INDICATED, EQUAL TO YOUNG REGULATOR, REMOTE GEAR OPERATED,
WITH CEILING ESCUTCHEON.
10.DUCT MOUNTED SMOKE DETECTORS SHALL BE ZERO VELOCITY TYPE WHERE INDICATED ON DRAWINGS.
11.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ACTUAL LOCATION OF GRILLES, DIFFUSERS, AND ACCESS DOORS IN CEILING.
SECURE DIFFUSERS & GRILLES TO T-BAR CEILINGS WHERE APPLICABLE. SUBMIT SHOP DWG. FOR APPROVAL PRIOR TO BEGINNING WORK.
12.AT THE COMPLETION OF WORK, PROVIDE TESTING AND BALANCING SERVICES FOR MECHANICAL SYSTEM. SUBMIT WRITTEN REPORT TO
ARCHITECT LISTING SYSTEM AIRFLOWS, ELECTRIC DATA, TEMPERATURES, AND PRESSURE DROPS. AIR BALANCE REPORT REQUIRED PRIOR TO
SCHEDULING FINAL MECHANICAL INSPECTION.
13.WHERE PIPES PASS THROUGH FIRE-RATED FLOOR OR WALLS, SEAL WITH MATERIALS EQUAL TO 3M FIRE BARRIER, MEETING TESTING PER
ASTM-E-814 (UL 1479). USE CAULK OR PUTTY TYPE. ALL EXTERIOR WALL AND ROOF PENETRATIONS SHALL BE SEALED WATERPROOF.
14.AT THE COMPLETION OF THE WORK AND PRIOR TO FINAL ACCEPTANCE, ALL PARTS OF THE WORK INSTALLED UNDER THIS SPECIFICATION
SHALL BE THOROUGHLY CLEANED.
15.ALL EQUIPMENT, MATERIALS, AND INSTALLATION IS TO BE WARRANTEED FOR ONE YEAR TO BE FREE FROM DEFECT. PROVIDE WRITTEN
WARRANTY TO OWNER.
16.THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR TO MEANS, METHODS,
TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM HIS WORK.
17.THIS CONTRACTOR SHALL FIELD VERIFY LOCATIONS AND SIZES OF ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, ELECTRICAL CONDUIT,
STRUCTURAL MEMBERS, ETC., PRIOR TO STARTING OF CONSTRUCTION. COORDINATE CONFLICTS WITH THE GENERAL CONTRACTOR.
18.THIS CONTRACTOR SHALL COORDINATE ALL REQUIRED EXISTING BUILDING SERVICE SYSTEM OUTAGES WITH BUILDING MANAGEMENT.
19.ALL MECHANICAL SYSTEMS ARE REQUIRED TO BE INSTALLED PER BASE BUILDING REQUIREMENTS, LOCAL AND STATE JURISDICTIONAL
CODES, ORDINANCES, AND APPLICABLE REGULATIONS.
20.PATCH AND REPAIR TO MATCH EXISTING, ANY WALL/CEILINGS TO BE ACCESSED TO ROUTE PIPING AND DUCTWORK.
21.EXISTING DUCTWORK, PIPING, AND EQUIPMENT TO REMAIN IS SHOWN LIGHT. NEW DUCTWORK, PIPING, AND EQUIPMENT IS SHOWN HEAVY.
M0.0 MECHANICAL LEGEND AND NOTES
SHEET NO. SHEET DESCRIPTION
MECHANICAL SHEET INDEX
ISSUE
M3.1 MECHANICAL SCHEDULES
M4.1 MECHANICAL DETAILS
06-04-18 CONSTRUCTION DOCUMENTS
M3.2 MECHANICAL SCHEDULES
M3.3 MECHANICAL SCHEDULES
M2.1E MECHANICAL PLAN - EAST
Page 19 of 28
D E F
WATER
1604
SERVICE
1505
PROCEDURE
1603
STAIR
1406
CORRIDOR
1502
PROCEDURE
PROCEDURE
1410
UTILITY
BREAK
1503
ROOM
PROCEDURE
1507
SUPPORT
PROCEDURE
1508
SUPPORT
1602
UNISEX
1307
STORAGE
UTILITY
1504
HALL
1501
CORRIDOR
EDUCATION
1601
OFFICE
1506
PROCEDURE
1408
MEN
1407
WOMEN
R.N.
1409
OFFICE
1411
ULTRASOUND
1306
ULTRASOUND
1405
WAITING
1404
CONSULT
1403
CONSULT
1402
CONSULT
1309
RECOVERY
1308
SCALE: 1" = 4'-0"
MECHANICAL MEZZANINE PLAN - WEST
1
A B C D
4
3
2
1
RECOVERY
OPEN TO UNDERSIDE OF ROOF
WAITING ROOM
OPEN TO UNDERSIDE OF ROOF
VESTIBULE
OPEN TO UNDERSIDE OF ROOF
2103
LANDING
2206
I.T.
