HomeMy WebLinkAbout3238 Bryce Dr - Disclosures/Mechanical - 11/17/2015City of Fort Collins Residential Mechanical Systems Performance Report
This form Is a record of testing targets and results, with Pass/Fail outcomes. For information on measurement tools and testing techniques, see the
"Residential New Construction Mechanical Systems Testing Gulde." The guide and this form may be periodically updated; check the Building
Services web site for the current version.
This form must be completed and signed by an "Approved Agency,~ and submitted to Building Services as a requirement for receiving a C.O .
Color
key
Target
orllmlt
Measured value
to compare with Pass Fall
..
Caution ..
Other
data ADCF
ADCF =Air Density Correction Factor, based on tool,
altitude (5000'), air temperature through tool
target or limit .1
Volumetric flow (CFM 5000') = ADCF x Indicated flow (CFM)
Address 3238 Bryce Dr
Bullder Meritage Homes
HVAC contractor Four Seasons Heating Inc.
As-built changes vs
mech design submittal
Testing date(s) 11/9/15
Bath exhaust
Flow .!.. Flow box
tool - Passive flow hood -
Pitot tube duct traverse
Other (note below)
Design
Exhaust Pickup Location
Airflow
(CFM
5000')
Bath 2 50
Laundry 50
Master Bath 50
MasterWIC 50
Testing
notes
Date of "Residential
Mechanical Systems
Design Submittal"
information referenced
by testing technicians
Air tempi
through too! (F) ?O
Testing tech (initia!s)J IP
ADCFI 1.098
Measured Airflow
Minimum Airflow Requirement Indicated Volumetric
(CFM 5000') Flow Flow Pass
+Type of Operation (CFM) (CFM 5000')
..:L 50 Intermittent - 20 Continuous 80 88 IZJ
.
L 50 Intermittent - 20 Conllnuous 79 87 Iii
L 50 Intermittent -
20 Continuous 84 92 Iii
J/.._ 50 Intermittent - 20 Continuous 93 102 Iii
FE'®@•''·ll4'''·t,4•1fiil*ltififflit.1.
Systems other than sub-structural floor exhaust
Code-minimum ventilation alrflowl?O ICFM 5000' Des!gn ventaillarfltioownl~_o __ ~ICFM 5000'
(based on CFA and# of B;_R::.1'.:. ====-· -------~ _ .
Target ventilation airflow range 70
{code-minimum)
to 83 CFM 5000'
(120% of design fkiw)
S stem _Exhaust-only
Y ty ./ Supply-only
pe =Balanced
Measured Airflow
Air Temp Indicated Volumetric
Measurement Method Tool Location Through ADCF Flow Flow Pass Fall
Toot (F) (CFM) (CFM 5000')
Tota! - N/A Passive flow hood
exhaust -
Flow box ./ Pilot tube traverse ARD 70 1.098 75 0 HJ
airflow - Flow collar _ Other (note below) \'.'.·.:
Tota! -
N/A -
Passive flow hood
supply i[]
- F!owbox
- Pitot tube traverse 0
airflow - F!owco!lar _Other (note below)
When supply airflow is circulated by air handler fan, fan speed for measurementj~ ___ H_e_at_in_g __ ,,f.._C_oo_lin_g ___ c_o_n_li_n_uo_u_s_r_a_n~
Balanced airflow in balanced systems
Average of measured'
supply+ exhaust flows
ICFM
5000'
Target flow range!
(average+/- 15%)
to 0 Pass 0Fall
Testing
notes
Sub-structural floor exhaust 121 NIA -- no sub-structural floor exhaust system Testing tech (lnitia!s)cjl_P __ ~
Design exhaust airflow (based onl J
CFM 5000'
approved deslgn)~----~-
Target airflow limits to
(design +/-150/o)~------------~CFM 5000'
Measured airflow
Flow _Flow box Pitot tube traverse T 11 Air tempo
tool
_Passive flow hood Flow collar
00
through
location
_Powered flow hood _Other (note below) _ tool (F)
-~--;:::::====:==;-'------'----' '---;:==:::::.__,
Indicated flowl jcFM Volumetric flowl lcFM 5000'
Testing
notes
N/AI- :L No No ductwork ductwork outside condi!loned space I
Duct reaka e _Testing tech (initials):
d
1
g Energy rater {name,
f j; ®' 11, r. c 15.r.111. r. 1 § • lDJ .1;, t§, 1
For multiple systems, attach one page per system
System #D Wh!ch parts of house does it serve?I Whole House
'--~~~~~~~~~~----;::::::::::::;
Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech {initials)~
Furnace or Boller AC or Heat Pump Condenser AC or Heat Pump Coll
Manufacturer Goodman
Model# GMSS920803BN
:~~~a
Static pressures
Setup
Type
_Basic fiberglass
.:{ Basic pleated
High-effic pleated
Speed:_ Heating :!_Cooling _Cont. fan
_ Hlgh-stage for multi-stage equipment
Blower speed tap: _L_o_w _______ _
Humidifier damper::!_ NIA
_Open (Heating}
_Closed (Cooling)
..:!__AH registers open
_Zone dampers open
SP11-129.4
\
Goodman
GSX16030
- - Other: Electrostatic
.6.P Filler I ~99 J
(SP1 - SP2) L. ----'·
------------ SP2 l-30.4
t
Goodman
CAPF3642
Thickness[] MERV
(optional) 8
(inches) D
Testing tech {Initials)~
e-+--sP4118.1 I
\
\
(Same loca~on
for NSOP,
TFS OP)
Cooling: Measured air flow through indoor coil 0 NJA ·-no AC Installed Testing tech {lnitlals)~
Design coolin~ airllowl1_
0_3
_8 ___ _,JcFM
5000,
{high stage)_ .
