HomeMy WebLinkAbout2383 Palomino Dr - Disclosures/Mechanical - 08/19/2015°. <Y— k Cl ' ZJ l� City of Fort Collins Residential Mechanical Systems Performance Report This form is a record of testing targets and results, with Pass/Fail outcomes. For Information on measurement tools and testing techniques, see the "Residential New Construction Mechanical Systems Testing Guide." The guide and this form may be periodically updated; check the Building Services web site for the current version. This form must be completed and signed by an 'Approved Agency,' and submitted to Building Services as a requirement for receiving a C.O. Color key ...:.. .Target,'-''=-- Measured value::.::'::::. Other orlimll to compare vrih PassFall. "Caulioh; - data target or limit ADCF = Air Density Correction Factor, based on tool, ADCF altitude (5000'), air temperature through tool Volumetric flow (CFM 5000') = ADCF x Indicated flow (CFM) Address 2383 Palomino Dr Date of 'Residential Afcchanlcal Systems Design Submittal" Builder D-R Horton Information referenced IIVAC contractor Four Seasons Healing Inc. by testing technicians As -built ct meth design Testing date(s) Tuesday 8/18/15 - - - - - _ - -..,.._.�_��'�'•r..:.�`.:::.:,.v't..+_v�.s+R`.tr:;i...:: ram... .. ':7;u:o. :':!. Bath exhaust resting tech (Initials) FR.S. Flaw ✓ Flow box _ Pilot tube duct traverse Air temp 64 ADCF 1.088 tool _ Passive flow hood _ Other (note below) through tool (F) Airflow Minimum Airflow Requirement Indicated I Volumetric Exhaust Pickup Location (CFM (CFM 5000') Flow Flow Pass Fall cnnn-r +Type or Operation (CFM) (CFM 5000') Powder 50501gtefinlfteht:���:.�_.20:Ggnllnudtls.. ...................... . 71 77 :�: ?. .. ... .... .. ....... Contipuous.;: ... ........ ... .. ... ❑ .;❑; ,...., Canllnuous; ❑ ❑j; Testing notes Kitchen exhaust WA - hood does not vent to outside Testing tech (initials) FR.S " Oven fuel 1/ Gas _ Elecldc Minirnurri airflow requirement (CFM 5000') +operation ,;L:1O.O:Irile�rmlllent. :'.�_?S.C.onlinuous Measured airflow Flow Flow box _ Pilot tube traverse Tool Interior grille Air temp❑ Passive Dow hood Flow grid Exhaust duct through 84 ADCF 1.088 r t001— — locationjExteria tcrtnlna5on notOK _ Powered now hood _ Other (note below) ) tool (F) ':• Indicated flow 214 CFM Volumetric flow 233 CFM 5000' Pass ❑ Fail Testing notes Residential Mechanical Design Submittal V20140101 Page 1 approach and targets Testing tech (Initials) R.S Testing ;:Ls ❑ N/A: No complete AC system ❑ NIA: House completed November • April (:nsraring coneactorrosponsibie for resting to warm reamer) m TXV: Subcooling + SH check ❑ Non-TXV: Superheat ❑ OEM -specific: Approach ❑ Other OEM -specific (dacmenialion requ red) .:' Temperatures Condenser Non-TXV: Return Target ?