2101
STAIR
OPEN
2202
OFFICE
2203
UNISEX
2107
BREAK
2105
FILES
2104
MECHANICAL 2204
MECHANICAL
2201
MECHANICAL
2106
MECHANICAL
2102
MECHANICAL
1
13
4
3
3
4 3
10
11
T
12/12
14/14
8/12
T
NOTES
1 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED HORIZONTALLY IN CEILING SPACE. CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: HORIZONTAL FURNACE DETAIL 6/M4.1}
3 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 1, 5/M4.1}
2 \pxsm1,t3;{\Fsimplex|c0;\W1;18/10 TRANSFER AIR OPENING AS HIGH IN WALL AS POSSIBLE, PROVIDE GRILLE ON EACH SIDE OF OPENING.}
4 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 1, 2/M4.2}
5 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 4"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
6 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 2, 4/M4.2}
\pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 2, 5/M4.2}
8 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 3, 6/M4.2}
D E F
EDUCATION OFFICE
OPEN TO UNDERSIDE OF ROOF
RECOVERY
OPEN TO UNDERSIDE OF ROOF
2307
EQUIPMENT
2206
2306
STAIR
EDUCATION
2304
ENTRY
EDUCATION
2302
OFFICE
OPEN
2202
OFFICE
2305
MECHANICAL
EDUCATION
2301
OFFICE
2303
MECHANICAL
2203
UNISEX
2205
MECHANICAL
2204
MECHANICAL
SCALE: 1" = 4'-0"
MECHANICAL MEZZANINE PLAN - EAST
1
1
3
6 4
10
T
8/12
T
NOTES
1 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED HORIZONTALLY IN CEILING SPACE. CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: HORIZONTAL FURNACE DETAIL 6/M4.1}
3 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 1, 5/M4.1}
2 \pxsm1,t3;{\Fsimplex|c0;\W1;18/10 TRANSFER AIR OPENING AS HIGH IN WALL AS POSSIBLE, PROVIDE GRILLE ON EACH SIDE OF OPENING.}
4 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 1, 2/M4.2}
5 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 4"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
6 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 2, 4/M4.2}
\pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 2, 5/M4.2}
8 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 3, 6/M4.2}
9 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 8"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
10 11 \\pxsm1,pxsm1,t3;{\Fsimplex|t3;{\Fsimplex|c0;\W1;NEW AC c0;UNIT \W1;INSTALLED NEW ON FURNACE WALL ABOVE DOOR INSTALLED PER MANUFACTURER'S ON MEZZANINE INSTALLATION INSTRUCTIONS
FLOOR, WITH CONNECT CONDENSING UNIT 10"MOUNTED OA TO ON RETURN GRADE. EXTEND AIR REFRIGERANT AND EXTEND PIPING FROM UP CONDENSING THROUGH UNIT TO ROOF. FAN COIL UNIT RE: INSTALLED VERTICAL
PER MANUFACTURER'S UPFLOW INSTALLATION FURNACE INSTRUCTIONS. DETAIL } 4, 1/M4.3}
12 \pxsm1,t3;{\Fsimplex|c0;\W1;INSULATE ALL DUCTS ROUTED THROUGH ATTIC WITH R12 INSULATION.}
13 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE 1" GAP AT BOTTOM OF DOOR FOR AIR TRANSFER.}
{DEMO NOTES:
1. REMOVE ALL EXISTING HVAC EQUIPMENT EXCEPT FOR EXHAUST FAN AT MEZZANINE LEVEL BATHROOM.}
14 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 10"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
SUPPLY FAN
(IN. WC)
ESP
ITEM
SERVICE
LOCATION/
MODEL
MANUFACTURER/
FURNACE SCHEDULE (NATURAL GAS HEATING - DX COOLING)
CFM
(LBS.)
MIN. MOTOR HP
VOLTS/PH WT.
MAX
OPER.
HEATING CAPACITY COOLING CAPACITY
(CFM)
OA
MINIMUM
DIMENSIONS
OVERALL
NOTES
1
%%UNOTES:
PROVIDE 1 STAGE FURNACE DESIGNED FOR SEALED COMBUSTION OPERATION UTILIZING PVC VENTING, PROVIDE CONDENSATE NEUTRALIZATION KIT, MANUFACTURER APPROVED CONCENTRIC VENT AND INTAKE TERMINATION.
2 PROVIDE FILTER RACK AND 1" MERV 8 DISPOSABLE FILTER.
(DB/WB)
EAT
MBH
(DB/WB)
LAT
(DEGREES F)
AMBIENT TEMP
CONDENSER
(SEER)
EFFICIENCY
(MBH @ SL)
OUTPUT
(MBH @ SL)
INPUT
MINIMUM
3 FURNISH UNIT DESIGNED FOR HIGH ALTITUDE OPERATION (5000 FT).
EVAPORATOR
EVAPORATOR
AMPACITY
FUSE
MAXIMUM
4 PROVIDE 24/7 PROGRAMMABLE THERMOSTAT WITH 5 DEG F DEADBAND BETWEEN HEATING AND COOLING AND 10 HOUR BATTERY BACKUP.
AMPACITY
CIRCUIT
MINIMUM
F
1 WAITING
MEZZANINE/
(DB)
EAT MIN.
(DB)
LAT MIN.
5
F
CONDENSING UNIT SCHEDULE
ITEM
1
%%UNOTES:
PROVIDE CRANKCASE HEATER, ANTI-SHORT CYCLE TIMER, VIBRATION ISOLATION AND CONCRETE BASE & PAD, TXV, LONG LINE KIT, AND LOW AMBIENT (-10 DEGREES F) OPERATING ACCESSORIES.
MANUFACTURER/
MODEL
LOCATION/
SERVICE
CAPACITY
(MBH)
DB (%%DF)
EAT
RLA LRA NOTES
REFRIGERANT WEIGHT
PHASE (LBS)
MCA MOP VOLT/
COOLING
EFFICIENCY
(SEER)
MINIMUM
DIMENSIONS
OVERALL
MAX
CU
F-2
CU
F-1
CU
F-3
CU
F-4
CU
F-5
GRADE/
F-5
CU
F-6
CU
F-7
GRADE/
F-7
CU
F-8
GRADE/
F-8
CU
F-9
GRADE/
F-9
CU
F-10
GRADE/
F-10
CU
F-11
CU
F-12
GRADE/
F-4
CFM
ITEM MANUFACTURER/ MAX.
