HomeMy WebLinkAbout483 Lupine Dr - Disclosures/Mechanical - 11/26/2014City of Fort Collins Residential Mechanical Systems Performance Report
This form is a record of testing targets and results, with Pass/Fail outcomes. For information on measurement tools and testing techniques, see the
"Residential New Construction Mechanical Systems Testing Guide." The guide and this form may be periodically updated; check the Building
Services web site for the current version.
This form must be completed and signed by an "Approved Agency," and submitted to Building Services as a requirement for receiving a C.O.
Color
key
Target
Measured value
Other
or limit
to compare with
Pass
Fail
Caution
data
target or limit
ADCF = Air Density Correction Factor, based on tool,
ADCF altitude (5000'), air temperature through tool
Volumetric flow (CFM 5000') = ADCF x Indicated flow (CFM)
1. House Data
Address 483 Lupine Dr Date of"Residential
Mechanical Systems
Builder AS en Heights Construction Design Submittal"
P 9 information referenced
HVAC contractor by testing technicians
As -built changes
mech design submit
Testing date(s) 111/26/14
2. Local Exhaust (Spot Ventilation)
Bath exhaust
Testing tech (initials) TS
Flow ✓ Flow box Lj Pitot tube duct traverse Air temp
72
ADCF1.098
tool _ Passive flow hood _ Other (note below) through tool (F)
Measured Airflow
Design
Airflow
Minimum Airflow Requirement
Indicated
Volumetric
Exhaust Pickup Location
(CFM
(CFM 5000')
Flow
Flow
Pass
Fail
5000')
+Type of Operation
(CFM)
(CFM 5000')
Bath, 2, S
❑✓ 50 Intermittent ❑20 Continuous
49
54 '
❑✓
❑
Bath, 2, W
❑✓ 50 Intermittent 020 Continuous
59
65
❑✓
❑
Bath, 2, N
❑✓ 50 Intermittent ❑20 Continuous
57
63
✓❑
❑
Bath, 1, E
✓❑ 50 Intermittent ❑20 Continuous
50
55
❑✓
❑
❑ 50 Intermittent ❑20 Continuous
❑
❑
❑,50Intermittent ❑20 Continuous
❑
50 Intermittent 1:120 Continuous
❑
Testing
notes
Kitchen exhaust N/A - hood does not vent to outside Testing tech (initials) TS
Oven fuel ❑ Gas ✓❑ Electric Minimum airflow requirement (CFM 5000') + operation 100 Intermittent ❑ 25 Continuous
Measured airflow
Flow Flow box — tube traverse Tool —Interior grille Air temp
ADCF
Passive flow hood _ Flow grid cat duct through
tool _ Powered flow hood Other (note below) location (Exterior termination not OK) tool (F)
Indicated flow CFM Volumetric flow CFM 5000' ❑ Pass ❑ Fail
Testing
notes
Residential Mechanical Design Submittal V20140101 Page 1
3. Whole -Dwelling -Unit Ventilation
Systems other than sub -structural floor exhaust Testing tech (initials) TS
Code -minimum ventilation airflow Design ventilation
f 4H COrlt. CFM 5000' Intermitent CFM 5000' ❑Exhaust -only
(based on CFA and # of BR) airflow System
type ❑✓ Supply -only
F
8 Cont. to 58 cont. CFM 5000' ❑
Balanced
Target ventilation airflow range
i wde-minimum) (120/ of design now)
Measured Airflow
Measurement Method
Too) Location
Air Temp
Through
Tool (F)
ADCF
Indicated
Flow
(CFM)
Volumetric
Flow
I (CFM 5000')
Pass
Fail
Total
exhaust
airflow
N/A Passive flow hood
Flow box ✓❑Pitot tube traverse
Flow collar Other (note below)
Total
supply
airflow
N/A Passive flow hood
Flow box ❑Pitottube traverse
Flow collar Other (note below)
Fresh Air duct
31
1.056
86
91
0✓
101
When supply airflow is circulated by air handler fan, fan speed for measurement
Q
Heating IZI
Cooling
Continuous fan
1 Balanced airflow in balanced systems _
4 Average omeasur
ed red CFM Target flow range CFM
I I Pass Fail
supply +exhaust flows 5000' (average +/-15%) to 5000' ���---III
. I
! I Testing
notes April air damper controller set to 30 mins / hr on setting C for (cold climates)
L;
Sub -structural floor exhaust N/A - no sub -structural floor exhaust system Testing tech (initials)
t
I Design exhaust airflow (based on Target airflow limits
approved design) CFM 5000' (design +/-15%) to CFM 5000'