Target airflow t!mits,~8-8-3------to --1193 ----~,
{design+/- 15%) _ CFM 5000'
Measured airflow
plate Flow size grid' _ !._ 20 141
AirtempEJ
through 70
tool {F)
ADCFEJ NSOPEJ
Indicated airflow~CFM
Measured AF x FRCFt.::___j
Testing tech {initials)~
Testing approach and targets
0 N/A: No complete AC system (2) N/A: House completed November· April (instatting contractor responsible for testing in wa1m weather)
0 TXV: Subcoollng +SH check D Non·TXV: Superheat 0 OEM-specific: Approach 0 Other OEM-specific (documentation required)
Temperatures Condenser~
(F): entering air tempL_j
Non-TXV: Return D TargetD TargetD
air wet-bulb temp superheat , - subcooling -_ -
TargetD
approach , _-
Subcooling
DischargeD
pressure
(PSI)
Superheat
SuctionD
pressure
(PSI)
CondenserD
saturation T F
(5000' chart)
EvaporatorD
saturation T F
(5000' chart)
LiquidD
!ine F
temp
SuctionD
line F
temp
ActualD
subcooling F
(Cond T - !iq line D
ActualD
superheat F
(Suet line T • evap T)
0 TXV Pass: Actual SC within+/.
3 F of target SC, 2 F min
0TXVFail
0 Non·TXV Pass: Actual SH
within+/. 5 F of target SH
0 Non·TXV Fail
TXV checks: 0 Pass: Fleld·lnsta!!ed TXV installed in accordance with OEM Instructions D' Caution: Actual SH outside mfgr range
Approach
Uqu!dfineDF
temp
Actual approachDF
(Liq line T ·condenser EAT)
0 Approach Pass: Actual approach within+/- 1 F of target approach
0 Approach Fail
Testing
notes
Register air flows
AU registers are cut through finish materials and moving air []Pass 0Fall
(Remainder of register air flow section under development, not yet being enforced)
Pressure balance
Room Room-to-Core
{match names on plans, include Pressure Drop
basement If there Is a door) Target Range (Pa)
Master Bedroom ·3 to +3
[t1 Combustion safety testing NIA - no natural-draft combustion appliances
(Appliance Types table must be completed for every home)
Appliance types
Combustion Type
Appliance Draft-hood Induced-draft Power- Direct-
Testing tech (initials)Li
Powered sealed-
NIA
'Natura!-draftl INatura!-drafO vent vent combustion Electric
Furnace #1 0 0 0 0 0 0 0
Furnace #2 0 0 0 0 0 0 0
Boiler #1 D D D 0 0 0 0
Boller #2 0 D 0 0 0 0 0
Water heater #1 D 0 0 D 0 0 D
Water heater #2 D 0 0 D 0 0 0
Fireplace #1 D 0 0 0 0 0 0
Fireplace #2 0 0 0 0 0 0 0
Other:
D 0 0 0 0 0 0
Worst-case depressurization performance
H ouse setun
These doors are closed:
-- # of bath fans on
__ Vented range hood on
__ Clothes dryer on
-- Air handler on
Other fans on: Other setup notes:
Outdoor temperatureLJF I
Tested appliances
Appliancef----------+----------1----------1
location
CAZ pressure
BPI depressurization limit {Pa wrt outside)
Measured net CAZ depressurization (Pa wrt outside)
OK (less negative) I Caution (more negative)
Spillage
BPI maximum l!mit
Measured spillage duration
Pass= duration not exceeding limit
Draft pressure
(seconds
(seconds
I
I
'--~~~~~-'-~~~~~-'-~~~~~__J
0 loK T DJ Caution D loK I 0 I Caution 0 loK 1.0 I Caution
60 60 60
0 !Pass IC!J.¥a11 0 jPass kEJ.''1Fa1t 0 !Pass l.D\!Fail
BPI limit (Pa wrt CAZ)
!--~~~~~-+-~~~~~-+~~~~~--!