HEATER (ELECTRIC)
(KW)
HEATING
CAP. VOLTS/PHASE
DIMENSIONS
OVERALL
(LBS.)
WT.
MAX.
OPER.
1
%%UNOTES:
FURNISH FACTORY INSTALLED DISCONNECT AND INTEGRAL TAMPER-PROOF THERMOSTAT SET AT 60 DEG F
NOTES
MODEL
LOCATION/
SERVICE
WALL/ 3.0 160 208/1 24 4-1/2" DEEP X 14-1/2" WIDE X 19-7/8" TALL 1 2
HEAT
2 FURNISH WITH RECESSED WALL BOX WHERE INSTALLED IN FRAMED WALLS AND SURFACE MOUNT BOX WHERE INSTALLED ON CONCRETE WALLS.
INDEECO/
WCI
CUH
3.0KW
%%UTYPE R2%%U:
DIFFUSER & REGISTER SPECIFICATIONS
%%UTYPE R1%%U:
%%URETURN/EXHAUST AIR
%%USUPPLY AIR
%%UTYPE S1%%U:
DIFFUSER & REGISTER SCHEDULE
SUPPLY AIR
13
18/10
14/14
12
22/6
8
9
10
11
18/6
14/6
10/6
6/6
2 12/12 - 8"~
3 12/12 - 10"~
4
5
6/6 - 6"~
ITEM NECK SIZE
1
6
0 - 1,020
R2
36/18
0 - 720
0 - 230
FLEXIBLE CONNECTION DETAIL
NO SCALE
1
M4.1
3"-4" (10" MAX.)
FAN OUTLET/INLET
DIFFUSER MOUNTING DETAIL
NO SCALE
2
M4.1
45 DEGREE TAKE-OFF DETAIL
NO SCALE
3
M4.1
W
45%%d
RL
RS
CONDENSING UNIT AT GRADE DETAIL
NO SCALE
4
M4.1
VERTICAL DOWNFLOW FURNACE DETAIL 1
NO SCALE
5
M4.1
RS
RL
HORIZONTAL FURNACE DETAIL
NO SCALE M4.1
RS
RL
M4.1
NONE
MECHANICAL DETAILS
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
Page 26 of 28
EXPOSED SPIRAL DUCT HANGER DETAIL
NO SCALE
1
M4.2
VERTICAL UPFLOW FURNACE DETAIL 1
NO SCALE
2
M4.2
RS
RL
REMOTE DAMPER CONTROL DETAIL
NO SCALE
3
M4.2
PROVIDE CEILING OPERATORS FOR INACCESSIBLE MVD'S WHERE INDICATED, EQUAL TO YOUNG REGULATOR, REMOTE GEAR OPERATED, WITH CEILING ESCUTCHEON.
VERTICAL DOWNFLOW FURNACE DETAIL 2
NO SCALE
4
M4.2
RS
RL
VERTICAL UPFLOW FURNACE DETAIL 2
NO SCALE
5
M4.2
RS
RL
VERTICAL UPFLOW FURNACE DETAIL 3
NO SCALE M4.2
RS
RL
M4.2
NONE
MECHANICAL DETAILS
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
Page 27 of 28
Page 28 of 28
0 - 360
0 - 480
0 - 610
S3
8
9
10
11
0 - 930
0 - 2,100
12/12
18/18
22/18
TYPE
0 - 410
0 - 600
CFM RANGE
0 - 230
2 12/6
3
4
5
S1
ITEM
1
MODULE-NECK SIZE
6/6
6
0 - 300
0 - 600
0 - 1,100
TYPE
0 - 150 R1
CFM RANGE
0 - 1,375
RETURN/EXHAUST AIR
12/24 - 10/22 0 - 500
24/24 - 22/22 0 - 1,000
KRUEGER MODEL SHR 24"X24" STEEL LOUVERED PANEL DIFFUSER, NON-ADJUSTABLE 4-WAY HORIZONTAL THROW, WHITE FINISH, ROUND NECK. FRAME 23 FOR LAY-IN CEILINGS. FRAME 21 FOR GYP. BOARD CEILINGS.
KRUEGER MODEL S85H, STEEL GRILLE, 1/2" BLADE SPACING, 35%%D BLADE ANGLE, WHITE FINISH, OBD. FRAME 23 FOR LAY IN CEILINGS. CONCEALED MOUNTING FOR GYP. BOARD CEILINGS.
KRUEGER MODEL 6490 STEEL PERFORATED FACE RETURN WITH SQUARE NECK FOR DUCTED APPLICATIONS, FRAME 23 FOR LAY-IN CEILINGS, FRAME 22 FOR GYP. BOARD CEILINGS, WHITE FINISH.
14 22/10 0 - 1,120
15 24/10 0 - 1,220
18/10 0 - 700
18/8 0 - 600
%%UTYPE R3%%U: KRUEGER MODEL #600, STEEL SIGHT-PROOF TRANSFER AIR GRILLE, WHITE FINISH.
13
12/6
14
15
16
12
18/12
12/12
17
24/12
18
36/12
0 - 100
0 - 200
0 - 300
0 - 400
0 - 600
R3
36/18 0 - 900
36/24 0 - 1,200
19
20
21
%%UTYPE R4%%U: KRUEGER MODEL 6690 STEEL PERFORATED FACE RETURN WITH ROUND NECK FOR DUCTED APPLICATIONS, FRAME 23 FOR LAY-IN CEILINGS, FRAME 22 FOR GYP. BOARD CEILINGS, WHITE FINISH.
