HomeMy WebLinkAbout825 Shields St - Special Inspections/Field Verification - 02/13/2020Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 2/13/20 PROJECT 825 S. Shields St. Tenant Improvement 825 S. Shield St. Fort Collins, CO ***Updated Phase 1 Report*** ARCHITECT Miller Design Works 1261 York Street Denver, CO ENGINEER MEC 4640 Pecos Street Unit F Denver, CO CONTRACTOR Air Comfort, Inc 150 Rome Court Fort Collins, CO Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: 825 S. Shields St. Tenant Improvement ADDRESS: 825 S. Shields St. Fort Collins, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:2/13/20 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:2/13/20 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 2/13/20 CERTIFICATION EXPIRATION DATE: 3/31/2020 Table Of Contents PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Table Of Contents 1 Instrument Calibration Report.pdf............................................................................................................................ 1 2 Abbreviation Report.pdf............................................................................................................................................ 3 3 Fan Coil.................................................................................................................................................................... 4 3.1 F-01.................................................................................................................................................................... 4 3.2 F-02.................................................................................................................................................................... 4 3.3 F-03.................................................................................................................................................................... 5 3.4 F-04.................................................................................................................................................................... 5 3.5 F-05.................................................................................................................................................................... 6 3.6 F-06.................................................................................................................................................................... 7 3.7 F-07.................................................................................................................................................................... 8 3.8 F-08.................................................................................................................................................................... 9 3.9 F-09.................................................................................................................................................................... 10 3.10 F-10.................................................................................................................................................................. 11 3.11 F-11................................................................................................................................................................... 12 3.12 F-12.................................................................................................................................................................. 13 3.13 F-13.................................................................................................................................................................. 14 3.14 F-14.................................................................................................................................................................. 15 4 Fan Unit.................................................................................................................................................................... 16 4.1 EF-01.................................................................................................................................................................. 16 4.2 EF-02.................................................................................................................................................................. 16 4.3 EF-03.................................................................................................................................................................. 17 4.4 EF-04.................................................................................................................................................................. 17 5 6 - Mechanical Sheets............................................................................................................................................. 18 5.1 6 - Mechanical Sheets.PDF.pdf......................................................................................................................... 18 5.1.1 6 - Mechanical Sheets................................................................................................................................. 18 5.1.1.1 M00......................................................................................................................................................... 18 5.1.1.1.1 Layout1.............................................................................................................................................. 18 5.1.2 2018-07-12 PPRM FORT COLLINS - DELTA 2 REVISION - MECHANICAL S&S.PDF.pdf......................... 19 5.1.3 6 - Mechanical Sheets................................................................................................................................. 20 5.1.3.1 M21......................................................................................................................................................... 5.1.3.1.1 M2.1E................................................................................................................................................ 20 5.1.3.2 M22......................................................................................................................................................... 21 5.1.3.2.1 M2.2W................................................................................................................................................ 21 5.1.3.2.2 M2.2E................................................................................................................................................ 22 5.1.3.3 M31......................................................................................................................................................... 23 5.1.3.3.1 Layout1.............................................................................................................................................. 