Loading...
HomeMy WebLinkAbout1708 Deep Woods Ln - Disclosures/Blower Door Test - 05/14/2015BUILDING LEAKAGE TEST Date of Test: 5/14/2015 Test File: 1708 Deep Woods Ln Multi Point Tectite Technician: Brad Smith - EnergyLogic Project Number: 35782 Customer: Midtown Homes Building Address: 1708 Deep Woods Ln Fort Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 925 CFM50 ( +/- 1.0 %) (50 Pa = 0.2 w.c.) 2.81 ACH50 2. Leakage Area: 50.9 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 87.0 ( +/- 25.5 %) Exponent (n) = 0.604 ( +/- 0.064 ) Correlation Coefficient = 0.99448 4. Test Settings: Test Standard: RESNET Multi-Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 54.0 CFM 0.16 ACH 10.8 CFM per person 2. Estimated Design Infiltration Rate: Winter: 101.5 CFM 0.31 ACH Summer: 63.7 CFM 0.19 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 55.4 CFM Base Rate: 60.0 CFM Infiltration Credit: <4.5 CFM> BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 5/14/2015 Test File: 1708 Deep Woods Ln Multi Point Tectite Building Information Volume 19722 Surface Area 5311 Floor Area 2246 Height 20 # of Bedrooms 4 # of Occupants 5 Year of Construction 2015 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 13013-7 4/16/2015 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 5/14/2015 Test File: 1708 Deep Woods Ln Multi Point Tectite Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 68.0 64.0 5003.0 Data Points Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration 0.2 n/a n/a -66.8 -66.9 36.5 1098 1113 0.8 Ring A -62.3 -62.4 32.9 1044 1058 -0.0 Ring A -60.0 -60.2 31.3 1018 1031 -0.3 Ring A -57.5 -57.7 29.3 987 1000 -0.8 Ring A -53.8 -54.0 26.8 945 958 -1.2 Ring A -50.6 -50.7 249.4 935 947 1.4 Ring B -47.7 -47.8 227.7 893 905 0.5 Ring B -44.7 -44.8 206.8 852 863 -0.4 Ring B 0.1 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 5/14/2015 Test File: 1708 Deep Woods Ln Multi Point Tectite Comments Connection to: Garage: -45.1 Mechanicals: -50 Pa