�Measured airflow,
III Flow box Pitot tube traverse A r temp
Flow — Passive flow hood Flow collar Tool through ADCF
tool — — location tool (F)
_Powered flow hood _ Other below)
r
Indicated flow CFM Volumetric flow CFM 5000' ❑I Pass ❑ Fail
LJ ... I I
Heating4. + Cooling Duct Leakage
_ No ductwork Testing notes
N/A _ No ductwork outside conditioned space (Incl multiple sys)
Duct leaka e — " ""'' -"
g Energy rater (name,
data source
fZ 71Ah'- WvJ ate,
House conditioned floor area
(include full basement) �70�
Test Parameter and Conditions
sf Air temp/ ADCF (. D 9Fl
through tool(F) 6�
Maximum Allowed Duct Leakage
Normalized Absolute
(CFM25 5000' / 100 sf) (CFM25 5000')
Measured Duct Leakage
Indicated Volumetric
(CFM25) (CFM25 5000')
System #1
System #2
Leakage Type
Timing
Air Handler
Pass
Fail
Pass
Fail
Total leakage
Rough -in
Excluded
4
0
❑
❑
Total leakage
Rough -in
Included
6
/ 0)-
❑
❑
❑
Total leakage
Complete
Included
12
El
Eli
❑
❑
Leakage
to outdoors
Complete
Included
8
El❑
Residential Mechanical Design Submittal
V20140101
Page 2
la
Cooling
For multiple systems, attach one page per system
System #❑ Which parts of house does it serve? Whole House
Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech (initials)❑
Furnace or Boiler
AC or Heat Pump Condenser
AC or Heat Pump Coil
Manufacturer
- ku V J
h RE) U d
C IS -�
Model#
g/�h6-- (1�t
/l-t�CI-(� �3 S
/ 2
P J� Ao I
p
p&li GG
RC -FL - 9M'I
Filter Basic fiberglass Electrostatic Thickness MERV
brand G Type Basic pleated _ Other: (inches) (optional)
�O High-effic pleated 3�4 F1
Static pressures Testing tech (initials) TS
Setup
Speedo Heating ✓❑Cooling❑font. fan
JHigh-stage for multi -stage equipment
Blower speed tap: High
Humidifier damper:0 N/A
Open (Heating)
Closed (Cooling)
All registers open
Zone dampers open
SP1 -35 Pa
AP Filter 1 9 Pa
(SP1 - SP2)
Cooling: Measured air flow through indoor coil
Design cooling airflow (high stage) 1033 CFM 5000'
125 Pa I
(Same location
for NSOP,
TFSOP)
AP Coil
(SP3-SP4) 33 Pa
-SP3 58 Pa
OP Total ESP 202 Pa
(SP3-SP2)
.81 IWC
SP2
❑ N/A - no AC installed Testing tech (initials) TS
Target airflow limits $.78 to 1 1 $$ CFM 5000'
(design +/-15 )
Measured airflow
Flow
PI size
0 14
20
Air temp
thro ghF72]
ADCF pgg NSOP 25
TFSOP❑ Flow Resistance
Correction Factor
tool F
Measured airflow, no
CFM
Indicated airflow Q C
8�5 CFM
Volumetric airflow Q Q /1 CFM Q✓ Pass
884 5000'
adjustment/correction
Measured AF x FRCF
Indicated AFxADCF Fall
Heating: Gas manifold pressure (high stage) Testing tech (initials)
Manifold pressure Target manifold P 7 Measured ❑✓ Pass
OEM spec @ 5000' IWC limits (spec +/_ 5%) 3. 3 J to 3 , V7 IWC pressure i • S IWC ❑ Fail
Heating: Temperature rise Testing tech (initials) {✓/ W
OEM temperature rise limits Z �- to S S F
(high stage)
Supply _ Return _ Temp ❑ ❑ Caution: within 10F
'Measured temps (F): air U air S - rise 2 Pass Fail of top of range
Residential Mechanical Design Submittal
V20140101
Page 3
6. Refrigerant Charge
Testing tech (initials) /� i»I
Testing approach and targets
❑ N/A: No complete AC system t N/A: House completed November - April (installing contractor responsible for testing in wan weather)
❑TXV: Subcooling+SHcheck ❑.Non-TXV:Superheat ❑OEM -specific: Approach ❑Other OEM -specific (documentation required)
Temperatures Condenser Non-TXV: Return Target Target Target
p (F): entering airtemp� air wet -bulb temp superheat subcoolii approach
Subcooling -
Dischar a
pre u
Condenser
saturation T❑F
Li uid
line❑F
Actual
subcooling❑F
❑TXV Pass: Actual SC wthin +!-
3 F of target SC, 2 F min
(s
PSI )❑
(5000'chart)
tem
(ContlT-Iigline T)
❑TXV Fail
Superheat
Suction
pressure❑
Evaporator
saturationT❑F
Suction
line❑F
Actual
superheat❑F
❑Nan-TXV Pass: Actual SH
withinXVFail ftargetSH
(PSI)