%�•>. Target " Target 68 fl 1Q < 4. approach ": i.'i'ii .. (F): entering air temp air wet -bulb temp superheater subcoolin � a r EM Subcooling Dischar a Condenser LI uld Actual m TXV Pass: Actual SC within +/- q pressure 00 saturation T g� F line 73 F subcooling 8 F 3 F of target SC, 2 F min (PSI) ❑ 150eo•chan)❑ temp (condT-i:gOneT)❑ TXV Fall Superheat Suction Evaporator Suction Actual ❑Non-TXV Pass: Actual SH pressure❑ saturation T❑F Ilne❑F superheat❑F within +/• 5 F o(target SH (PSI)F] temp (avctrnoT-erhe .ONon-TXV rail TXV checks: ❑ Pass: Field -Installed TXV Installed In accordance with OEM Instructions . Caution: Actual SH outside mfgr range Approach 1 Liquid line Actual approach ❑Approach Pass: Actual approach within +/• 1 F of target approach lamp (trq Ona T-condenser EAT) ,]Approach Fail Register air flows Testing tech (initials) R.S All registers are cut through finish materials and moving air ❑ Pass ,[] Fall (Remainder of register air flow section under development, not yet being enforced) Pressure balance Testing tech (initials) R.S Room Room•to-Core Measured (match names on plans, Include Pressure Drop Pressure Pass Fall basement If there Is a door) Target Range (Pa) Drop (Pa) Master Bedroom 2.2 ,❑ ❑:' Bedroom 2 Bedroom 3 1.8 : i?❑' Bedroom 4 Residential Mechanical Design Submittal V20140101 Page 4 yy �i - ._.�_..�•a "Mt.4N; r. 4Q.': �...".:.. .nY'.?�y!'._X �=:3 fin¢:.i�� ^1"''-•:. � Combustion safety testing NIA — no natural -draft combustion appliances ❑ (Appliance Types table must be completed for every home) Testing tech (initials) R Appliance types Appliance Combustion Type NIA Draft -hood Natural -draft Induced -draft Natural -draft Power- vent Direct- vent Powered sealed - combustion Electric Furnace #1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Furnace #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Boiler #1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Boiler #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Water heater#1 ❑ ❑ ❑ ❑ [.] ❑ ❑ Water heater #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Fireplace #1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Fireplace #2 ❑ ❑ 0 ❑ ❑ ❑ ❑ Olttor: ❑ ❑ ❑ ❑ ❑ ❑ ❑ Worst -case depressurizatlon performance House seta These doors are _ # of bath fans on _ Venled range hood on _ Clothes dryer on _ Air handler on Oltrer fans on: Other soluo note Outdoor temperature =F %.1 CAZ pressure B depressurization PI I i Iml P avert outs de ( I Measured net CAZ depressudzation (Pa wrt outsido) OK (less negative)) Caution (more negative) .Spillage B ma ximum a xl mum limit (seconds Measured spillage duration (seconds Pass = duration not exceeding limit urart pressure 5 ' BPI 1I n1t Pa wrt CAZ ( 1 Measured (Pa wrt CAZ) Pass = pressure more negative than limit CO concentration in undiluted Due gas BPI maxi i m (PP mumlmt ) Measured CO (ppm) Pass = CO level not exceeding limit Caution = CO level 25 to 100 ppm Testing notes to ❑ OK =i0, Caution II -TOT 'rU%. Caution I ❑ OKT:E:<. Caution ❑ jPoSs :: Q: Fa11 tj' Pass ..::D Fall ❑ Pass ::.❑ :Fall ❑ Pass I ❑ Fait ❑ Pass ;❑;': Fail IPass ❑;; Fail ❑: Pass ._❑, Fail Q� Pass , ❑ 'Fail ❑ .Pass :;[[:. Fail :+❑; cautionfli lCaullon ;;❑;: Caution Residential Mechanical Design Submittal V20140101 Page 5 System Controls Operating Per Design Intent Local exhaust (ell fans) ❑ N/A Pass.L.']r' Fail Whole -house ventilation ® NIA ❑ Pass Fail Sub -structural floor exhaust � NIA ❑ Pass rP'% Fall Heating (all systems) ❑ NIA Pass "❑ Fall Cooling (all systems) ❑ N/A Pass �.