R4
22
24/24 - 8" 0 - 225
24/24 - 10" 0 - 350
24/24 - 12" 0 - 500
24/24 - 14" 0 - 700
24/24 - 16" 0 - 900
MECHANICAL EQUIPMENT SCHEDULE
ITEM DESCRIPTION
VOLT PH
ELEC. DATA
RPM
FAN
.25
ESP
FAN SCHEDULE
EF
1
ITEM
MODEL
MANUFACTURER/ CFM
WATTS
OPERATING
WEIGHT (LBS) NOTES
80 900 28.7 115 1 15
1
%%UNOTES:
1
PROVIDE RUBBER IN SHEAR VIBRATION ISOLATORS, WHITE PLASTIC GRILLE, BACKDRAFT DAMPER, AND PRE-WIRED DISCONNECT.
TOILET EXHAUST
PLAN/
SERVICE
LOCATION/
GC-146
COOK/ 13-1/4"W X 14-3/4"L X 8-3/8" TALL
DIMENSIONS
OVERALL
2 FAN TO BE INTERLOCKED TO OPERATE VIA TOILETROOM LIGHTSWITCH.
2
.35
EF
2
150 1,113 62.2 115 1 25 1
DIRTY LAB EXHAUST
PLAN/
GC-188
COOK/ 15-1/2"W X 13-1/4"L X 6-11/16" TALL 3
3 FAN TO OPERATE CONTINUOUSLY.
4 PROVIDE FAN SPEED CONTROL
SONES
FAN
MAX MAX
3
14/6 5 4
10/6
10/4
10/3 0 - 120
0 - 170
0 - 250
0 - 340
16 S4
17
18
19
%%UTYPE S3%%U: KRUEGER MODEL 880H DOUBLE DEFLECTION STEEL SUPPLY GRILL, 3/4" BLADE SPACING, OBD, WHITE FINISH. USE CONCEALED MOUNTING IN PUBLIC AREAS.
%%UTYPE S4%%U: KRUEGER MODEL DMGDU DOUBLE DEFLECTION STEEL DUCT MOUNTED SUPPLY GRILLE, 3/4" BLADE SPACING, OBD, CLEAR ANODIZED FINISH.
%%UTYPE S2%%U: KRUEGER MODEL SH 12"X12" STEEL LOUVERED PANEL DIFFUSER, NON-ADJUSTABLE 4-WAY HORIZONTAL THROW, WHITE FINISH, SQUARE NECK, FACE OPERATED OPPOSED BLADE STEEL DAMPER. PROVIDE
12" X 12" X 12" SHEET METAL CAN FOR SIDE DUCT CONNECTION PER DIFFUSER MOUNTING DETAIL 2/M4.1. FRAME 21 FOR GYP. BOARD CEILINGS.
12/12 - 8"~
12/12 - 10"~
6/6 - 6"~
0 - 410
0 - 600
0 - 230 S2
%%UTYPE S5%%U: KRUEGER MODEL TAD STEEL PERFORATED FACE, LAMINAR, NON-ASPARATING DIFFUSER, WHITE FINISH. PROVIDE SURFACE MOUNT FRAME FOR GYP CEILINGS AND T-BAR FRAME FOR LAY-IN CEILINGS
WHERE REQUIRED.
20 12/48 - 8" 0 - 340 S5
AC
2.0T CARRI
AC
0.5T CARRI
.35
EF
3
150 1,113 62.2 115 1 25 1
BREAKROOM EXHAUST
PLAN/
GC-188
COOK/ 5 15-1/2"W X 13-1/4"L X 6-11/16" TALL 4 5
5 FAN TO OPERATE VIA SEPARATE WALL SWITCH
6 CEILING MOUNTED DIRECT DRIVE FAN WITH ALUMINUM GRILLE, FAN SPEED CONTROL, RUBBER IN SHEAR VIBRATION ISOLATORS AND NEMA 1 PRE-WIRED DISCONNECT SWITCH.
PROVIDE REVERSE ACTING THERMOSTAT SET TO TURN FAN ON AT 85 DEG F AND OFF AT 80 DEG F.
.3
EF
4
600 1,375 195 115 1 50
EQUIP ROOM EXHAUST
PLAN/
GC-720
COOK/ 5 17"W X 11-7/8"L X 11-7/8" TALL 6
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
M3.3
NONE
MECHANICAL SCHEDULES
Page 25 of 28
GRADE/ 18 14.0 R-410 95 200 1
F-3 9.0 47.5 11.7 20 208/1
GRADE/
F-11
GRADE/
F-12
CU
F-13
GRADE/
F-13
GRADE/
F-2
CARRIER/ GRADE/ 36 14.0 R-410 95 200 31-3/16" X 31-3/16" X 25-5/16" TALL 1
24ACC436 F-1 13.6 79.0 18.1 30 208/1
23-1/8" X 23-1/8" X 25-5/16" TALL
24ACC436 CARRIER/ 36 14.0 R-410 95 13.6 79.0 18.1 30 208/1 200 31-3/16" X 31-3/16" X 25-5/16" TALL 1
CARRIER/
24ACC418
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ GRADE/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
GRADE/
F-6
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ 24 14.0 R-410 95 10.9 62.9 14.1 20 208/1 200 25-3/4" X 25-3/4" X 25-5/16" TALL 1
24ACC424
1
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1
24ACC418
CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL
24ACC418
CU
F-14
CARRIER/ GRADE/ 36 14.0 R-410 95 200 31-3/16" X 31-3/16" X 25-5/16" TALL 1
24ACC436 F-14 13.6 79.0 18.1 30 208/1
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
M3.2
NONE
MECHANICAL SCHEDULES
Page 24 of 28
2
F
3
F
4
RECOVERY
MEZZANINE/
CORE RECEPTION
MEZZANINE/
CORE OFFICE AND EXAM
MEZZANINE/
UNIT CONFIGURED FOR UPFLOW, DOWNFLOW, OR HORIZONTAL INSTALLATION AS INDICATED ON PLANS.
