Loading...
HomeMy WebLinkAbout1061 Mary Jane Way - Disclosures/Blower Door Test - 12/14/2014BUILDING LEAKAGE TEST Date of Test: 12/14/2014 Test File: 1061 Mary Jane Way Technician: Doug Jean, Efficiency Matters, LLC Project Number: Customer: Aspen Heights Aspen Heights Fort Collins, CO Phone: 573-286-7115 Email: atuttle@myaspenheights.com Building Address: Boulder 1061 Mary Jane Way Fort Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 1105 CFM50 (50 Pa = 0.2 w.c.) 3.74 ACH50 2. Leakage Area: 60.8 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 86.9 Exponent (n) = 0.650 (Assumed) 4. Test Settings: Test Standard: RESNET One-Point Test Test Mode: Depressurization 5. Accuracy Level Reduced Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 50.7 CFM 0.17 ACH 2. Estimated Design Infiltration Rate: Winter: 74.0 CFM 0.25 ACH Summer: 54.3 CFM 0.18 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 12/14/2014 Test File: 1061 Mary Jane Way Building Information Volume 17703 Surface Area Floor Area 1967 Height 9 # of Bedrooms 4 # of Occupants Year of Construction 2014 Wind Shield M Location Climate Information Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) - Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 12/14/2014 Test File: 1061 Mary Jane Way Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature (°F) Altitude (ft) 69.0 42.0 4800.0 Baseline Pressure Data Baseline 1 (Pa) 47 Baseline 2 49 Baseline 3 48 Baseline 4 52 Baseline 5 51 Average Baseline (Pa) 49.4 Baseline Range (Pa) 5.0 Data Points - Data Entered Manually Nominal Building Pressure (Pa) Baseline Adjusted Building Pressure (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) Fan Configuration -1.8 -51.2 39.7 1144 1122 Ring A Time Averaging Period: 10 Deviations from Standard RESNET One-Point Test - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 12/14/2014 Test File: 1061 Mary Jane Way Comments None