Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
1220 W Elizabeth St - Special Inspections/Field Verification - 07/02/2014
Frank's Sheet Metal 1020 E Vine Dr Fort Collins Co 80524 970-484-2812 Butters Caf6 (Permit # B1305431) 1220B W Elizabeth St Fort Collins Co 80521 970-797-2062 Method used to measure CFM: Flow Hood Dining Room RTU register # size Initial CFM Adjusted CFM Final CFM Target CFM 1 8" x 12" 304 280 301 290 2 8" x 12" 294 286 292 290 3 8" x 12" 384 291 311 290 4 8" x 12" 407 278 314 290 5 8" x 12" 274 281 290 290 6 8" x 12" 270 300 330 290 7 8" x 12" 272 300 306 290 8 6" 148 90 88 90 9 6" 0 89 93 90 10 6" 0 85 98 90 Total 2353 2280 2423 2300 Make -Up Air register # size Initial CFM Adjusted CFM Adjusted CFM Adjusted CFM Final CFM Target CFM 1 12" 450 413 322 342 328 330 2 12" 359 372 271 363 368 330 3 12" 265 198 281 320 310 330 4 12" 404 380 399 326 324 330 5 12" 380 372 353 346 357 330 6 12" 431 371 335 336 231 330 7 7 x 30 290 211 320 450 528 525 Total CFM 2579 2317 2281 2483 2446 2505 Exhaust Initial CFM Final CFM Target CFM Kitchen Hood 1862 2285 2300 Bathroom Exhaust Women 50 50 50 Bathroom Exhaust Men 50 50 50 Mop Closet Exhaust 50 50 50 Total CFM 2012 2435 2450