�❑' Fail Testing tech (Initials) FS Testing Notes Technician g1 performing Inspection and testing documented on this report (Approved Agency) I certify that the tests referenced above, In sections bearing my initials, were performed in accordance with protocols specified by the ;::;City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. Rigaberto Santibanez Air Flow Tech Four Seasons Heating Inc. RigobertoSantibenez 8/18115 Technlelan p2 performing Inspection and testing documented on this report (Approved Agency) ;- I certify that the tests referenced above, In sections bearing my Ini0aIs, were perform ad in accordance with protocols specired by the City of Fort Collins Building Services Department, and that the reported re suits are accurate to the best of my knowledge. Na Signature HVAC Contractor (City of Fort Collins license holder) I certify that I have reviewed this report and that the test results are an accurate representation of the performance of the Installed mechanical ;:;:systems. Name (print) Lynn Cobb Tille Project Manager Company Four Seasons Heating Inc. Signature and Data Lynn Cobb 8119/15 Residential Mechanical Design Submittal V20140101 Page 6 Systems other than sub -structural floor exhaust Testing tech (initials)FR.S Code-mInImurn ventilation airflow 99 CFM 5000, Design ventilation 99 CFM 5000' (based on CFA and # of BR) airflow System . ... type Supplyanly ..... ... CFM 5000, Target ventilation airflow, range .. ..... ow) Measured Afrflow Air Tamp Indicated Volumetric Measurement Method Tool Location Through ADCF Flow Flow Pass Fall Taol(F) (CFM) (CFM 5000') Total NIA Passive flow hood exhaust Z Flow box Pilot tube traverse Laundry 64 1.088 94 102 airflow Flow collar Other (note below) Total NIA Passive flow hood supply Flow box Pilot tube traverse airflow Flow collar Other (note below) When supply airflow Is circulated by air handler fan, fan speed for mcasurementi Heating Cooling Continuous fan Balanced airflow In balanced systems Average of measured CFM Target now range CFM supply + exhaust flows 5000'(avers ge 115%) El Pass ;E3Fail Testing notes Sub -structural floor exhaust ❑ NIA no sub -structural floor exhaust system Testing tech (Initlals)[R.S. Target eirflow limits ... ....... to Design exhaust airflow (based on CFM 5000' 5 ... .. . ...... ..... (design 44- 15%) CFM 5000 ' `:`I: ... ... approved design) ...Measured airflow — Flow box — Pilot tube traverse Tool Passive flow hood _Flow collar location through tool — ❑ ADCF Powered flow hood Other (note below) tool (F) Flow Air temp Indicated flowl 1CFM VOIUMOtHC JIDWI CFM 5000' El Pass Fall Testing notes NIA No ductwork Testing notes No ductwork outside conditioned space Oncl mult:ple sys) Duct leakage .-;e data source nor so (name House conditioned floor area sf Airtemp ADCF (include rub basement) through tool (F) F Maximum Allowed Duct Leakage Measured Duct Leakage System #1 System #2 Test Parameter and Conditions Normalized Absolute (CIFIV1255000'1100sn (CFM25 5000') Indicated Volumetric (CFM25) (CFM25 5000') Leakage Type Timing Alr Handler Pass Fall Pass Fall Total leakage Rough -In Excluded 4 Total leakage Rough -in Included 6 IX El: Total leakage Complete Included 12 El — e-a Complete Included 8 outdoors Residential Mechanical Design Submittal V20140101 Page 2 +; For multiple systems, attach one page per system System # 17 Which pads of house does It serve? Main Floor Installed equipment (Be clear about which AC components are Installed at time of testing) Testing tech (initlals) R.S Furnace or Boller AC or Heat Pump Condenser AC or Heat Pump Coil Manufacturer Bryan( Carrier Carrier Model tt 912SB48080517 CA13NA030 CNPVP3017AL Filler olUmbus Type _ Basic fiberglass Basic pleated Thlcnches ness A1ERV� _ Electrostatic .