23 5.1.3.4 M32......................................................................................................................................................... 24 5.1.3.4.1 Layout1.............................................................................................................................................. 24 5.1.3.5 M33......................................................................................................................................................... 25 5.1.3.5.1 Layout1.............................................................................................................................................. 25 5.1.3.6 M41......................................................................................................................................................... 26 L.H. Finn and Associates Updated Phase 1 Report Table Of Contents PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore 5.1.3.6.1 Layout1.............................................................................................................................................. 26 5.1.3.7 M42......................................................................................................................................................... 27 5.1.3.7.1 Layout1.............................................................................................................................................. 27 5.2 2018-07-15 PPRM FORT COLLINS - CD - M43 S&S........................................................................................ 28 L.H. Finn and Associates Updated Phase 1 Report Manufacturer Model Serial Application Cal. Date Alnor HM-675 71841075 Hydronic Press. & Diff. Press. 12/18/2018 Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 11/7/2019 Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 5/13/2019 Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 11/6/2018 Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 7/7/2017 Cooper SH66A 92711016 Temperature Measurement 10/9/2017 Extech 461895 Q394479 Rotation Measurement 6/7/2018 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/8/2016 Extech 461895 L268576 Rotation Measurement 11/11/2019 Extech 461895 Q331990 Rotation Measurement 11/9/2018 Extech 461895 Q477125 Rotation Measurement 9/25/2015 Extech 461895 Q477126 Rotation Measurement 4/5/2016 Extech 461895 Q527632 Rotation Measurement 10/3/2017 Extech 461895 Q590099 Rotation Measurement 4/17/2017 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 11/5/2015 Fluke 336 97110539R Electrical Measurement 4/5/2016 Fluke 336 97110538R Electrical Measurement 9/29/2015 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 335 72990071 Electrical Measurement 11/5/2018 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 10/3/2017 Fluke 374 20030354 Electrical Measurement 6/4/2018 Fluke 324 41620416WS Electrical Measurement 11/11/2019 TSI 8322 55100720 Air Velocity Measurement 10/4/2017 Shortridge ADM-860C M05789 Digital Manometer 11/25/2015 Shortridge ADM-860C M06821 Digital Manometer 6/1/2018 Shortridge ADM-860C M07352 Digital Manometer 6/6/2016 Shortridge ADM-860C M09123 Digital Manometer 4/18/2016 Shortridge ADM-860C M09347 Digital Manometer 9/26/2015 Shortridge ADM-860C M10144 Digital Manometer 4/14/2017 Shortridge ADM-860C M10371 Digital Manometer 11/5/2015 Shortridge ADM-860C M11448 Digital Manometer 4/14/2017 Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 10/5/2015 Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 6/1/2018 Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Project: 825 S. Shield St. Tenant Improvement Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 1 of 28 Evergreen Telemetry S-PVF-1 1500177 Pressure Velocity Module 10/3/2017 Evergreen Telemetry S-PVF-1 1500176 Pressure Velocity Module 4/26/2019 Evergreen Telemetry S-PVF-1 1700352 Pressure Velocity Module 9/22/2017 Evergreen Telemetry S-PVF-1 1600314 Pressure Velocity Module 4/9/2018 Evergreen Telemetry S-PVF-1 1600319 Pressure Velocity Module 4/9/2018 Evergreen Telemetry S-PVF-1 1600317 Pressure Velocity Module 4/26/2019 Evergreen Telemetry S-PVF-1 1600323 Pressure Velocity Module 10/11/2019 Evergreen Telemetry S-PVF-1 1600324 Pressure Velocity Module 4/26/2019 Evergreen Telemetry S-PVF-1 1600321 Pressure Velocity Module 6/5/2018 Evergreen Telemetry S-PVF-1 1600322 Pressure Velocity Module 6/5/2018 Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 5/11/2017 Evergreen Telemetry S-PVF-1 1700214 Pressure Velocity Module 5/11/2017 Evergreen Telemetry S-PVF-1 1700215 Pressure Velocity Module 2/25/2019 Evergreen Telemetry S-PVF-1 1700216 Pressure Velocity Module 5/11/2017 Evergreen Telemetry S-PVF-1 1700217 Pressure Velocity Module 5/11/2017 Evergreen Telemetry S-PVF-1 1700218 Pressure Velocity Module 5/11/2017 Evergreen Telemetry S-PVF-1 1900188 Pressure Velocity Module 3/7/2019 Evergreen Telemetry S-PVF-1 1900138 Pressure Velocity Module 2/6/2019 Evergreen Telemetry RM-T-1 1700269 Radio Module 11/7/2019 Evergreen Telemetry RM-T-1 1600236 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1600235 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1600233 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1600234 Radio Module 10/10/2016 Evergreen Telemetry RM-T-1 1700260 Radio Module 4/21/2017 Evergreen Telemetry RM-T-1 1700261 Radio Module 4/21/2017 Evergreen Telemetry RM-T-1 1900172 Radio Module 2/12/2019 Evergreen Telemetry PR-T-1 1400257 Temperature Probe (Air) 11/7/2019 Evergreen Telemetry PR-T-1 1600237 Temperature Probe (Air) 10/10/2016 Evergreen Telemetry PR-T-1 1600247 Temperature Probe (Air) 10/10/2016 Evergreen Telemetry PR-T-1 1600246 Temperature Probe (Air) 10/10/2016 Evergreen Telemetry PR-T-1 1600244 Temperature Probe (Air) 10/10/2016 Evergreen Telemetry PR-T-1 1700260 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-1 1700261 Temperature Probe (Air) 4/21/2017 Evergreen Telemetry PR-T-4 1400132 Temperature Probe (Insertion) 5/17/2017 Evergreen Telemetry PR-T-4-6 1900119 Temperature Probe (Insertion) 1/23/2019 Evergreen Telemetry PR-T-5 1900172 Temperature Probe 2/12/2019 Evergreen Telemetry S-H-3-5" 1900155 Humidity Sensor 3/8/2019 Evergreen Telemetry S-H-3-5" 1500142 Humidity Sensor 5/18/2017 Evergreen Telemetry S-DP-250 1600125 Water Press. Sensing Module 5/22/2018 Fuji Porta Flow SO414581 Ultrasonic Water Flow Meter 9/26/2018 REMARKS: Not all equipment shown was used on this project. Project: 825 S. Shield St. Tenant Improvement INSTRUMENT CALIBRATION REPORT (Continue) Page 2 of 28 Project: 825 S. Shield St. Tenant Improvement Symbol Description Symbol Description A Airflow (L/S) NA Not Applicable AF Air Foil NI Not Installed ANA Access Not Available NIC Not In Contract BI Backward Incline NM Not Measurable CD Ceiling Diffuser NPT No Pressure Tap CFM Airflow (Cubic Feet / Minute) NR Not Readable DD Direct Drive NS Not Shown DWDI Double Width Double Inlet NT No Information Tag EAT Entering Air Temperature OD Outside Diameter EF Exhaust Fan RPM Revolution Per Minute EG Exhaust Grille SD Supply