1 2 3 4 5
F
5 CORE OFFICE AND EXAM
MEZZANINE/
1 2 3 4 5
F
6 ULTRASOUND
MEZZANINE/
F
NORTH EXAM PERIMETER
MEZZANINE/
1 2 3 4
F
8 PROCEDURE 1502
MEZZANINE/
1 2 3 4 5
F
9 PROCEDURE 1505
MEZZANINE/
1 2 3 4
F
10 PROCEDURE 1506
MEZZANINE/
F
11 CLEAN-DIRTY LABS
MEZZANINE/
F
12 EDUCATION OFFICE
MEZZANINE/
1 2 3 4
1 2 3 4
1 2 3 4 5
1 2 3 4 5
F
13 NORTHWEST PERIMETER
MEZZANINE/ 1 2 3 4
1,200 .50 3/4 120/1 300
FURNACE WITH CNPV DX COIL 36 80/57 95 190 11.7 15 29-1/2" DEEP X 21" WIDE X 35" TALL 1 2 3 4
CARRIER/59SC2C080S21--20 80 75 14
1 2 3 4
1,200 .50 3/4 120/1 300
FURNACE WITH CNPV DX COIL 36 80/57 95 11.7 15 29-1/2" DEEP X 21" WIDE X 35" TALL 1 2 3 4
CARRIER/59SC2C080S21--20 80 75 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 24 80/57 95 800 .50 1/2 11.7 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C060S17--16 60 56 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL
CARRIER/59SC2C040S17--12 40 37 14
220
65
60
115
70
65
80
80
80
60
60
5
5
5
5
5
5
5
5
6 PROVIDE CARRIER GAPAAXCC1625 AIR PURIFICATION UNIT WITH MERV 15 FILTER AND GERMICIDAL AIR TREATMENT SYSTEM CAPABLE OF REMOVING OR KILLING 99% OF ALL VIRUSES, BACTERIA, AND FUNGI. PHYSICAL
DATA: 17-1/2"W X 25-1/4"D X 11-1/8"TALL. ELECTRICAL: 115/60/1 VAC, 18 WATTS WITH POWER TO BE CONNECTED TO FURNACE.
6
6
6
FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL 6
CARRIER/59SC2C040S17--12 40 37 14 150
F
14 EDUCATION
MEZZANINE/ 1,200 .50 3/4 230 120/1 300
FURNACE WITH CNPV DX COIL 36 80/57 95 11.7 15 29-1/2" DEEP X 21" WIDE X 35" TALL 1 2 3 4
CARRIER/59SC2C080S21--20 80 75 14 5
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
M3.1
NONE
MECHANICAL SCHEDULES
Page 23 of 28
M2.2E
AS NOTED
MECHANICAL MEZZANINE
PLAN - EAST
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
Page 22 of 28
9 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 8"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
10 11 \\pxsm1,pxsm1,t3;{\Fsimplex|t3;{\Fsimplex|c0;\W1;NEW AC c0;UNIT \W1;INSTALLED NEW ON FURNACE WALL ABOVE DOOR INSTALLED PER MANUFACTURER'S ON MEZZANINE INSTALLATION INSTRUCTIONS
FLOOR, WITH CONNECT CONDENSING UNIT 10"MOUNTED OA TO ON RETURN GRADE. EXTEND AIR REFRIGERANT AND EXTEND PIPING FROM UP CONDENSING THROUGH UNIT TO ROOF. FAN COIL UNIT RE: INSTALLED VERTICAL
PER MANUFACTURER'S UPFLOW INSTALLATION FURNACE INSTRUCTIONS. DETAIL } 4, 1/M4.3}
12 \pxsm1,t3;{\Fsimplex|c0;\W1;INSULATE ALL DUCTS ROUTED THROUGH ATTIC WITH R12 INSULATION.}
13 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE 1" GAP AT BOTTOM OF DOOR FOR AIR TRANSFER.}
{DEMO NOTES:
1. REMOVE ALL EXISTING HVAC EQUIPMENT EXCEPT FOR EXHAUST FAN AT MEZZANINE LEVEL BATHROOM.}
14 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 10"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
M2.2W
AS NOTED
MECHANICAL MEZZANINE
PLAN - WEST
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
Page 21 of 28
OFFICE
SCALE: 1" = 4'-0"
MECHANICAL PLAN - EAST
1
3
3 3 3
3 3 3 3
3
12"
14"
5
T
16/10
16/12
16/10
10"RA
16/12
T
T
T
16/12
16/10
14/8
12"
8"
5
T
10"RA
16/14 RA
16/12 SA
T
10
3
T
T
NOTES
1 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 4"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
2 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 8"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.}
3 \pxsm1,t3;{\Fsimplex|c0;\W1;CONDENSING UNIT INSTALLED AT GRADE, EXTEND REFRIGERANT PIPING FROM CONDENSING UNIT TO FURNACE/FAN COIL ACCORDING TO MANUFACTURER'S INSTALLATION INSTRUCTIONS.}
4 \pxsm1,t3;{\Fsimplex|c0;\W1;14/8 RA DUCT DOWN IN CHASE TO INLET GRILLE AT 6" AFF.}