� brand _Other: ( ) (optional) _ High-offic pioated Static pressures Sotup Speed: _ Heating ✓ Cooling _ Cont. fan _ Hfgh-stage for mull( -stage equipment Blower speed tap: Low Humidifier damper: ✓ N/A _ Open (Healing) _ Closed (Cooling) ✓ All registers open Zone dampers open SP1 AP Filter 29 (SP1 - sr2) Cooling: Measured air flow through indoor coil Design cooling eirffow 1220 CFM 5000' h� hsw e (5 5) Measured airflow SP2 -4g ❑ WA -- no AC installed Testing tech (inllfals) R-S (szmo lonton - SP4 16 for NSOP, TFSOP) AP Coll (sr3-Sao) 35 -SP3 51 AP Total ESP 100 (SP3-SP2) Testing tech (Initlais) R.S. Target airflow limits ::::.......::::.:::::::.....:....:...:..:....,....:.,,...... (design +/- 15%)l to..:1403... c:...;: CFA15o00' Flow grid _ 14 Air temp❑ F plate size i/ 20 through 64 ADCF 1.088 NSOP tool (F) Measured airflow, no 1078 CFPA Indicated airflow CFM adjuslment/correclion WacurcdAFxFRCF 1078 Testing notos Heating: Gas manifold pressure Manifold pressure 3 5 IVJC OEM spec Q 5000' Heating: Temperature rise TFSOP[497Flow Resistance Correction Factor Volumetric airflow 1173 CFM R9Pass Ind:umed Ar x ADCF 5000' .[f Fail (high sMgu) Target manifold ) limits (spec+/- 5%) 3....::;:.;<:,: IWC OEM temperature rise limits F Supply _ Return Temp Measured temps (F): air 120 air 64 rise 58 Pass Testing tech (initlals)R.S Measured 3.5 IWC [✓Pass pressure Fail Testing tech (Initials) FR.S [] Fail Caution: within 10F :;,.-of lop of range Residential Mechanical Design Submittal V20140101 Page 3 TTesting tech (initials) [R.S Testing approach and (argots D NIA: No complete AC system ❑NIA: House completed November - April finsioing contraclarresponsible (m ie&Gng la warm weather) .4.MTXV: Subroollnu +SH check []Non-TXV: Superheat ❑ OEM -specific: Approach ElOther OEM-speclflc (dixumenLaGon leqv;red) Temperatures I Non-TXV: Return Target r7777771 Targetr77771 Target Condenser F78 superheatsubcooling approach (F): entering airwet-bulbtemp El S. ubcoollnq Condenser Li liqu!,d Ao�ual TXV Pass: Actual SC velthIn 00 in saturation T! fir _]F bc ng pressure 105 Litaill 78 8 F 3 F of target SC, 2 F min (SX0, chart) tamp W U- liq line T) TXV Fail Disch:rge ure F (PSI)F; F (cons Superheat saturation T line F within +/- 5 F of target SH S (PSI) (5000'chart) tamp El Non-TXV Pass: Actual SH Suction Evaporator Suction ressure Actual p F F suprhe El El (suct We T - evap T) Q Non-TXV Fall TXV checks: ❑ Pass: Field -installed TXV Installed In accordance With OEM Instructions Caution: Actual Sil outside mfgr range Approach Liquid lin0 F Actual approach 0 Approach Pass: Actual approach Wthin 1 F of target approach jUq [n lemp a T . =denser EAT) F7 FF EI.Approach Fall F7,.