(500ti'chan)
temp
(suctlineT-evapT)
❑Non-TXV Fail
TXV checks: ❑Pass: Field -installed TXV installed in accordance with OEM instructions ❑Caution:
Actual SH outside mfgr range
Approach
Liquid line�F Actual approach
�F ❑Approach Pass: Actual approach within +/- 1 F of target approach
temp (Liq line T -condenser FAT) ❑Approach Fail
Heating season, testing not required
Register air flows
All registers are cut through finish materials and moving air Pass ❑ Fail
(Remainder of register air flow section under development, not yet being enforced)
Pressure balance
Testing tech (initials) FTS
Testing tech (initials) TS
Room
(match names on plans, include
basement if there is a door)
Room -to -Core
Pressure Drop
Target Range (Pa)
Measured
Pressure
Drop (Pa)
Pass
Fail
Bed, 2, SW
-3to+3
.6
0✓
❑
Bed, 2, W
-3to+3
,7
✓❑
❑
Bed, 2, NW
-3to+3
.6
✓❑
❑
-3 to +3
❑
❑
-3 to +3
0
❑
-3 to +3
❑
❑
-3 to +3
❑
❑
-3 to +3
❑
❑
-3 to +3
❑
❑
-3 to +3
❑
❑
Residential Mechanical Design Submittal V20140101 Page 4
%
i Combustion
�✓ Combustion safety testing WA — no natural -draft combustion appliances
Testing tech (initials) /4
L , (Appliance Types table must be completed for every home) / � �
Appliance types
j
Appliance
I Combustion
T pe
N/A
Draft -hood
Natural -draft
Induced -draft
Natural -draft
Power-
vent
Direct-
vent
Powered sealed -
combustion
Electric
Furnace #1
❑
❑
❑
❑
❑
❑
Furnace #2
R
❑
❑
❑
❑
❑
❑
I4
Boiler#1
a
❑
❑
❑
❑
❑
❑
Boiler#2
9
❑
❑
❑
❑
❑
❑
Water heater #1
❑
❑
❑
IT
❑
❑
❑
Water heater #2
Q
❑
❑
❑
❑
❑
❑
Fireplace #1
a
❑
❑
❑
❑
❑
❑
Fireplace #2
Q
❑
❑
❑
❑
❑
❑
Ll
Other:
d
❑
❑
❑
❑
❑
❑
Worst -case depressurization performance
These doors are cl
_ # of bath fans on
_ Vented range hood on
_ Clothes dryer on
—Air handler on
Other fans on: Othersetuo notes:
Outdoor temperature = F
�CAZ pressure
BPI depressurization limit
(Pawrt outside)
Measured net CAZ depressurization
(Pawrtoutside)
OK (less negative) ) Caution (more negative)
i
Spillage
BPI maximum limit
(seconds'
Measured spillage duration
(seconds.
Pass = duration not exceeding limit
Draft pressure
BPI limit
(Pa wrt CAZ'
Measured
(Pa wrt CAZ'
Pass = pressure more negative than limit
CO concentration in undiluted flue gas
BPI maximum limit
(ppm,
Measured CO
(ppm,
'Pass = CO level not exceeding limit
Caution = CO level 25 to 100 ppm
Testing
El OK ❑ Caution ❑ OK I ElCaution ❑ OK ❑ Caution
60
60
60
❑
Pass I ❑ Fail
_MP
ss I ❑ lFail
I ❑
Pass I ❑ Fail
ElPass ElFail ❑ Pass I ❑ IFail I ❑ jPass I ❑ Fail
100
100
100
❑
Pass ❑ Fail
❑
jPass I ❑ lFail
❑
IPass I ❑ Fail
❑
Icaution
❑
Icaution
❑
Icaution
Residential Mechanical Design Submittal V20140101 Page 5
,. U
System
Controls Operating
Per Design Intent
Local exhaust (all fans)
WA
Pass
Fail
Whole -house ventilation
N/A
Pass
Fail
Sub -structural floor exhaust
N/A
Pass
Fail
Heating (all systems)
N/A
Pass
❑
Fail
Cooling (all systems)
NIA
Pass
Fail
Testing tech (initials) TS
Testing Notes
Technician #1 performing inspection and testing documented on this report (Approved Agency)
I certify that the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the
City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge.
Name (print) Tyler .Stein
Title Field Energy Rater
Company EnergyLogic Inc.
Signature and Date
Technician #2 performing inspection and testing documented on this report (Approved Agency)
{ I certify that the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the
City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge.
Na
Ll Signature
HVAC Contractor (City of Fort Collins license holder)
I certify that l have reviewed this report and that the test results are an accurate representation of the performance of the installed mechanical
systems.
Name (print) j
Titre v L
Company
Signature and Date
Residential Mechanical Design Submittal V20140101 Page 6