Diffuser ER Exhaust Register SNKL Snorkel ESP External Static Pressure SP Static Pressure EWT Entering Water Temperature SPD Static Pressure Drop FC Forward Curve SR Supply Register GPM Waterflow (Gallons / Minute) SWSI Single Width Single Inlet HC Heat Coil T Temperature ( F ) HEX Heat Exchanger TSP Total Static Pressure HRC Heat Recovery Coil VFD Variable Frequency Drive Hz Hertz VS Variable Speed ID Inside Diameter W Waterflow (L/S) In. WC Inches of Water Column LAT Leaving Air Temperature LWT Leaving Water Temperature REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 3 of 28 Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-01 Log: F-01 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 1200 CFM Outside Air CFM Design 190 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1112 18 200 Outlet-02 1113 18 200 Outlet-03 1113 18 200 Outlet-04 1113 18 200 Outlet-05 1113 18 200 Outlet-06 1113 18 200 Totals: - - - 1200 0 0 0 0 F-01 Supply Outlet Summary Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-02 Log: F-02 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 1200 CFM Outside Air CFM Design 220 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1309 18 175 Outlet-02 1309 18 175 Outlet-03 1309 18 175 Outlet-04 1309 18 175 Outlet-05 1309 18 175 Outlet-06 1309 18 175 Outlet-07 1309 18 175 Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-03 Log: F-03 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 600 CFM Outside Air CFM Design 65 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1114 5 240 Outlet-02 1109 5 200 Outlet-03 1104 5 160 Totals: - - - 600 0 0 0 0 F-03 Supply Outlet Summary Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-04 Log: F-04 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 600 CFM Outside Air CFM Design 60 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1301 5 150 Outlet-02 1401 5 135 Outlet-03 1201 5 115 Outlet-04 1203 2 200 Totals: - - - 600 0 0 0 0 F-04 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-05 Log: F-05 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 600 CFM Outside Air CFM Design 115 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1304 5 90 Outlet-02 1306 5 90 Outlet-03 1401 5 80 Outlet-04 1402 5 70 Outlet-05 1403 5 70 Outlet-06 1207 5 70 Outlet-07 1206 5 70 Outlet-08 1404 2 200 Totals: - - - 740 0 0 0 0 F-05 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1304 3 90 Inlet-B 1306 3 80 Inlet-C 1401 3 70 Inlet-D 1402 3 70 Inlet-E 1203 3 70 Inlet-F 1207 3 70 Inlet-G 1206 3 70 Inlet-H 1404 18 200 Totals: - - - 720 0 0 0 0 F-05 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/22/2020 SYSTEM/UNIT: F-06 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2D040E171112 Unit Serial Number 3719A67664 Filter Type Pleated Filter Qty 1 Filter Size 16x24x1 Test Data Total CFM Design 600 CFM Total CFM Actual 633 CFM Outside Air CFM Design 70 CFM Outside Air CFM Actual 75 CFM Return Air CFM Design 530 CFM Return Air CFM Actual 558 CFM Motor Volts T1-T2 122 Volts Amps T1 5.8 Amps Fan RPM Actual High Speed RPM Unit E.S.P. Actual 0.42 In. wc. E.S.P. In -0.14 In. wc. E.S.P. Out 0.28 In. wc. Motor Data Motor Manufacturer Broad-Ocean Motor HP 1/2 Motor RPM 1050 RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1308 2 130 280 136 215 105 Outlet-02 1501 5 200 287 209 144 105 Outlet-03 1411 5 200 149 212 75 106 Outlet-04 1409 5 70 103 76 147 109 Totals: - - - 600 819 633 137 106 F-06 Supply Outlet Summary Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-07 Log: F-07 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 800 CFM Outside Air CFM Design 65 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1406 2 130 Outlet-02 1406 2 75 Outlet-03 See Print 2 75 Outlet-04 1405 2 100 Outlet-05 1205 2 180 Outlet-06 1204 2 240 Totals: - - - 800 0 0 0 0 F-07 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1406 18 130 Inlet-B 1406 18 75 Inlet-C See Print 18 75 Inlet-D 1405 18 100 Inlet-E 1205 19 180 Inlet-F 1204 19 240 Totals: - - - 800 0 0 0 0 F-07 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 8 of 28 Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-08 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2D040E171112 Unit Serial Number 3119A60893 Filter Type Pleated Filter Qty 1 Filter Size 18x25x3 Test Data Total CFM Design 600 CFM Total CFM Actual 593 CFM Outside Air CFM Design 80 CFM Outside Air CFM Actual 85 CFM Return Air CFM Design 520 CFM Return Air CFM Actual 508 CFM Motor Volts T1-T2 121 Volts Amps T1 3.4 Amps Fan RPM Actual Medium High RPM Unit E.S.P. Actual 0.66 In. wc. E.S.P. In -0.03 In. wc. E.S.P. Out 0.63 In. wc. Motor Data Motor Manufacturer Broad-Ocean Motor HP 1/2 Motor RPM 1050 RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1502 20 300 156 294 52 98 Outlet-02 1502 20 300 163 299 54 100 Totals: - - - 600 319 593 53 99 F-08 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/22/2020 SYSTEM/UNIT: F-09 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2D040E171112 Unit Serial Number 3519A60178 Filter Type Pleated Filter Qty 1 Filter Size 18x25x3 Test Data Total CFM Design 600 CFM Total CFM Actual 638 CFM Outside Air CFM Design 80 CFM Outside Air CFM Actual 86 CFM Return Air CFM Design 520 CFM Return Air CFM Actual 552 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Medium High Speed RPM Unit E.S.P. Actual 0.31 In. wc. E.S.P. In -0.11 In. wc. E.S.P. Out 0.2 In. wc. Motor Data Motor Manufacturer Broad-Ocean Motor HP 1/2 Motor RPM 1050 RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1505 20 300 316 316 105 105 Outlet-02 1505 20 300 322 322 107 107 Totals: - - - 600 638 638 106 106 F-09 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/22/2020 SYSTEM/UNIT: F-10 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2D040E171112 Unit Serial Number 3519A60893 Filter Type Pleated Filter Qty 1 Filter Size 18x25x3 Test Data Total CFM Design 600 CFM Total CFM Actual 614 CFM Outside Air CFM Design 80 CFM Outside Air CFM Actual 83 CFM Return Air CFM Design 520 CFM Return Air CFM Actual 531 CFM Motor Volts T1-T2 121 Volts Amps T1 2.9 Amps Fan RPM Actual Medium High Speed RPM Unit E.S.P. Actual 0.24 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.22 In. wc. Motor Data Motor Manufacturer Broad-Ocean Motor HP 1/2 Motor RPM 1050 RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1506 20 300 268 303 89 101 Outlet-02 1506 20 300 273 311 91 104 Totals: - - - 600 541 614 90 102 F-10 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/22/2020 SYSTEM/UNIT: F-11 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2D040E171112 Unit Serial Number 3119A60843 Filter Type Pleated Filter Qty 1 Filter Size 18x25x3 Test Data Total CFM Design 600 CFM Total CFM Actual 593 CFM Outside Air CFM Design 150 CFM Outside Air CFM Actual 155 CFM Return Air CFM Design 450 CFM Return Air CFM Actual 438 CFM Motor Volts T1-T2 121 Volts Amps T1 3.3 Amps Fan RPM Actual Medium High Speed RPM Unit E.S.P. Actual 0.21 In. wc. E.S.P. In -0.13 In. wc. E.S.P. Out 0.08 In. wc. Motor Data Motor Manufacturer Broad-Ocean Motor HP 1/2 Motor RPM 1050 RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1508 2 300 575 298 192 99 Outlet-02 1508 2 300 27 295 9 98 Totals: - - - 600 602 593 100 99 F-11 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/22/2020 SYSTEM/UNIT: F-12 Log: F-12 1/15/2020 Emerson Moore Unit toltal based on Outlet summation. Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2D040E171112 Unit Serial Number 3519A60136 Filter Type Pleated Filter Qty 1 Filter Size 18x25x3 Test Data Total CFM Design 610 CFM Total CFM Actual 612 CFM Outside Air CFM Design 60 CFM Outside Air CFM Actual 155 CFM Return Air CFM Design 450 CFM Return Air CFM Actual 438 CFM Motor Volts T1-T2 123 Volts Amps T1 2.2 Amps Fan RPM Actual Medium High Speed RPM Unit E.S.P. Actual 0.21 In. wc. E.S.P. In -0.13 In. wc. E.S.P. Out 0.08 In. wc. Motor Data Motor Manufacturer Broad-Ocean Motor HP 1/2 Motor RPM 1050 RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1504 5 75 104 76 139 101 Outlet-02 1503 5 75 66 74 88 99 Outlet-03 1601 17 115 175 117 152 102 Outlet-04 1601 17 115 162 114 141 99 Outlet-05 1601 17 115 114 113 99 98 Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-13 Log: F-13 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 600 CFM Outside Air CFM Design 60 CFM System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 1106 2 80 Outlet-02 1107 2 50 Outlet-03 1102 8 260 Outlet-04 1103 2 210 Totals: - - - 600 0 0 0 0 F-13 Supply Outlet Summary System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1106 18 130 Inlet-B 1103 18 210 Inlet-C 1102 2 260 Totals: - - - 600 0 0 0 0 F-13 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 14 of 28 Fan Coil PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: F-14 Log: F-14 1/15/2020 Emerson Moore Unit to be balanced on phase 2. Test Data Total CFM Design 1200 CFM Outside Air CFM Design 230 CFM System/Unit Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 50 Outlet-02 100 Outlet-03 100 Outlet-04 140 Outlet-05 140 Outlet-06 140 Outlet-07 140 Outlet-08 115 Outlet-09 115 Outlet-10 75 Outlet-11 85 Totals: - - - 1200 0 0 0 0 F-14 Supply Outlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 15 of 28 Fan Unit PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: EF-01 Log: EF-01 1/22/2020 Emerson Moore Multiple EF-01s on site. Recorded values shown as range of operation between identical fans. Unit Data Fan Manufacturer Greenheck Fan Model Number SP-A125-QD Fan Arrangement DWDI Fan Discharge Vertical/Up Starter Data Installed Thermal Internal Test Data Total CFM Design 80 CFM Total CFM Actual 78-86 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 120-122 Volts Motor Amps 1 0.1 Amps SP In Actual 0.0 in. wc SP Out Actual ANA in. wc Total SP Actual NM in. wc Motor Data Motor Manufacturer Greenheck Motor RPM 1100 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 0.18 Amps Sheave Data Motor Sheave Make Direct Drive Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: EF-02 Log: EF-02 2/11/2020 Emerson Moore Fan slowed down to design CFM after installation of Speed Control. Unit Data Fan Manufacturer Greenheck Fan Model Number SP-A200-QD Fan Serial Number 16016915 Fan Type Forward Curve Fan Arrangement DWDI Fan Discharge Vertical/Up Starter Data Installed Thermal Internal Test Data Total CFM Design 150 CFM Total CFM Actual 155 CFM Fan RPM Actual Low Speed RPM Motor Volts 1 121 Volts Fan Unit PROJECT: LOCATION: 825 S. Shields St. Tenant Improvement Fort Collins , CO DATE: CONTACT: AUTHOR: 2/13/2020 Emerson Moore Emerson Moore Tested By: Emerson Moore Date: 1/15/2020 SYSTEM/UNIT: EF-03 Log: EF-03 1/15/2020 Emerson Moore Fan to be tested on Phase 2. Test Data Total CFM Design 150 CFM Tested By: Emerson Moore Date: 2/13/2020 SYSTEM/UNIT: EF-04 Unit Data Fan Manufacturer Greenheck Fan Model Number SP-A700-QD Fan Serial Number 15997155 Fan Type Forward Curve Fan Arrangement DWDI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 600 CFM Total CFM Actual 588 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 122 Volts Motor Amps 1 3.1 Amps SP In Actual 0.0 in. wc SP Out Actual ANA in. wc Total SP Actual NM in. wc Motor Data Motor Manufacturer Fasco Motor RPM 1100 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.5 Amps Sheave Data Motor Sheave Make Direct Drive L.H. Finn and Associates Updated Phase 1 Report Page 17 of 28 GENERAL NOTES 1.ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES, LOCAL CODES, AND OWNER'S STANDARDS INDICATED BY THE CONSTRUCTION DOCUMENTS. 2.MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE OWNER. 3.CONTRACTOR SHALL COORDINATE WORK INDICATED WITH PLUMBING, ELECTRICAL, STRUCTURAL, AND ARCHITECTURAL DIVISIONS. VERIFY FIT OF MECHANICAL SYSTEMS PRIOR TO FABRICATION. COORDINATE ALL CHASE, SLEEVE, AND SLAB SAWCUT/COREDRILL REQUIREMENTS BEFORE CONSTRUCTION. 4.PROVIDE ALL EQUIPMENT SCHEDULED OR INDICATED ON THE DRAWINGS BUT NOT INCLUDED WITHIN THE SPECIFICATIONS INCLUDING ANY REQUIRED BUT NOT LISTED MISC ITEMS NEEDED TO PROVIDE COMPLETELY OPERATIONAL SYSTEMS AS INDICATED WHETHER SPECIFICALLY CALLED FOR OR NOT. INSTALLATION SHALL CONFORM TO MANUFACTURERS RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE SUBMITTALS FOR ALL PROPOSED EQUIPMENT AND MATERIALS TO BE UTILIZED. PROVIDE OPERATION AND MAINTENANCE MANUAL FOR ALL SYSTEMS AND EQUIPMENT AT END OF PROJECT. 5.ELECTRICAL CHARACTERISTICS OF MECHANICAL EQUIPMENT SHALL BE VERIFIED WITH ELECTRICAL DRAWINGS AND ELECTRICAL CONTRACTOR PRIOR TO EQUIPMENT ORDER RELEASE. ADDITIONAL ELECTRICAL WORK RESULTING FROM EQUIPMENT SUBSTITUTION IS THE RESPONSIBILITY OF THIS CONTRACTOR. 6.ITEM DESIGNATIONS INDICATED HEREON ARE FOR PURPOSES OF THESE DOCUMENTS ONLY. CONTRACTOR SHALL VERIFY WITH OWNERS REPRESENTATIVE ACTUAL "TAGGING" INFORMATION TO BE PROVIDED FOR EACH ITEM OF MECHANICAL EQUIPMENT PRIOR TO NAMEPLATE ORDER RELEASE. 7.PROVIDE 18" X 18" MINIMUM ACCESS DOOR IN INACCESSIBLE CEILINGS AND WALLS FOR EQUIPMENT AND VALVES REQUIRING ACCESS OR ADJUSTMENT. COORDINATE LOCATIONS AND SUBMIT TO ARCHITECT FOR APPROVAL PRIOR TO BEGINNING WORK. 7.DUCT SIZES INDICATED ARE OUTSIDE DIMENSIONS, BRANCH RUN-OUT DUCTS TO DIFFUSERS AND GRILLES TO BE SAME SIZE AS DIFFUSER OR GRILLE CONNECTION SIZE UNLESS OTHERWISE NOTED. 8.LENGTH OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO 5'-0" MAX. HORIZONTAL RUN WITH ONLY ONE 90^ ELBOW PERMITTED. SECURE FLEXIBLE DUCTWORK WITH SCREWS & DRAWBANDS PER SMACNA STANDARDS. 9.PROVIDE CEILING OPERATORS FOR INACCESSIBLE MVD'S WHERE INDICATED, EQUAL TO YOUNG REGULATOR, REMOTE GEAR OPERATED, WITH CEILING ESCUTCHEON. 10.DUCT MOUNTED SMOKE DETECTORS SHALL BE ZERO VELOCITY TYPE WHERE INDICATED ON DRAWINGS. 11.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ACTUAL LOCATION OF GRILLES, DIFFUSERS, AND ACCESS DOORS IN CEILING. SECURE DIFFUSERS & GRILLES TO T-BAR CEILINGS WHERE APPLICABLE. SUBMIT SHOP DWG. FOR APPROVAL PRIOR TO BEGINNING WORK. 12.AT THE COMPLETION OF WORK, PROVIDE TESTING AND BALANCING SERVICES FOR MECHANICAL SYSTEM. SUBMIT WRITTEN REPORT TO ARCHITECT LISTING SYSTEM AIRFLOWS, ELECTRIC DATA, TEMPERATURES, AND PRESSURE DROPS. AIR BALANCE REPORT REQUIRED PRIOR TO SCHEDULING FINAL MECHANICAL INSPECTION. 