-'fRo6_rfi-Air','f lbw"* J%% .t Pressure Wlwv-' Register air flows Testing tech (initials) All registers are cut through finish materials and moving air Pass Fall (Remainder of register air flow section under development, not yet being enforced) Pressure balance Room Room -to -Core Measured (match names an plans, Include Pressure Drop I Pressure basement If there Is a door) I Target Range (Pa) Drop (Pa) Testing tech (initials) = ?ass Fall El h. glue Residential Mechanical Design Submittal V201401 01 Page 4 :.;r:✓:,..,::• *:.�a:��;'`Ss6 �".r � is[.�' ii' .:.Ji,� i' )'d" '-�R'::, - Combustion safety testing N/A — no natural -draft combustion appliances (Appliance Types table must be completed for every home) Testing tech (Initials) R.S Appliance types Appliance - Combustion T pe NIA Oraft-hood Natuial-draft Induced -draft Natural draft) Power- vent Direct- vent Powered sealed- combustion Electric Furnace k1 ❑ ❑ ❑ El El El ❑ Furnace k2 ❑ El ❑ El ❑ Boller kl ❑ ❑ ❑ ❑ El El Boiler #2 ❑ ❑ ❑ U ❑ El Water heater kl ❑ ❑ ❑ El El[1 Water healer k2 ❑ 0 ❑ ❑ ❑ ❑ El Fireplace ki El ❑ ❑ El ❑ ❑ Fireplace 1l2 ❑ ❑ El El El ❑ El Other: r- J ❑ ❑ ❑ ❑ ❑ ❑ Worst case depressurization pertorinance Nouse sotu r These doors are cl _ k of bath fans on _ Vented range hood on _ Clothes dryer on _Air handler on Other fans on: Olhcr setup notes: Outdoor temperature = F CAZ pressure BPI depressurization limit (13a vrn outside) Measured net CAZ depressurization (Pa wrl outside) OK (loss negative) Caution (more negative) ..::..Spillage BPI maximum limit ( seconds Measured spillage duration (seconds Pass = duration not exceeding limit Draft pressure BPI limit P t (Pa vr, t CAZ Measured (Pa wrt CAZ) Pass = pressure more negative than limit ':.;.CO concentration In undiluted flue gas BPI maxima m limit m (PP ) Measured CO (ppm) Pass = CO level not exceeding limit Caution = CO level 25 to 100 ppm �:. Testing notes ❑ OK ❑:_ Cautlon ❑.OK [] Caution ❑ OK : Cautlon 60 ❑ Pass I_❑ _` Fail ❑ JPass ;%IT': Fnll ❑ Pass ':❑ Fail ❑ Pass I❑:= Fall ❑ Pass ❑% Fail Q Pass Fall ❑: :10g::.: Pass ;❑_ Fail : ❑ Pass ❑:"]Fail .❑ :Pass ❑; Fail `.❑" Caution :❑:' Caution %.0 Cautlon Residential Mechanical Design Submittal V20140101 Page 5 . , • I , ; ;� • �p��..�-;��° .... s � � � ' �X. �:l..�i'!di'Y.:�V'I.' �4 � �T� � I a�x;� �F ,', .[s;i�:: -.f.3.�'� '.A}'y,'� � Testing tech(irrtfals)R.S ! S stam Controls Oporaling Y Per�es�gn Intent Testing Notes local exhausl(all fans) ❑ NIA � Pass !��O= �ail � Wholo-housovenlllatlon ❑ N/A �,/] Pass ��0����:rail Sub-slruclurallooraxhausl � N/A ❑ Pass ':���Fail Heatinp(oll syslems) ❑ N/A � Pess =;��:. Fail Cooling(all systems) ❑ NIA � Pass !�� Fali � :.. .. . � .:.. . , . � :: . . :- .. . . ��...: . . . . , . , ..� . . . . . .�. .,, . . . }.,. ...._ �, . . � , ...�., . . . _ �F:� .,.. :f�JF. . ..r .:_ � .Jfi'c�:[':a,�fi3:._,e_„S:Y=s:�^6a�vt�g� .1fi41. '^L"�=�:-'�'- ws�'. ; . .: .: :. '' tg" : Techniclan#t periorming Inspectlon and tesling documented on lhls report(Approved Apency) :'.