5 \pxsm1,t3;{\Fsimplex|c0;\W1;DUCT MOUNTED DIFFUSER MOUNTED TO SIDE OF DUCT ROTATED 30 DEG DOWN FROM HORIZONTAL. }
6 \pxsm1,t3;{\Fsimplex|c0;\W1;DUCT ROUTED BETWEEN JOIST, RUN-OUTS FROM MAINS TO DIFFUSERS THROUGH OPEN WEB JOISTS.}
\pxsm1,t3;{\Fsimplex|c0;\W1;DUCT ROUTED BETWEEN JOIST, RUN-OUTS FROM MAINS TO DIFFUSERS THROUGH OPEN WEB JOISTS. NO DUCT LINER TO BE USED IN SYSTEMS SERVING PROCEDURE ROOMS.}
8 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE BALANCE DAMPER WITH REMOTE OPERATOR. RE: REMOTE DAMPER CONTROL DETAIL 3/M4.2}
9 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE 1" GAP AT BOTTOM OF DOOR FOR AIR TRANSFER.}
10 11 \\pxsm1,pxsm1,t3;{\Fsimplex|c0;t3;\W1;NEW {\AC Fsimplex|UNIT INSTALLED IN CEILING c0;PER \W1;MANUFACTURER'S SPIRAL INSTALLATION DUCT INSTRUCTIONS WITH PREPARED CONDENSING UNIT
MOUNTED AT FOR GRADE. EXTEND PAINTING, REFRIGERANT PIPING FROM HERCULES CONDENSING UNIT TO FAN COIL PAINTLOCK UNIT INSTALLED PER MANUFACTURER'S FINISH INSTALLATION OR INSTRUCTIONS. EQUAL.}
}
{DEMO NOTES:
1. REMOVE ALL EXISTING HVAC EQUIPMENT EXCEPT FOR EXHAUST FAN AT
M2.1E
AS NOTED
MECHANICAL
PLAN - EAST
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
Page 20 of 28
M2.1W MECHANICAL PLAN - WEST
M2.2E MECHANICAL MEZZANINE PLAN - EAST
M2.2W MECHANICAL MEZZANINE PLAN - WEST
BDD
REFRIGERANT SUCTION
RL REFRIGERANT LIQUID
RS
RL
RS
AFF ABOVE FINISHED FLOOR
OBD
BDD
SW SIDEWALL DIFFUSER
BACKDRAFT DAMPER
OPPOSED BLADE DAMPER
DESCRIPTION
LEGEND
ABBR SYMBOL
DD
F S
S
T
F
DD
S
T-STAT
FLFD
FSD
DUCT MOUNTED SMOKE DETECTOR
SPACE SENSOR W/ PLUG-IN PORT
COMBINATION FIRE/SMOKE DAMPER
THERMOSTAT
FUSIBLE LINK FIRE DAMPER
M
RA
SA
RE-D
AUTO D
MVD
WC
OA
GBS
ESP
EA
EXTERNAL STATIC PRESSURE
GALVANIZED BIRD SCREEN
WATER COLUMN
MVD WITH REMOTE CEILING OPERATOR
SUPPLY AIR
RETURN AIR
EXHAUST AIR
OUTSIDE AIR
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
UNO
TSP TOTAL STATIC PRESSURE
UNLESS NOTED OTHERWISE
M4.2 MECHANICAL DETAILS
MECHANICAL SPECIFICATIONS
SUPPLY, RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED STEEL PER SMACNA DUCT CONSTRUCTION
STANDARDS. SUPPLY, RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED FOR 2" W.C. STATIC PRESSURE. SPIRAL
LOCK-FORMED ROUND DUCT MAY BE UTILIZED WHERE SPACE ALLOWS. TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL BE SEALED
AIR-TIGHT WITH MASTIC, MASTIC SHALL BE APPLIED ONLY TO THE INSIDE OF EXPOSED DUCTWORK. RADIUSED ELBOWS (R/D=1.5) OR MITERED
ELBOWS WITH SINGLE THICKNESS TURNING VANES SHALL BE UTILIZED WHERE POSSIBLE. TURNING VANES SHALL BE SUPPORTED AT INTERVALS
OF 36" MAXIMUM. TURNING VANE RUNNERS SHALL HAVE A VANE IN EVERY SLOT AND SHALL CONFORM TO SMACNA DUCT CONSTRUCTION
STANDARDS FOR STANDARD SPACING.
INSULATED, FACTORY FABRICATED, FLEXIBLE DUCTWORK MAY BE UTILIZED AT RUNOUTS TO AIR DIFFUSERS WHERE DUCTWORK IS CONCEALED
ABOVE CEILINGS. FLEXIBLE DUCTWORK SHALL CONSIST OF AN EXTERIOR REINFORCED LAMINATED VAPOR BARRIER, R-6.0 MINIMUM FIBERGLASS
INSULATION AND INTERIOR VINYL LINER WITH SPRING STEEL WIRE HELIX. VINYL LINER SHALL NOT BE PERFORATED. FLEXIBLE DUCT ASSEMBLY
SHALL HAVE A FLAME SPREAD/SMOKE DEVELOPED RATING OF 25/50 OR LESS. FLEXIBLE DUCT TO FLEXIBLE DUCT CONNECTIONS SHALL BE MADE
WITH FACTORY FABRICATED STEEL COLLARS. FLEXIBLE DUCT SHALL BE SECURED TO RIGID DUCTWORK AND AIR DEVICES WITH SCREWS AND
DRAWBANDS. LENGTH OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO 5' AND SHALL NOT BE COMPRESSED. FLEXIBLE DUCTWORK SHALL NOT BE
USED FOR ELBOWS. FLEXIBLE DUCT SHALL NOT BE USED ABOVE INACCESSIBLE CEILINGS. FLEXIBLE DUCT SHALL NOT PASS THROUGH WALLS.