13.WHERE PIPES PASS THROUGH FIRE-RATED FLOOR OR WALLS, SEAL WITH MATERIALS EQUAL TO 3M FIRE BARRIER, MEETING TESTING PER ASTM-E-814 (UL 1479). USE CAULK OR PUTTY TYPE. ALL EXTERIOR WALL AND ROOF PENETRATIONS SHALL BE SEALED WATERPROOF. 14.AT THE COMPLETION OF THE WORK AND PRIOR TO FINAL ACCEPTANCE, ALL PARTS OF THE WORK INSTALLED UNDER THIS SPECIFICATION SHALL BE THOROUGHLY CLEANED. 15.ALL EQUIPMENT, MATERIALS, AND INSTALLATION IS TO BE WARRANTEED FOR ONE YEAR TO BE FREE FROM DEFECT. PROVIDE WRITTEN WARRANTY TO OWNER. 16.THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR TO MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM HIS WORK. 17.THIS CONTRACTOR SHALL FIELD VERIFY LOCATIONS AND SIZES OF ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, ELECTRICAL CONDUIT, STRUCTURAL MEMBERS, ETC., PRIOR TO STARTING OF CONSTRUCTION. COORDINATE CONFLICTS WITH THE GENERAL CONTRACTOR. 18.THIS CONTRACTOR SHALL COORDINATE ALL REQUIRED EXISTING BUILDING SERVICE SYSTEM OUTAGES WITH BUILDING MANAGEMENT. 19.ALL MECHANICAL SYSTEMS ARE REQUIRED TO BE INSTALLED PER BASE BUILDING REQUIREMENTS, LOCAL AND STATE JURISDICTIONAL CODES, ORDINANCES, AND APPLICABLE REGULATIONS. 20.PATCH AND REPAIR TO MATCH EXISTING, ANY WALL/CEILINGS TO BE ACCESSED TO ROUTE PIPING AND DUCTWORK. 21.EXISTING DUCTWORK, PIPING, AND EQUIPMENT TO REMAIN IS SHOWN LIGHT. NEW DUCTWORK, PIPING, AND EQUIPMENT IS SHOWN HEAVY. M0.0 MECHANICAL LEGEND AND NOTES SHEET NO. SHEET DESCRIPTION MECHANICAL SHEET INDEX ISSUE M3.1 MECHANICAL SCHEDULES M4.1 MECHANICAL DETAILS 06-04-18 CONSTRUCTION DOCUMENTS M3.2 MECHANICAL SCHEDULES M3.3 MECHANICAL SCHEDULES M2.1E MECHANICAL PLAN - EAST Page 19 of 28 D E F WATER 1604 SERVICE 1505 PROCEDURE 1603 STAIR 1406 CORRIDOR 1502 PROCEDURE PROCEDURE 1410 UTILITY BREAK 1503 ROOM PROCEDURE 1507 SUPPORT PROCEDURE 1508 SUPPORT 1602 UNISEX 1307 STORAGE UTILITY 1504 HALL 1501 CORRIDOR EDUCATION 1601 OFFICE 1506 PROCEDURE 1408 MEN 1407 WOMEN R.N. 1409 OFFICE 1411 ULTRASOUND 1306 ULTRASOUND 1405 WAITING 1404 CONSULT 1403 CONSULT 1402 CONSULT 1309 RECOVERY 1308 SCALE: 1" = 4'-0" MECHANICAL MEZZANINE PLAN - WEST 1 A B C D 4 3 2 1 RECOVERY OPEN TO UNDERSIDE OF ROOF WAITING ROOM OPEN TO UNDERSIDE OF ROOF VESTIBULE OPEN TO UNDERSIDE OF ROOF 2103 LANDING 2206 I.T. 2101 STAIR OPEN 2202 OFFICE 2203 UNISEX 2107 BREAK 2105 FILES 2104 MECHANICAL 2204 MECHANICAL 2201 MECHANICAL 2106 MECHANICAL 2102 MECHANICAL 1 13 4 3 3 4 3 10 11 T 12/12 14/14 8/12 T NOTES 1 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED HORIZONTALLY IN CEILING SPACE. CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: HORIZONTAL FURNACE DETAIL 6/M4.1} 3 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 1, 5/M4.1} 2 \pxsm1,t3;{\Fsimplex|c0;\W1;18/10 TRANSFER AIR OPENING AS HIGH IN WALL AS POSSIBLE, PROVIDE GRILLE ON EACH SIDE OF OPENING.} 4 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 1, 2/M4.2} 5 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 4"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} 6 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 2, 4/M4.2} \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 2, 5/M4.2} 8 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 3, 6/M4.2} D E F EDUCATION OFFICE OPEN TO UNDERSIDE OF ROOF RECOVERY OPEN TO UNDERSIDE OF ROOF 2307 EQUIPMENT 2206 2306 STAIR EDUCATION 2304 ENTRY EDUCATION 2302 OFFICE OPEN 2202 OFFICE 2305 MECHANICAL EDUCATION 2301 OFFICE 2303 MECHANICAL 2203 UNISEX 2205 MECHANICAL 2204 MECHANICAL SCALE: 1" = 4'-0" MECHANICAL MEZZANINE PLAN - EAST 1 1 3 6 4 10 T 8/12 T NOTES 1 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED HORIZONTALLY IN CEILING SPACE. CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: HORIZONTAL FURNACE DETAIL 6/M4.1} 3 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 1, 5/M4.1} 2 \pxsm1,t3;{\Fsimplex|c0;\W1;18/10 TRANSFER AIR OPENING AS HIGH IN WALL AS POSSIBLE, PROVIDE GRILLE ON EACH SIDE OF OPENING.} 4 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 8"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 1, 2/M4.2} 5 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 4"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} 6 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL DOWNFLOW FURNACE DETAIL 2, 4/M4.2} \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 2, 5/M4.2} 8 \pxsm1,t3;{\Fsimplex|c0;\W1;NEW FURNACE INSTALLED ON MEZZANINE FLOOR, CONNECT 10"OA TO RETURN AIR AND EXTEND UP THROUGH ROOF. RE: VERTICAL UPFLOW FURNACE DETAIL 3, 6/M4.2} 9 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 8"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} 10 11 \\pxsm1,pxsm1,t3;{\Fsimplex|t3;{\Fsimplex|c0;\W1;NEW AC c0;UNIT \W1;INSTALLED NEW ON FURNACE WALL ABOVE DOOR INSTALLED PER MANUFACTURER'S ON MEZZANINE INSTALLATION INSTRUCTIONS FLOOR, WITH CONNECT CONDENSING UNIT 10"MOUNTED OA TO ON RETURN GRADE. EXTEND AIR REFRIGERANT AND EXTEND PIPING FROM UP CONDENSING THROUGH UNIT TO ROOF. FAN COIL UNIT RE: INSTALLED VERTICAL PER MANUFACTURER'S UPFLOW INSTALLATION FURNACE INSTRUCTIONS. DETAIL } 4, 1/M4.3} 12 \pxsm1,t3;{\Fsimplex|c0;\W1;INSULATE ALL DUCTS ROUTED THROUGH ATTIC WITH R12 INSULATION.} 13 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE 1" GAP AT BOTTOM OF DOOR FOR AIR TRANSFER.} {DEMO NOTES: 1. REMOVE ALL EXISTING HVAC EQUIPMENT EXCEPT FOR EXHAUST FAN AT MEZZANINE LEVEL BATHROOM.} 14 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 10"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} SUPPLY FAN (IN. WC) ESP ITEM SERVICE LOCATION/ MODEL MANUFACTURER/ FURNACE SCHEDULE (NATURAL GAS HEATING - DX COOLING) CFM (LBS.) MIN. MOTOR HP VOLTS/PH WT. MAX OPER. HEATING CAPACITY COOLING CAPACITY (CFM) OA MINIMUM DIMENSIONS OVERALL NOTES 1 %%UNOTES: PROVIDE 1 STAGE FURNACE DESIGNED FOR SEALED COMBUSTION OPERATION UTILIZING PVC VENTING, PROVIDE CONDENSATE NEUTRALIZATION KIT, MANUFACTURER APPROVED CONCENTRIC VENT AND INTAKE TERMINATION. 