�<`.I certify Ihat Ihe tests re(erenced a6ove,In sectlons bearin�my inlllals,�5ere performed in accordance with protacols spoclfied by the � _���:City of Forl Collins 8ullding Servlces DepaAment,antl Ih2t tho reported results are accurate to iho best of my knowlodge. Namc(print) Ric�oberto Santibanez i - Tiue Alr Flow Tech � Cornprny Four Seasons Heating Inc. � Slgnature and Datc Rigoberto Sanlit�anez 8/18/15 � Tnchnlcian#2 porfornilng Inspecllon and testin�documented on this report(Approved Agency) ; �-.":;I certify lhat Ihe lests referenced above,fn sections bearing rny inilials,were performed in accordance vrilh proiocols specifieJ�y lhe � �;-Cityof Fort Colllns Buildinp Servlces Departmant,end tnal lho reported resulls arc accuralo lo lhe best ol my knowledge. i Name(print) i ri^ Titfe � Company � Sipnaturc and Date ! � HVAC Conlrac[or(City of Fort Collins Ilconco holder) :�.��1 cenify Ihal I have reviewed lhls report and Ihat lho lost resulls aro an accurate roprosentation of the pertonnanca of ihe Inslalled machanlc2l � '.a`syslems. � Namu(pr�nt) Lynn Cobb ! i - I Tiuo p�oject Menager I Company Four Seasons Healing Inc. Slgneture end Date Lynn Cobb 8/19/15 � � Residential Mechanical Desfpn Submittal V20140101 Pago 6 i i . �S— c a— Zoi� City of Fort Collins Residential Mechanical Systems Performance Report Thls(orm Is a record ol lesling targets end rosults,wifh PasslFall oulcomes.For Infonnalion on measurement lools and tesling techniquas,seu lhe 'Residentlal New Conslrucllon Mechanical Syslems Tesl;ng Guido."The guide and this form may bo periodically updated;eheck Iho 8uiltling Services web sile lofthe current verslon. , Thls form must bo comple[ed and slgned by an'Approved Agency,"and submilled to 8uilding Serv:ces as a rnqulremont for recelving a C.O. �������������� Moasured valuo �'������� ��,�� � �� ADCF=Alr Densily Carreclion Factor,based on tooi, Colof �7argel,. �"�"' ��`"�'"�=� Olhnr allitude(5000'),nir temperature thiough tool to compare wilh Pass :Fall_. Coolian': ADCF key or:limlt:: - - � data �. targetorlimit Volumetricflaw(CFh15000')=AOCFxIndlcated0ow(CFA7) � � � Address 2383 Palomino Df Date of'Rosidential Mechanical Systams Desi�n Submittal" [iullder D-R Horton Information refcrenced HVAC canirac(or Fouf Se850n5 HeBling Inc, by tostlny tochniclans As-built changes vs � mech deslgn submittal 7estiny date(s) Tuesday 8/18/15 . . . . Bath exhaust Testing tech(inillals) R.S. ���': flaw ✓Flow 6ox Pitot�ubo duct Iravorso Air temp 64 ADCF 1.088 `. tool Passlve flov�hood Olher(nole below) Ihrough looi(F) MoasureU Airllow Design Mlnimum Airtlow Requlremont Indlcated Volumetrie Exhaust Plckup Loeallon Alrllow (CFM 5000') Flow Flow Pass Fotl (CFM ..,; 5000' •TYPo o(Oporatlon (CFM) (CFM 5000') ::..: :;.,�.:.�:�.:,.:�::,:.::.�.::�:�...:,..�:..:.:.,::�::..::-:.::.:::�.: . ... :�:;.�. MBSte�Balh 50 ;�.��.SO;In(ermil.ten[.�.�;_::�_20,:Con(Inu..ous.:; gp gg �: :'0�',� `.;.�: MasterW/C 50 `�[;.50�.In(eiiniltonf:�:.:.;:`�Y20�Conil.n.y6u§.;:�� 74 81 G� '��Cl��. ;, Balh2 50 `�:soinlermtitenl:<:;%:.:sa`Cpntir�uous;.. 75 F32 � �Ll�:. '�50.Intermiltenl;'::��:'�::�;20.Conlinuoiis.::� ❑ ;=��.�. �:�_;50.IntC�mitient;:�;���_�YD,Coritl�uous:.: ❑ <�.�t.�' �'._SO,.Intermltlent.:::,�:'�:�20.'Continuous;�.. ❑ ���;j '� :,.., . . . ......:............::.... .... ... ........ ........ :��_:SO.��Intennllteii).�:;:�:::'�20:;Conlinpou's:;::: ��.