ALL SUPPLY AND RETURN RECTANGULAR DUCTWORK SHALL BE PROVIDED WITH DUCT LINER (INSIDE THE DUCT): ONE INCH THICK, RESIN
BONDED GLASS FIBER, IMMOBILIZED, EPA-REGISTERED ANTIMICROBIAL AGENT COATING ON AIR STREAM SURFACE, RATED BY MANUFACTURER
FOR AT LEAST 4000 FPM AND MEETING THE REQUIREMENTS OF ASTM C1071 TYPE I. FIRE RESISTANCE SHALL MEET REQUIREMENTS OF NFPA
90A. FLAME SPREAD RATING NOT TO EXCEED 25. FUEL CONTRIBUTION AND SMOKE DEVELOPMENT NOT TO EXCEED 50. NOISE REDUCTION
COEFFICIENT (NRC) OF NOT LESS THAN 0.60 WHEN TESTED IN ACCORDANCE WITH ASTM C423 USING AN "A" MOUNTING OR A MINIMUM OF 0.70
USING AN "F" MOUNTING. K VALUE NOT MORE THAN 0.26 BTUH PER SQUARE FOOT PER DEG. F AT 75 DEG. F OR AN "R" VALUE OF 4. MAXIMUM
ABSOLUTE ROUGHNESS FACTOR PER FOOT OF .004
SUPPLY AND RETURN AIR DUCTWORK SHALL BE INSULATED WITH R-6 INSULATION WHEN LOCATED IN UNCONDITIONED SPACES WITHIN THE
BUILDING ENVELOPE AND R-12 WHEN LOCATED OUTSIDE OF THE BUILDING. OUTSIDE AIR INTAKE DUCTS INSTALLED IN CONDITIONED AREAS
SHALL BE INSULATED WITH R-3.5 INSULATION. DUCT INSULATION TO BE FLEXIBLE FIBERGLASS WITH FOIL SCRIM FACING. INSULATION SHALL
HAVE A MAXIMUM CONDUCTIVITY, K-VALUE, OF 0.29 AT 75°F AND HAVE FLAME SPREAD/SMOKE DEVELOPED RATING OF 25/50 OR LESS.
INSULATION SHALL BE SECURED WITH WIRE TIES AT 12" ON CENTER OR WITH SELF-SEALING LAP AND TAPE JOINTS 3" ON CENTER AT FITTINGS.
JOINTS SHALL BE COVERED WITH 3" WIDE FOIL REINFORCED KRAFT TAPE. ADHESIVE OR MECHANICAL FASTENERS SHALL BE USED WHERE
NECESSARY TO PREVENT SAGGING. VAPOR BARRIER PENETRATIONS BY MECHANICAL FASTENERS SHALL BE SEALED WITH VAPOR BARRIER
ADHESIVE. INSULATION SHALL STOP AND POINT AROUND ACCESS DOORS AND DAMPER OPERATORS TO ALLOW OPERATION WITHOUT
DISTURBING WRAPPING.
DUCT HANGERS SHALL BE CONSTRUCTED OF GALVANIZED STEEL. DUCTS SHALL BE SUPPORTED AND CONNECTED TO THE STRUCTURE PER
SMACNA DUCT CONSTRUCTION STANDARDS. HANGERS AND SUPPORTS FOR GREASE DUCT SHALL BE OF NONCOMBUSTIBLE MATERIALS.
FLEXIBLE DUCTS SHALL BE SUPPORTED WITH GALVANIZED STRAPS.
HEAVY FLEXIBLE CONNECTIONS SHALL BE FURNISHED AND INSTALLED AT DUCT CONNECTIONS TO FANS AND AIR HANDLING UNITS EXCEPT HIGH
TEMPERATURE KITCHEN HOOD EXHAUST FANS. FLEXIBLE CONNECTIONS SHALL BE 6" MINIMUM AND 10" MAXIMUM IN LENGTH. MATERIAL FOR
INTERIOR INSTALLATIONS SHALL BE VENTFLEX MANUFACTURED BY VENTFABRICS, EXCELON MANUFACTURED BY DURO-DYNE OR APPROVED
EQUAL. MATERIAL FOR EXTERIOR INSTALLATIONS SHALL BE VENTLON MANUFACTURED BY VENTFABRICS, DUROLON MANUFACTURED BY
DURO-DYNE OR APPROVED EQUAL.
MANUAL VOLUME DAMPERS SHALL BE FURNISHED AND INSTALLED WHERE INDICATED AT SUPPLY AIR DUCT RUNOUTS TO AIR DIFFUSERS AND
GRILLES AS NEAR AS POSSIBLE TO THE TRUNK DUCT. MANUAL VOLUME DAMPERS FOR RECTANGULAR DUCT SHALL BE CONSTRUCTED OF 16
GAUGE GALVANIZED STEEL AND BE THE OPPOSED BLADE TYPE. MANUAL VOLUME DAMPERS FOR ROUND DUCT SHALL BE CONSTRUCTED OF 16
GAUGE GALVANIZED STEEL AND BE THE SINGLE BLADE TYPE. DAMPER BEARINGS SHALL BE NYLON. STAND-OFFS TO OUTSIDE OF INSULATION
SHALL BE PROVIDED FOR MANUAL VOLUME DAMPERS IN INSULATED DUCT. LOCKING AND INDICATING QUADRANTS SHALL BE PROVIDED WHERE
DAMPER IS ACCESSIBLE. REMOTE CEILING OPERATORS SHALL BE FURNISHED AND INSTALLED FOR DAMPERS ABOVE INACCESSIBLE CEILINGS.