2 PROVIDE FILTER RACK AND 1" MERV 8 DISPOSABLE FILTER. (DB/WB) EAT MBH (DB/WB) LAT (DEGREES F) AMBIENT TEMP CONDENSER (SEER) EFFICIENCY (MBH @ SL) OUTPUT (MBH @ SL) INPUT MINIMUM 3 FURNISH UNIT DESIGNED FOR HIGH ALTITUDE OPERATION (5000 FT). EVAPORATOR EVAPORATOR AMPACITY FUSE MAXIMUM 4 PROVIDE 24/7 PROGRAMMABLE THERMOSTAT WITH 5 DEG F DEADBAND BETWEEN HEATING AND COOLING AND 10 HOUR BATTERY BACKUP. AMPACITY CIRCUIT MINIMUM F 1 WAITING MEZZANINE/ (DB) EAT MIN. (DB) LAT MIN. 5 F CONDENSING UNIT SCHEDULE ITEM 1 %%UNOTES: PROVIDE CRANKCASE HEATER, ANTI-SHORT CYCLE TIMER, VIBRATION ISOLATION AND CONCRETE BASE & PAD, TXV, LONG LINE KIT, AND LOW AMBIENT (-10 DEGREES F) OPERATING ACCESSORIES. MANUFACTURER/ MODEL LOCATION/ SERVICE CAPACITY (MBH) DB (%%DF) EAT RLA LRA NOTES REFRIGERANT WEIGHT PHASE (LBS) MCA MOP VOLT/ COOLING EFFICIENCY (SEER) MINIMUM DIMENSIONS OVERALL MAX CU F-2 CU F-1 CU F-3 CU F-4 CU F-5 GRADE/ F-5 CU F-6 CU F-7 GRADE/ F-7 CU F-8 GRADE/ F-8 CU F-9 GRADE/ F-9 CU F-10 GRADE/ F-10 CU F-11 CU F-12 GRADE/ F-4 CFM ITEM MANUFACTURER/ MAX. HEATER (ELECTRIC) (KW) HEATING CAP. VOLTS/PHASE DIMENSIONS OVERALL (LBS.) WT. MAX. OPER. 1 %%UNOTES: FURNISH FACTORY INSTALLED DISCONNECT AND INTEGRAL TAMPER-PROOF THERMOSTAT SET AT 60 DEG F NOTES MODEL LOCATION/ SERVICE WALL/ 3.0 160 208/1 24 4-1/2" DEEP X 14-1/2" WIDE X 19-7/8" TALL 1 2 HEAT 2 FURNISH WITH RECESSED WALL BOX WHERE INSTALLED IN FRAMED WALLS AND SURFACE MOUNT BOX WHERE INSTALLED ON CONCRETE WALLS. INDEECO/ WCI CUH 3.0KW %%UTYPE R2%%U: DIFFUSER & REGISTER SPECIFICATIONS %%UTYPE R1%%U: %%URETURN/EXHAUST AIR %%USUPPLY AIR %%UTYPE S1%%U: DIFFUSER & REGISTER SCHEDULE SUPPLY AIR 13 18/10 14/14 12 22/6 8 9 10 11 18/6 14/6 10/6 6/6 2 12/12 - 8"~ 3 12/12 - 10"~ 4 5 6/6 - 6"~ ITEM NECK SIZE 1 6 0 - 1,020 R2 36/18 0 - 720 0 - 230 FLEXIBLE CONNECTION DETAIL NO SCALE 1 M4.1 3"-4" (10" MAX.) FAN OUTLET/INLET DIFFUSER MOUNTING DETAIL NO SCALE 2 M4.1 45 DEGREE TAKE-OFF DETAIL NO SCALE 3 M4.1 W 45%%d RL RS CONDENSING UNIT AT GRADE DETAIL NO SCALE 4 M4.1 VERTICAL DOWNFLOW FURNACE DETAIL 1 NO SCALE 5 M4.1 RS RL HORIZONTAL FURNACE DETAIL NO SCALE M4.1 RS RL M4.1 NONE MECHANICAL DETAILS MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS Page 26 of 28 EXPOSED SPIRAL DUCT HANGER DETAIL NO SCALE 1 M4.2 VERTICAL UPFLOW FURNACE DETAIL 1 NO SCALE 2 M4.2 RS RL REMOTE DAMPER CONTROL DETAIL NO SCALE 3 M4.2 PROVIDE CEILING OPERATORS FOR INACCESSIBLE MVD'S WHERE INDICATED, EQUAL TO YOUNG REGULATOR, REMOTE GEAR OPERATED, WITH CEILING ESCUTCHEON. VERTICAL DOWNFLOW FURNACE DETAIL 2 NO SCALE 4 M4.2 RS RL VERTICAL UPFLOW FURNACE DETAIL 2 NO SCALE 5 M4.2 RS RL VERTICAL UPFLOW FURNACE DETAIL 3 NO SCALE M4.2 RS RL M4.2 NONE MECHANICAL DETAILS MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS Page 27 of 28 Page 28 of 28 0 - 360 0 - 480 0 - 610 S3 8 9 10 11 0 - 930 0 - 2,100 12/12 18/18 22/18 TYPE 0 - 410 0 - 600 CFM RANGE 0 - 230 2 12/6 3 4 5 S1 ITEM 1 MODULE-NECK SIZE 6/6 6 0 - 300 0 - 600 0 - 1,100 TYPE 0 - 150 R1 CFM RANGE 0 - 1,375 RETURN/EXHAUST AIR 12/24 - 10/22 0 - 500 24/24 - 22/22 0 - 1,000 KRUEGER MODEL SHR 24"X24" STEEL LOUVERED PANEL DIFFUSER, NON-ADJUSTABLE 4-WAY HORIZONTAL THROW, WHITE FINISH, ROUND NECK. FRAME 23 FOR LAY-IN CEILINGS. FRAME 21 FOR GYP. BOARD CEILINGS. KRUEGER MODEL S85H, STEEL GRILLE, 1/2" BLADE SPACING, 35%%D BLADE ANGLE, WHITE FINISH, OBD. FRAME 23 FOR LAY IN CEILINGS. CONCEALED MOUNTING FOR GYP. BOARD CEILINGS. KRUEGER MODEL 6490 STEEL PERFORATED FACE RETURN WITH SQUARE NECK FOR DUCTED APPLICATIONS, FRAME 23 FOR LAY-IN CEILINGS, FRAME 22 FOR GYP. BOARD CEILINGS, WHITE FINISH. 14 22/10 0 - 1,120 15 24/10 0 - 1,220 18/10 0 - 700 18/8 0 - 600 %%UTYPE R3%%U: KRUEGER MODEL #600, STEEL SIGHT-PROOF TRANSFER AIR GRILLE, WHITE FINISH. 13 12/6 14 15 16 12 18/12 12/12 17 24/12 18 36/12 0 - 100 0 - 200 0 - 300 0 - 400 0 - 600 R3 36/18 0 - 900 36/24 0 - 1,200 19 20 21 %%UTYPE R4%%U: KRUEGER MODEL 6690 STEEL PERFORATED FACE RETURN WITH ROUND NECK FOR DUCTED APPLICATIONS, FRAME 23 FOR LAY-IN CEILINGS, FRAME 22 FOR GYP. BOARD CEILINGS, WHITE FINISH. R4 22 24/24 - 8" 0 - 225 24/24 - 10" 0 - 350 24/24 - 12" 0 - 500 24/24 - 14" 0 - 700 24/24 - 16" 0 - 900 MECHANICAL EQUIPMENT SCHEDULE ITEM DESCRIPTION VOLT PH ELEC. DATA RPM FAN .25 ESP FAN SCHEDULE EF 1 ITEM MODEL MANUFACTURER/ CFM WATTS OPERATING WEIGHT (LBS) NOTES 80 900 28.7 115 1 15 1 %%UNOTES: 1 PROVIDE RUBBER IN SHEAR VIBRATION ISOLATORS, WHITE PLASTIC GRILLE, BACKDRAFT DAMPER, AND PRE-WIRED DISCONNECT. TOILET EXHAUST PLAN/ SERVICE LOCATION/ GC-146 COOK/ 13-1/4"W X 14-3/4"L X 8-3/8" TALL DIMENSIONS OVERALL 2 FAN TO BE INTERLOCKED TO OPERATE VIA TOILETROOM LIGHTSWITCH. 2 .35 EF 2 150 1,113 62.2 115 1 25 1 DIRTY LAB EXHAUST PLAN/ GC-188 COOK/ 15-1/2"W X 13-1/4"L X 6-11/16" TALL 3 3 FAN TO OPERATE CONTINUOUSLY. 4 PROVIDE FAN SPEED CONTROL SONES FAN MAX MAX 3 14/6 5 4 10/6 10/4 10/3 0 - 120 0 - 170 0 - 250 0 - 340 16 S4 17 18 19 %%UTYPE S3%%U: KRUEGER MODEL 880H DOUBLE DEFLECTION STEEL SUPPLY GRILL, 3/4" BLADE SPACING, OBD, WHITE FINISH. USE CONCEALED MOUNTING IN PUBLIC AREAS. %%UTYPE S4%%U: KRUEGER MODEL DMGDU DOUBLE DEFLECTION STEEL DUCT MOUNTED SUPPLY GRILLE, 3/4" BLADE SPACING, OBD, CLEAR ANODIZED FINISH. %%UTYPE S2%%U: KRUEGER MODEL SH 12"X12" STEEL LOUVERED PANEL DIFFUSER, NON-ADJUSTABLE 4-WAY HORIZONTAL THROW, WHITE FINISH, SQUARE NECK, FACE OPERATED OPPOSED BLADE STEEL DAMPER. PROVIDE 12" X 12" X 12" SHEET METAL CAN FOR SIDE DUCT CONNECTION PER DIFFUSER MOUNTING DETAIL 2/M4.1. FRAME 21 FOR GYP. BOARD CEILINGS. 12/12 - 8"~ 12/12 - 10"~ 6/6 - 6"~ 0 - 410 0 - 600 0 - 230 S2 %%UTYPE S5%%U: KRUEGER MODEL TAD STEEL PERFORATED FACE, LAMINAR, NON-ASPARATING DIFFUSER, WHITE FINISH. PROVIDE SURFACE MOUNT FRAME FOR GYP CEILINGS AND T-BAR FRAME FOR LAY-IN CEILINGS WHERE REQUIRED. 20 12/48 - 8" 0 - 340 S5 AC 2.0T CARRI AC 0.5T CARRI .35 EF 3 150 1,113 62.2 115 1 25 1 BREAKROOM EXHAUST PLAN/ GC-188 COOK/ 5 15-1/2"W X 13-1/4"L X 6-11/16" TALL 4 5 5 FAN TO OPERATE VIA SEPARATE WALL SWITCH 6 CEILING MOUNTED DIRECT DRIVE FAN WITH ALUMINUM GRILLE, FAN SPEED CONTROL, RUBBER IN SHEAR VIBRATION ISOLATORS AND NEMA 1 PRE-WIRED DISCONNECT SWITCH. PROVIDE REVERSE ACTING THERMOSTAT SET TO TURN FAN ON AT 85 DEG F AND OFF AT 80 DEG F. .3 EF 4 600 1,375 195 115 1 50 EQUIP ROOM EXHAUST PLAN/ GC-720 COOK/ 5 17"W X 11-7/8"L X 11-7/8" TALL 6 MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS M3.3 NONE MECHANICAL SCHEDULES Page 25 of 28 GRADE/ 18 14.0 R-410 95 200 1 F-3 9.0 47.5 11.7 20 208/1 GRADE/ F-11 GRADE/ F-12 CU F-13 GRADE/ F-13 GRADE/ F-2 CARRIER/ GRADE/ 36 14.0 R-410 95 200 31-3/16" X 31-3/16" X 25-5/16" TALL 1 24ACC436 F-1 13.6 79.0 18.1 30 208/1 23-1/8" X 23-1/8" X 25-5/16" TALL 24ACC436 CARRIER/ 36 14.0 R-410 95 13.6 79.0 18.1 30 208/1 200 31-3/16" X 31-3/16" X 25-5/16" TALL 1 CARRIER/ 24ACC418 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ GRADE/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 GRADE/ F-6 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ 24 14.0 R-410 95 10.9 62.9 14.1 20 208/1 200 25-3/4" X 25-3/4" X 25-5/16" TALL 1 24ACC424 1 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 1 24ACC418 CARRIER/ 18 14.0 R-410 95 9.0 47.5 11.7 20 208/1 200 23-1/8" X 23-1/8" X 25-5/16" TALL 24ACC418 CU F-14 CARRIER/ GRADE/ 36 14.0 R-410 95 200 31-3/16" X 31-3/16" X 25-5/16" TALL 1 24ACC436 F-14 13.6 79.0 18.1 30 208/1 MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS M3.2 NONE MECHANICAL SCHEDULES Page 24 of 28 2 F 3 F 4 RECOVERY MEZZANINE/ CORE RECEPTION MEZZANINE/ CORE OFFICE AND EXAM MEZZANINE/ UNIT CONFIGURED FOR UPFLOW, DOWNFLOW, OR HORIZONTAL INSTALLATION AS INDICATED ON PLANS. 