�>Q�� :�:���Tosting notos Kitchen exhaust N/A-hood does nol venl to outsido� Testing lech(Inillals) R.S � �� Ovenfuel _Gas ,_EleclAc MinlmumalrBowrequlremont(CFM5000')+operation �"_.�t00..Intermlllent:::;:�.��25�ConlinuoUs�; :��;��Aieasured airRow Fiow box Pitot tube Iraverse Inlorior rille Alr lem ��''�`� Flow—Passivellowhood Flowgrid Tool—Exhaus9duct through❑ ADCF� �� ����_Powered(Iow hood _Other(nolo bolow) �acati0fl(Exle�ior Imn!nnlion nol OK) tool(F) . :`: Indlcated flow CFM Volumelric flow CFM 5000' ❑Pass :[?Fail `?':7csting � notes Residenllal Alechanlcel Design Submlllal V20140101 Pago 1 il � - � . � Systems other than sub-structural floor exhaust Teslinp tech(inilials) R.S i�: Code•minimum venlilation alrllow�CFM 5000' Doslgn vcnlilalion�CFM 5000' ; (hased on CFA and p ol BR) a��o�'+ System —Exhausl-only , ����� Supply-only .....:..:..........:�,�.�.:•.:..�.:: lype —Balanccd ����to.:::'�.:::',;;:;::..;�:�.:::::::::::�.:'.;::.:,� CFM 5000' — :��.����Tar�otventiletionalr�owran9c ::.���:��::.`..':�:��.':'_.�.:.,;'�'.;:::;:,-::�.:::�.,;�..��:�:::�:���:;�::...,:;::'.;�::,::::;:;:. ..(cpdamin!mum) ... .:::�".(1205oo�doa!gnflavj��... Moaeured Atrftow AlrTemp Indicoted Volumetric MeasuramontMethod 7oolLocatlon Through ADCF Flow Flow Pass Fall Tool(F) (CFM) (CFM 5000') � =�� Total NIA Passiva Ilow hood ���: exhausl Plowbox Pilottubotraverse ❑ :;���°. ��: elrllow Flowcollar Other(notebelow) �� Total N/A Passiveflowhood - ':.� supply _Flow box Pitot tubo lr�vcrsa ❑ °':��;?� '�� eir�low Ffow collar Other(nule below) When supply al�low Is clrculated by air handler fan,fan speed for measuremenl Hoating Cooting Conllnuous fan �;��?�Balenced elrilowin bnlanced syslems Averagcolmoasured CFM Targetllowrnnge ;::�:^.�':�:::;»�.�:`.-���!r:`::,:>'-:;�:>::<.:::i:;�:'; CFM �`' � su I +exhnust(Iot+rs�5000' avcra c+/•15% � �t.o�tri�::::=.;.';�:��:::�:;. � ❑Pass :�Feil PPY � 9 )��"::%:�.�.��:z:��.:%`.:',i�:�.-.;:.,��::::�:t[:::::���.::�;":::�000' ;�� Tos�ing With s stem#1 � notes Y Sub•struetural floor exhaust �NlA—no sub-slruclural lloor exhaust system Tesling tech(inilials)R.S. z, Dosign exhaust alr0ow(based on Targat eirllow Iimils::,�.:?.;'.::;:�::;::;:.":'�:`:.:.':�:;::�;:�•:•:.:.;.:i,:r:::?3��.��.:':�:�::�.:.::��:...: CFM 5000' i_ ;�:�:::�.tfi`�;:;:::��;�::>?.:::;�:'��:::�'::�:�:;':;:.CFM 5000' ` ::i:�.. .... ..�.•.��:::: :.:::;.::;:, '��"' a roved desi n dosl n ! 15% :.,.. PP B ) ( 9 ) �r�:::r'�:>�:.�!:�:�::�t�::'::i:'�::;:.;.::::�::::�:,:::.:::•:�:=:;..;:..�::�.:.:.: `:���''���Measured alrllow :_��:..� F�aW _Flow box _Pilol tubo fraverse Toal Air 1em :� lool —Passlve IIoW hood _Flow collar Iocalion ihrou h ADCF _Pawered Ilow hood _Ofher(note below) tool(P)❑ � .':i Indicaled fiow Cf-M Volumetric Ilaw CFM 5000' ❑Pass �0 Fail .'.r� Tesling notes � � • • � . . • N�n_No duchvork Tosling nolas � �No ducl�trork outsldo canditioned space ('ncl mulGplo xysj Duct leakage—Tasling tech(inlllals): data source---Energy rate�(name, eompany,tesling date): House condltloned Iloor area 5� Alr temp qOCF (inUWefNI Wsement)� throu9h tool(F)� � � Maxlmum Allowed Duct Loakago Measured Duet Laakage Syetem N1 9ystem#2 ' Tost Parameter and Condillons Normalized Absolute Indicatod Volumelrle Leakage 7ypa Tlming Alr Handlar (CFM25 5000'/100 sq (CFtd25 5000') (CFM25) (CFM25 5000') Pass Fail Pass Fall Tolalloakage Rough-in Excluded 4 D�.