Measured (Pa wrt CAZ)
Pass= pressure more negative than limit
CO concentration In undlluted flue gas
BPlm aximum limit
Meas ured CO
Pass = CO fevel not exceeding limit
Cauti on = CO level 25 to 100 ppm
Testing
notes
Res!dentia! Mechanical Design Subm!ttal
Testlng tech {initials)~
System
Controls Operating
Per Design Intent
Testing Notes
Local exhaust (all fans) D NJA IZl Pass D Fall
Whole-house ventilation D NIA Ql Pass D Fail
Sub-structural floor exhaust IZl NIA D Pass El Fail
Heating (all systems) D NIA Ill Pass l.J Fail
Cooling (all systems) l!'l NIA D Pass :0 Fail
Technician #1 performing Inspection and testing documented on this report (Approved Agency)
I certify that the tests referenced above, in sections bearing my !niUa!s, were performed in accordance with protocols specified by the
City of Fort Collins Bullding Services Department, and that the reported results are accurate to the best of my knowledge.
Name {print ) Ian Pelman
Title Air Flow Tech
Company Four Seasons Heating Inc.
Signature and Date lanPolman 11/9/15
Technician #2 performing Inspection and testing documented on this report (Approved Agency)
I certify that the tests referenced above, in sections bearing my Initials, were performed in accordance with protocols specified by the
-City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge.
Name (print)
Title
Company
Signature and Date
H~AC Contractor (City of Fort Collins license holder)
I certify that I have reviewed this report and that the test results are an accurate representation of the performance of the installed mechanical
systems.
Name {print) Lynn Cobb
Title Project Manager
Company Four Seasons Heating Inc.
Signature and Date Lynn Cobb 11/17/15
Residential Mechanical Design Submittal V20140101 Page 6
(ppm)
(ppm)
D !Pass LOdFail 0 !Pass LEl'JFail
. 100 100 100
0 !Pass kO.lFail 0 !Pass 10,JFail 0 !Pass j':[JJFail
0 lcautton _O_- :JCaution O:icautton
V20140101 Page 5
Bedroom 2 ·3 to +3
-3 to +3
-3 to +3
-3 to +3
·3 to +3
·3 to +3
·3 to +3
-3 to +3
-3 to +3
Resldenlial Mechanical Design Submittal V20140101
.7
.6
Testing tech {initials)~
Testing tech {initials)~
Measured
Pressure Pass Fail
Drop (Pa)
YI ···[]
YI jj
0 tl
0 I• !'J~
0 :. :;1
0
0 -
0 JI
0 .. 0:
0 []
Page 4
M_easured airflow,_2 noEJ
CFM
adJustmenUcorrect1on
Testing
notes
Heating: Gas manifold pressure
Manifold pressure~lWC
OEM spec@ sooo·L_J
Heating: Temperature rise
{high stage)
Target manifold Pl3
3 to 3
_7
limits {spec+/· 5%)~·------~
OEM temperature rise fimilsl3
_5 ___ ,0_ 6_
5 __ ~JF
{high stage)_ _
TFSOPEJ
Flow ResistanceEJ
Correction Factor .9
Volumetric alrflowEJ
81
CFM
Indicated AF x AOCF 5000 1
!ll Pass
0Fail
Testing tech (initials)~
IWC Measuredr;;llWC
pressurec___J
[ii Pass
0Fail
Testing tech {Initials)~
Measured temps (F): Sup~!~~ - Retua~~ = Te'.11pEJ1 Ill Pass
rise
·n· 0
. Caution: within 10F
t,J Fail , of top of range
Residential Mechanical Design Submittal V20140101 Page 3
a a source - company, testing date):
House cond1troned floor areal
(mclude full basement)
Testing notesl
(incl multiple sys)I
A1rtemp~
through tool (F)L___j
0Pass 0Fail
Maximum Allowed Duct Leakage Measured Duct Leakage
System #1 System #2
Test Parameter and Conditions Normalized Absolute Indicated Volumetric
Leakage Type Timing Air Handler (CFM25 5000' / 100 sQ (CFM25 5000') (CFM25) (CFM25 5000') Pass Fail Pass Fall
Total leakage Rough-in Excluded 4 0 ,,q 0 Cl
'
Total leakage Rough-in Included 6 0 I' J, 0 I C2l
Total leakage Complete Included 12 0
j; ;Jo 0 d,
Leakage
to outdoors Complete Included 8 0 ,,::r 0 'tr ; ,: '
Residential Mechanical Design Submittal V20140101 Page 2
- 50 fntermrttent _ 20 Continuous El
- 50 Intermittent _ 20 Conllnuous El
- 50 Intermittent - 20 Continuous El
Fail
p
El
El
·o
El
>El
tr
Kitchen exhaust N/A - hood does not vent to outside D Testing tech (Initials)~
Oven fuell _Gas :L Electric )
Measured airflow
Minimum airflow requirement (CFM 5000') +operation! _ 100 Intermittent _ 25 Continuous I
- Flow box
1
_ Passive flow hood
_ Powered flow hood
Flow
too
lndi cated flow!
Test! ng
note s
- Pilot lube traverse
_Flow grid
Other (note below}
jcFM
Residential Mechanical Design Submittal
Tool
_ Interior grille AJrtempD
location ADC FD
_Exhaust duct through
(Exterior termination not OK) tool (F}
Volumetric flow! jcFM 5000' 0Pass 0Fail
V20140101 Page 1