1 2 3 4 5 F 5 CORE OFFICE AND EXAM MEZZANINE/ 1 2 3 4 5 F 6 ULTRASOUND MEZZANINE/ F NORTH EXAM PERIMETER MEZZANINE/ 1 2 3 4 F 8 PROCEDURE 1502 MEZZANINE/ 1 2 3 4 5 F 9 PROCEDURE 1505 MEZZANINE/ 1 2 3 4 F 10 PROCEDURE 1506 MEZZANINE/ F 11 CLEAN-DIRTY LABS MEZZANINE/ F 12 EDUCATION OFFICE MEZZANINE/ 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 F 13 NORTHWEST PERIMETER MEZZANINE/ 1 2 3 4 1,200 .50 3/4 120/1 300 FURNACE WITH CNPV DX COIL 36 80/57 95 190 11.7 15 29-1/2" DEEP X 21" WIDE X 35" TALL 1 2 3 4 CARRIER/59SC2C080S21--20 80 75 14 1 2 3 4 1,200 .50 3/4 120/1 300 FURNACE WITH CNPV DX COIL 36 80/57 95 11.7 15 29-1/2" DEEP X 21" WIDE X 35" TALL 1 2 3 4 CARRIER/59SC2C080S21--20 80 75 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 24 80/57 95 800 .50 1/2 11.7 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C060S17--16 60 56 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL CARRIER/59SC2C040S17--12 40 37 14 220 65 60 115 70 65 80 80 80 60 60 5 5 5 5 5 5 5 5 6 PROVIDE CARRIER GAPAAXCC1625 AIR PURIFICATION UNIT WITH MERV 15 FILTER AND GERMICIDAL AIR TREATMENT SYSTEM CAPABLE OF REMOVING OR KILLING 99% OF ALL VIRUSES, BACTERIA, AND FUNGI. PHYSICAL DATA: 17-1/2"W X 25-1/4"D X 11-1/8"TALL. ELECTRICAL: 115/60/1 VAC, 18 WATTS WITH POWER TO BE CONNECTED TO FURNACE. 6 6 6 FURNACE WITH CNPV DX COIL 18 80/57 95 600 .50 1/2 10.3 15 120/1 300 29-1/2" DEEP X 17.5" WIDE X 35" TALL 6 CARRIER/59SC2C040S17--12 40 37 14 150 F 14 EDUCATION MEZZANINE/ 1,200 .50 3/4 230 120/1 300 FURNACE WITH CNPV DX COIL 36 80/57 95 11.7 15 29-1/2" DEEP X 21" WIDE X 35" TALL 1 2 3 4 CARRIER/59SC2C080S21--20 80 75 14 5 MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS M3.1 NONE MECHANICAL SCHEDULES Page 23 of 28 M2.2E AS NOTED MECHANICAL MEZZANINE PLAN - EAST MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS Page 22 of 28 9 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 8"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} 10 11 \\pxsm1,pxsm1,t3;{\Fsimplex|t3;{\Fsimplex|c0;\W1;NEW AC c0;UNIT \W1;INSTALLED NEW ON FURNACE WALL ABOVE DOOR INSTALLED PER MANUFACTURER'S ON MEZZANINE INSTALLATION INSTRUCTIONS FLOOR, WITH CONNECT CONDENSING UNIT 10"MOUNTED OA TO ON RETURN GRADE. EXTEND AIR REFRIGERANT AND EXTEND PIPING FROM UP CONDENSING THROUGH UNIT TO ROOF. FAN COIL UNIT RE: INSTALLED VERTICAL PER MANUFACTURER'S UPFLOW INSTALLATION FURNACE INSTRUCTIONS. DETAIL } 4, 1/M4.3} 12 \pxsm1,t3;{\Fsimplex|c0;\W1;INSULATE ALL DUCTS ROUTED THROUGH ATTIC WITH R12 INSULATION.} 13 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE 1" GAP AT BOTTOM OF DOOR FOR AIR TRANSFER.} {DEMO NOTES: 1. REMOVE ALL EXISTING HVAC EQUIPMENT EXCEPT FOR EXHAUST FAN AT MEZZANINE LEVEL BATHROOM.} 14 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 10"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} M2.2W AS NOTED MECHANICAL MEZZANINE PLAN - WEST MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS Page 21 of 28 OFFICE SCALE: 1" = 4'-0" MECHANICAL PLAN - EAST 1 3 3 3 3 3 3 3 3 3 12" 14" 5 T 16/10 16/12 16/10 10"RA 16/12 T T T 16/12 16/10 14/8 12" 8" 5 T 10"RA 16/14 RA 16/12 SA T 10 3 T T NOTES 1 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 4"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} 2 \pxsm1,t3;{\Fsimplex|c0;\W1;CONNECT 8"EA TO CEILING FAN, EXTEND UP THROUGH ROOF TO SMACNA APPROVED VENT CAP.} 3 \pxsm1,t3;{\Fsimplex|c0;\W1;CONDENSING UNIT INSTALLED AT GRADE, EXTEND REFRIGERANT PIPING FROM CONDENSING UNIT TO FURNACE/FAN COIL ACCORDING TO MANUFACTURER'S INSTALLATION INSTRUCTIONS.} 4 \pxsm1,t3;{\Fsimplex|c0;\W1;14/8 RA DUCT DOWN IN CHASE TO INLET GRILLE AT 6" AFF.} 5 \pxsm1,t3;{\Fsimplex|c0;\W1;DUCT MOUNTED DIFFUSER MOUNTED TO SIDE OF DUCT ROTATED 30 DEG DOWN FROM HORIZONTAL. } 6 \pxsm1,t3;{\Fsimplex|c0;\W1;DUCT ROUTED BETWEEN JOIST, RUN-OUTS FROM MAINS TO DIFFUSERS THROUGH OPEN WEB JOISTS.} \pxsm1,t3;{\Fsimplex|c0;\W1;DUCT ROUTED BETWEEN JOIST, RUN-OUTS FROM MAINS TO DIFFUSERS THROUGH OPEN WEB JOISTS. NO DUCT LINER TO BE USED IN SYSTEMS SERVING PROCEDURE ROOMS.} 8 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE BALANCE DAMPER WITH REMOTE OPERATOR. RE: REMOTE DAMPER CONTROL DETAIL 3/M4.2} 9 \pxsm1,t3;{\Fsimplex|c0;\W1;PROVIDE 1" GAP AT BOTTOM OF DOOR FOR AIR TRANSFER.} 10 11 \\pxsm1,pxsm1,t3;{\Fsimplex|c0;t3;\W1;NEW {\AC Fsimplex|UNIT INSTALLED IN CEILING c0;PER \W1;MANUFACTURER'S SPIRAL INSTALLATION DUCT INSTRUCTIONS WITH PREPARED CONDENSING UNIT MOUNTED AT FOR GRADE. EXTEND PAINTING, REFRIGERANT PIPING FROM HERCULES CONDENSING UNIT TO FAN COIL PAINTLOCK UNIT INSTALLED PER MANUFACTURER'S FINISH INSTALLATION OR INSTRUCTIONS. EQUAL.} } {DEMO NOTES: 1. REMOVE ALL EXISTING HVAC EQUIPMENT EXCEPT FOR EXHAUST FAN AT M2.1E AS NOTED MECHANICAL PLAN - EAST MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS Page 20 of 28 M2.1W MECHANICAL PLAN - WEST M2.2E MECHANICAL MEZZANINE PLAN - EAST M2.2W MECHANICAL MEZZANINE PLAN - WEST BDD REFRIGERANT SUCTION RL REFRIGERANT LIQUID RS RL RS AFF ABOVE FINISHED FLOOR OBD BDD SW SIDEWALL DIFFUSER BACKDRAFT DAMPER OPPOSED BLADE DAMPER DESCRIPTION LEGEND ABBR SYMBOL DD F S S T F DD S T-STAT FLFD FSD DUCT MOUNTED SMOKE DETECTOR SPACE SENSOR W/ PLUG-IN PORT COMBINATION FIRE/SMOKE DAMPER THERMOSTAT FUSIBLE LINK FIRE DAMPER M RA SA RE-D AUTO D MVD WC OA GBS ESP EA EXTERNAL STATIC PRESSURE GALVANIZED BIRD SCREEN WATER COLUMN MVD WITH REMOTE CEILING OPERATOR SUPPLY AIR RETURN AIR EXHAUST AIR OUTSIDE AIR MANUAL VOLUME DAMPER MOTORIZED DAMPER UNO TSP TOTAL STATIC PRESSURE UNLESS NOTED OTHERWISE M4.2 MECHANICAL DETAILS MECHANICAL SPECIFICATIONS SUPPLY, RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED STEEL PER SMACNA DUCT CONSTRUCTION STANDARDS. SUPPLY, RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED FOR 2" W.C. STATIC PRESSURE. SPIRAL LOCK-FORMED ROUND DUCT MAY BE UTILIZED WHERE SPACE ALLOWS. TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL BE SEALED AIR-TIGHT WITH MASTIC, MASTIC SHALL BE APPLIED ONLY TO THE INSIDE OF EXPOSED DUCTWORK. RADIUSED ELBOWS (R/D=1.5) OR MITERED ELBOWS WITH SINGLE THICKNESS TURNING VANES SHALL BE UTILIZED WHERE POSSIBLE. TURNING VANES SHALL BE SUPPORTED AT INTERVALS OF 36" MAXIMUM. TURNING VANE RUNNERS SHALL HAVE A VANE IN EVERY SLOT AND SHALL CONFORM TO SMACNA DUCT CONSTRUCTION STANDARDS FOR STANDARD SPACING. INSULATED, FACTORY FABRICATED, FLEXIBLE DUCTWORK MAY BE UTILIZED AT RUNOUTS TO AIR DIFFUSERS WHERE DUCTWORK IS CONCEALED ABOVE CEILINGS. FLEXIBLE DUCTWORK SHALL CONSIST OF AN EXTERIOR REINFORCED LAMINATED VAPOR BARRIER, R-6.0 MINIMUM FIBERGLASS INSULATION AND INTERIOR VINYL LINER WITH SPRING STEEL WIRE HELIX. VINYL LINER SHALL NOT BE PERFORATED. FLEXIBLE DUCT ASSEMBLY SHALL HAVE A FLAME SPREAD/SMOKE DEVELOPED RATING OF 25/50 OR LESS. FLEXIBLE DUCT TO FLEXIBLE DUCT CONNECTIONS SHALL BE MADE WITH FACTORY FABRICATED STEEL COLLARS. FLEXIBLE DUCT SHALL BE SECURED TO RIGID DUCTWORK AND AIR DEVICES WITH SCREWS AND DRAWBANDS. LENGTH OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO 5' AND SHALL NOT BE COMPRESSED. FLEXIBLE DUCTWORK SHALL NOT BE USED FOR ELBOWS. FLEXIBLE DUCT SHALL NOT BE USED ABOVE INACCESSIBLE CEILINGS. FLEXIBLE DUCT SHALL NOT PASS THROUGH WALLS. ALL SUPPLY AND RETURN RECTANGULAR DUCTWORK SHALL BE PROVIDED WITH DUCT LINER (INSIDE THE DUCT): ONE INCH