OPERATORS SHALL BE GEAR AND LINKAGE TYPE EQUAL TO YOUNG REGULATOR WITH CHROME PLATED CEILING ESCUTCHEON AND COVER
PLATE.
AIR DEVICES SHALL BE AS SCHEDULED. EXPOSED SCREWS SHALL BE THE FINISHING TYPE AND PAINTED TO MATCH THE AIR DEVICE. SQUARE TO
ROUND ADAPTORS SHALL BE PROVIDED WHERE REQUIRED FOR AIR DEVICES IN CEILINGS. AIR DEVICES SHALL BE FINISHED WITH WHITE BAKED
ENAMEL UNLESS NOTED OTHERWISE. AIR DEVICES SHALL BE SECURED TO T-BAR CEILINGS WHERE APPLICABLE.
REFRIGERANT PIPING SHALL BE ASTM B 280 TYPE ACR COPPER TUBING WITH B16.22 WROUGHT COPPER FITTINGS. COPPER TUBING SHALL BE
BRAZED WITH AWS A5.8 BCuP SILVER BASED FILLER METAL. REFRIGERANT PIPING SYSTEM, INCLUDING FITTINGS, VALVES AND APPURTENANCES
SHALL BE TESTED FOR LEAKAGE AT 200 PSI WORKING PRESSURE WITH DRY NITROGEN.
INSULATE ALL REFRIGERANT SUCTION GAS AND LIQUID DISCHARGE TUBING WITH 1/2" MINIMUM THICKNESS FLEXIBLE CLOSED CELL
ELASTOMERIC INSULATION. PROVIDE TYPE R-374 PROTECTIVE COATING (2 COATS MINIMUM) TO INSULATION INSTALLED OUTSIDE OF BUILDING
WHERE EXPOSED TO ATMOSPHERE.
MECHANICAL EQUIPMENT SHALL BE SECURED AND INSTALLED PER MANUFACTURERS RECOMMENDATIONS AND APPLICABLE SECTIONS OF THE
JURISDICTIONAL BUILDING AND MECHANICAL CODES.
MECHANICAL EQUIPMENT SHALL BE IDENTIFIED WITH BAKELITE NAMEPLATES. COLOR CODING OF NAMEPLATES AND IDENTIFICATION
INFORMATION SHALL BE COORDINATED WITH THE OWNER.
AN INDEPENDENT TEST AND BALANCE FIRM WHICH IS AABC OR NEBB CERTIFIED SHALL BE RETAINED FOR CHECK/TEST-START-UP AND TESTING
M4.3 MECHANICAL DETAILS
M0.0
NONE
MECHANICAL LEGEND
AND NOTES
MOEN ENGINEERING CONSULTANTS INC
4640 PECOS ST., UNIT F
DENVER, CO 80211
P: (303)907-4285
SHEET NUMBER:
DATE:
SCALE:
SHEET TITLE:
REVISIONS:
Miller DesignWorks
1261 York Street
Denver, CO 80206
PH 303-480-5212
www.millerdw.com
TENANT IMPROVEMENT
825 S. SHIELDS STREET
FORT COLLINS, COLORADO
06/04/18
C MILLER DESIGNWORKS, INC 2018
CONSTRUCTION DOCUMENTS
Page 18 of 28
Motor Amps 1 0.4 Amps
SP In Actual 0.0 in. wc
SP Out Actual ANA in. wc
Total SP Actual NM in. wc
Motor Data
Motor Manufacturer Greenheck
Motor HP 1/40 HP
Motor RPM 900 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 0.46 Amps
Sheave Data
Motor Sheave Make Direct Drive
L.H. Finn and Associates
Updated Phase 1 Report
Page 16 of 28
Outlet-06 1601 17 115 109 118 95 103
Totals: - - - 610 730 612 120 100
F-12 Supply Outlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 13 of 28
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1508 20 450 389 438 86 97
Totals: - - - 450 389 438 86 97
F-11 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 12 of 28
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1506 4 260 108 264 42 102
Inlet-B 1506 4 260 255 267 98 103
Totals: - - - 520 363 531 70 102
F-10 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 11 of 28
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1502 4 260 222 278 85 107
Inlet-B 1502 4 260 193 274 74 105
Totals: - - - 520 415 552 80 106
F-09 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 10 of 28
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1505 4 260 145 255 56 98
Inlet-B 1505 4 260 191 253 73 97
Totals: - - - 520 336 508 65 98
F-08 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 9 of 28
System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1308 18 130 156 120 120 92
Inlet-B 1501 3 200 133 185 67 93
Inlet-C 1411 3 200 159 187 80 94
Inlet-D 1409 18 70 122 66 174 94
Totals: - - - 600 570 558 95 93
F-06 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 7 of 28
Page 6 of 28
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Inlet-A 1301 3 150
Inlet-B 1401 3 135
Inlet-C 1201 3 115
Inlet-D 1203 18 200
Totals: - - - 600 0 0 0 0
F-04 Return Inlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 5 of 28
Totals: - - - 1225 0 0 0 0
F-02 Supply Outlet Summary
L.H. Finn and Associates
Updated Phase 1 Report
Page 4 of 28