� :Q;.: U. ;[�. Tolal leakage Rough-In Included e p.�� �:o:� :o:`�:���. Tolal leakage Complele Inctuded 12 - ❑:; ;?Q.�; �iQ.:s�]�� ' Leakage � ��� � � to outdoore Camplete Includetl 8 �❑ �',[];; ❑ ;�:G]�=: .:::�.:.:::.::::..:.:.... . . I .::.:..:.::.._:.:..,...;. _ Resldential Mechanical Doslgn Submlltal V207A0101 Pago 2 I . : : :,,.. .. : ,. . .:. ;:- . < .. , . � . . . � � �. .:w� ;-:.�:�.t..��:*:�,.t. r>.� :. ,.. , .. :. -...,..-. :. 31.��" ._.Y�'..-e. -��9�.s:�. -a+w�.w�.-i'.-.::.i-�ver'„�t'yr.'_ 9 For multiplo syslems,allact�ono pago per systam System 1J� W hich paris af l�ouse Coes it serve? Uppet Floo� Installed 2qUlpmflnt (�e clear about which�C components a:e installed at tlme ol tes!inr�) Tesling tech(initials)R.S Furnace or Boller AC or Hcat Pump Condonser AC or Heat Pump Coll '` Manufacturcr Bryant Carrfer Carrier Modelq 912S848060S17 CA13NA030 CNPVP3017AL � Fillor Basic fiburgiass _Electrostatic , .: brand olumbUs Type ✓Baslc pleafed _Ofhor: � Thickness 2 PdEftV 8 i _Hlgh•efflc plealed (Inches)❑ (oPlional�❑ i � ' Static pressures Tnsting loth(Initials) R.S � :�.;�:� Setup . � .�r.�:��:Spocd:_Hoalinc7 �Cooling _Cont.fnn i�;��.�. SP� (s,momUron � 37 iorr�sor, i :.;, TFSO?) _High•stapo for mulli-ste�e equlpment r':� \ +.. ���� Dlowerspeedlap:�oN' .;. . ��' 4P Coll� ;..�;. � (SPJ-SP4) � � �:���:�Humidifierdampor:�NIA ;�� � _Open(Hoating) ` � � _Closetl{Coollnc�) �''���� ; .. .. .. . SP3 �p � :��: ✓ Allreglstersopen :';.::;y�:; �;:�,;;:�'.�,�. . i ' _Zone dampers open ��•�.�± � I .f:``.;�:: SP1 ::�.�: j::•1t.: : ` -32 `,•;.;:;,: , \ "�:5�-������-�� OP Talal ESP 107---- I � ��.`-,:;`'i'�,_,�:�`'.�;'. �sra-srz� :,:.e.;�"e':y:•'.: .: nN r•iuer .35 ' ' �sai• srx) I ., \ SP2 -�7 ' � i Cooling:Measured afr tlow through indoor co(I ❑NIA--no AC insla!led Tesling tech(inilials) R.S. I Design cooliny airfiow � Tar�et alrflow limits "'�����������������'����������:��.:��:'��=� Rhstae 1084 CPM�000' 921.�:,::.:;.i�;2::�.::.�.:`::�:';`�:4Q::�:,12.4.7:..':;�;;:;..`::.`..�:�.��::�.::CFA75C00' . ;... _: . ..:.. {'a� �) dasi n+/-15/, � � ;-; l 9 ) ...::.:................:.:...,..., I r::�.�PAeesured airllo�.v � Afr temp i Ffow�nd �4 FlowResislance j '� lale size 20 �hrough g$ ADCF 1,08� YSOP qp TFSOP 3g � � P � tool(F) Correclion Faclor i Moasured alrflow,no 62 CFM InJicated air0ow �Gz Cfh1 Vo!umelric alrllow 1056 �F�`� �Pass I ad�uslmenUeonecllon 6eeasureanFx�ftc� ir.a'unoaarxnocF�5000' .�Fall I ��� Tostinc� nofos � Heattng:Gas manifold pressure (M19h e�nge) Testlnp tech(inilials)R.S Manifoldprossuro TargetmanifoldP �"��`����� '��`�������'���"'������ Aleasured mPuss ' 3 5 IWC 3:3:':;::.:::s.fo`3.7';':`;:' IWC 3.5 IWC i � �' O[M spec�a 5000'� limils(spec+/•5%)� Prossuro Q Fall Heattng:Tnmperature rise Tosting tecli(initials) R.S � O[M temperelure risc Ilmils� � 35::...::>:to 85.:;::.4;t:::F .... >::: � ,. . ����: (h!qhSL: o :::;.. 5 )'�::::.::::.:::�"....:�:�::..:.....:.... ' P ( � pp y Re�urn 68 Temp�5 �pass �[�.Fail �[�Cautlon:v.ilhin tOF � ;:'.'.�.'Measured Lem s F: Su allr 123 air� rise� . . :... of lop of ran�c � i � ' I Rosidential A4echanlcal Deslpn Submltlal V2014otUt Pnge 3 