THICK, RESIN BONDED GLASS FIBER, IMMOBILIZED, EPA-REGISTERED ANTIMICROBIAL AGENT COATING ON AIR STREAM SURFACE, RATED BY MANUFACTURER FOR AT LEAST 4000 FPM AND MEETING THE REQUIREMENTS OF ASTM C1071 TYPE I. FIRE RESISTANCE SHALL MEET REQUIREMENTS OF NFPA 90A. FLAME SPREAD RATING NOT TO EXCEED 25. FUEL CONTRIBUTION AND SMOKE DEVELOPMENT NOT TO EXCEED 50. NOISE REDUCTION COEFFICIENT (NRC) OF NOT LESS THAN 0.60 WHEN TESTED IN ACCORDANCE WITH ASTM C423 USING AN "A" MOUNTING OR A MINIMUM OF 0.70 USING AN "F" MOUNTING. K VALUE NOT MORE THAN 0.26 BTUH PER SQUARE FOOT PER DEG. F AT 75 DEG. F OR AN "R" VALUE OF 4. MAXIMUM ABSOLUTE ROUGHNESS FACTOR PER FOOT OF .004 SUPPLY AND RETURN AIR DUCTWORK SHALL BE INSULATED WITH R-6 INSULATION WHEN LOCATED IN UNCONDITIONED SPACES WITHIN THE BUILDING ENVELOPE AND R-12 WHEN LOCATED OUTSIDE OF THE BUILDING. OUTSIDE AIR INTAKE DUCTS INSTALLED IN CONDITIONED AREAS SHALL BE INSULATED WITH R-3.5 INSULATION. DUCT INSULATION TO BE FLEXIBLE FIBERGLASS WITH FOIL SCRIM FACING. INSULATION SHALL HAVE A MAXIMUM CONDUCTIVITY, K-VALUE, OF 0.29 AT 75°F AND HAVE FLAME SPREAD/SMOKE DEVELOPED RATING OF 25/50 OR LESS. INSULATION SHALL BE SECURED WITH WIRE TIES AT 12" ON CENTER OR WITH SELF-SEALING LAP AND TAPE JOINTS 3" ON CENTER AT FITTINGS. JOINTS SHALL BE COVERED WITH 3" WIDE FOIL REINFORCED KRAFT TAPE. ADHESIVE OR MECHANICAL FASTENERS SHALL BE USED WHERE NECESSARY TO PREVENT SAGGING. VAPOR BARRIER PENETRATIONS BY MECHANICAL FASTENERS SHALL BE SEALED WITH VAPOR BARRIER ADHESIVE. INSULATION SHALL STOP AND POINT AROUND ACCESS DOORS AND DAMPER OPERATORS TO ALLOW OPERATION WITHOUT DISTURBING WRAPPING. DUCT HANGERS SHALL BE CONSTRUCTED OF GALVANIZED STEEL. DUCTS SHALL BE SUPPORTED AND CONNECTED TO THE STRUCTURE PER SMACNA DUCT CONSTRUCTION STANDARDS. HANGERS AND SUPPORTS FOR GREASE DUCT SHALL BE OF NONCOMBUSTIBLE MATERIALS. FLEXIBLE DUCTS SHALL BE SUPPORTED WITH GALVANIZED STRAPS. HEAVY FLEXIBLE CONNECTIONS SHALL BE FURNISHED AND INSTALLED AT DUCT CONNECTIONS TO FANS AND AIR HANDLING UNITS EXCEPT HIGH TEMPERATURE KITCHEN HOOD EXHAUST FANS. FLEXIBLE CONNECTIONS SHALL BE 6" MINIMUM AND 10" MAXIMUM IN LENGTH. MATERIAL FOR INTERIOR INSTALLATIONS SHALL BE VENTFLEX MANUFACTURED BY VENTFABRICS, EXCELON MANUFACTURED BY DURO-DYNE OR APPROVED EQUAL. MATERIAL FOR EXTERIOR INSTALLATIONS SHALL BE VENTLON MANUFACTURED BY VENTFABRICS, DUROLON MANUFACTURED BY DURO-DYNE OR APPROVED EQUAL. MANUAL VOLUME DAMPERS SHALL BE FURNISHED AND INSTALLED WHERE INDICATED AT SUPPLY AIR DUCT RUNOUTS TO AIR DIFFUSERS AND GRILLES AS NEAR AS POSSIBLE TO THE TRUNK DUCT. MANUAL VOLUME DAMPERS FOR RECTANGULAR DUCT SHALL BE CONSTRUCTED OF 16 GAUGE GALVANIZED STEEL AND BE THE OPPOSED BLADE TYPE. MANUAL VOLUME DAMPERS FOR ROUND DUCT SHALL BE CONSTRUCTED OF 16 GAUGE GALVANIZED STEEL AND BE THE SINGLE BLADE TYPE. DAMPER BEARINGS SHALL BE NYLON. STAND-OFFS TO OUTSIDE OF INSULATION SHALL BE PROVIDED FOR MANUAL VOLUME DAMPERS IN INSULATED DUCT. LOCKING AND INDICATING QUADRANTS SHALL BE PROVIDED WHERE DAMPER IS ACCESSIBLE. REMOTE CEILING OPERATORS SHALL BE FURNISHED AND INSTALLED FOR DAMPERS ABOVE INACCESSIBLE CEILINGS. OPERATORS SHALL BE GEAR AND LINKAGE TYPE EQUAL TO YOUNG REGULATOR WITH CHROME PLATED CEILING ESCUTCHEON AND COVER PLATE. AIR DEVICES SHALL BE AS SCHEDULED. EXPOSED SCREWS SHALL BE THE FINISHING TYPE AND PAINTED TO MATCH THE AIR DEVICE. SQUARE TO ROUND ADAPTORS SHALL BE PROVIDED WHERE REQUIRED FOR AIR DEVICES IN CEILINGS. AIR DEVICES SHALL BE FINISHED WITH WHITE BAKED ENAMEL UNLESS NOTED OTHERWISE. AIR DEVICES SHALL BE SECURED TO T-BAR CEILINGS WHERE APPLICABLE. REFRIGERANT PIPING SHALL BE ASTM B 280 TYPE ACR COPPER TUBING WITH B16.22 WROUGHT COPPER FITTINGS. COPPER TUBING SHALL BE BRAZED WITH AWS A5.8 BCuP SILVER BASED FILLER METAL. REFRIGERANT PIPING SYSTEM, INCLUDING FITTINGS, VALVES AND APPURTENANCES SHALL BE TESTED FOR LEAKAGE AT 200 PSI WORKING PRESSURE WITH DRY NITROGEN. INSULATE ALL REFRIGERANT SUCTION GAS AND LIQUID DISCHARGE TUBING WITH 1/2" MINIMUM THICKNESS FLEXIBLE CLOSED CELL ELASTOMERIC INSULATION. PROVIDE TYPE R-374 PROTECTIVE COATING (2 COATS MINIMUM) TO INSULATION INSTALLED OUTSIDE OF BUILDING WHERE EXPOSED TO ATMOSPHERE. MECHANICAL EQUIPMENT SHALL BE SECURED AND INSTALLED PER MANUFACTURERS RECOMMENDATIONS AND APPLICABLE SECTIONS OF THE JURISDICTIONAL BUILDING AND MECHANICAL CODES. MECHANICAL EQUIPMENT SHALL BE IDENTIFIED WITH BAKELITE NAMEPLATES. COLOR CODING OF NAMEPLATES AND IDENTIFICATION INFORMATION SHALL BE COORDINATED WITH THE OWNER. AN INDEPENDENT TEST AND BALANCE FIRM WHICH IS AABC OR NEBB CERTIFIED SHALL BE RETAINED FOR CHECK/TEST-START-UP AND TESTING M4.3 MECHANICAL DETAILS M0.0 NONE MECHANICAL LEGEND AND NOTES MOEN ENGINEERING CONSULTANTS INC 4640 PECOS ST., UNIT F DENVER, CO 80211 P: (303)907-4285 SHEET NUMBER: DATE: SCALE: SHEET TITLE: REVISIONS: Miller DesignWorks 1261 York Street Denver, CO 80206 PH 303-480-5212 www.millerdw.com TENANT IMPROVEMENT 825 S. SHIELDS STREET FORT COLLINS, COLORADO 06/04/18 C MILLER DESIGNWORKS, INC 2018 CONSTRUCTION DOCUMENTS Page 18 of 28 Motor Amps 1 0.4 Amps SP In Actual 0.0 in. wc SP Out Actual ANA in. wc Total SP Actual NM in. wc Motor Data Motor Manufacturer Greenheck Motor HP 1/40 HP Motor RPM 900 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 0.46 Amps Sheave Data Motor Sheave Make Direct Drive L.H. Finn and Associates Updated Phase 1 Report Page 16 of 28 Outlet-06 1601 17 115 109 118 95 103 Totals: - - - 610 730 612 120 100 F-12 Supply Outlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 13 of 28 Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1508 20 450 389 438 86 97 Totals: - - - 450 389 438 86 97 F-11 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 12 of 28 Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1506 4 260 108 264 42 102 Inlet-B 1506 4 260 255 267 98 103 Totals: - - - 520 363 531 70 102 F-10 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 11 of 28 Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1502 4 260 222 278 85 107 Inlet-B 1502 4 260 193 274 74 105 Totals: - - - 520 415 552 80 106 F-09 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 10 of 28 Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1505 4 260 145 255 56 98 Inlet-B 1505 4 260 191 253 73 97 Totals: - - - 520 336 508 65 98 F-08 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 9 of 28 System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1308 18 130 156 120 120 92 Inlet-B 1501 3 200 133 185 67 93 Inlet-C 1411 3 200 159 187 80 94 Inlet-D 1409 18 70 122 66 174 94 Totals: - - - 600 570 558 95 93 F-06 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 7 of 28 Page 6 of 28 Maximum Final % Prelim Deviation % Final Deviation Inlet-A 1301 3 150 Inlet-B 1401 3 135 Inlet-C 1201 3 115 Inlet-D 1203 18 200 Totals: - - - 600 0 0 0 0 F-04 Return Inlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 5 of 28 Totals: - - - 1225 0 0 0 0 F-02 Supply Outlet Summary L.H. Finn and Associates Updated Phase 1 Report Page 4 of 28