HomeMy WebLinkAbout5863 Northern Lights Dr - Disclosures/Blower Door Test - 06/01/2015BUILDING LEAKAGE TEST Date of Test: 6/1 /2015 Test File: 5863 Northern Lights Dr Multi Point Tectite Customer: Ryland Homes Technician: Brad Smith - EnergyLogic Project Number: 35012 Building Address: 5863 Northern Lights Dr Fort Collins, CO 80528 Test Results 1. Airflow at 50 Pascals: 1305 CFM50 (+/- 5.3 %) (50 Pa = 0.2 w.c.) 1.72 ACH50 2. Leakage Area: 71.7 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 339.3 (+/- 107.0 %) Exponent (n) = 0.344 (+/- 0.265 ) Correlation Coefficient = 0.79167 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 85.9 CFM 0.11 ACH 12.3 CFM per person 2. Estimated Design Infiltration Rate: Winter: 143.1 CFM Summer: 89.8 CFM 0.19 ACH 0.12 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 100.7 CFM Base Rate: 100.7 CFM Infiltration Credit: <0.0 CFM> BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 6/1/2015 Test File: 5863 Northern Lights Dr Multi Point Tectite Building Information Location Climate Information Volume 45501 Surface Area 9611 Floor Area 4817 Height 30 # of Bedrooms 6 # of Occupants 7 Year of Construction 2015 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 13013-7 4/16/2015 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 6/1/2015 Test File: 5863 Northern Lights Dr Multi Point Tectite Depressurization Test: Environmental Data Indoor Temperature (°F) Outdoor Temperature CF) Altitude (ft) 76.0 82.0 5003.0 Data Points Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration -1.9 n/a n/a -69.6 -68.3 80.8 -71.2 -69.8 69.8 -66.7 -65.4 57.3 -55.5 -54.1 54.3 -57.0 -55.6 63.5 -50.9 -49.5 54.1 -48.7 -47.4 56.3 -46.0 -44.7 51.4 -0.8 n/a n/a Time Averaging Period: 10 1618 1565 7.8 Ring A 1507 1458 -0.4 Ring A 1368 1324 -7.5 Ring A 1333 1290 -3.8 Ring A 1439 1392 2.9 Ring A 1331 1288 -0.9 Ring A 1357 1313 2.5 Ring A 1298 1256 0.1 Ring A Deviations from Standard RESNET Multi -Point Test - Test Parameters None * n value outside of normally accepted limits. * correlation coefficient outside of normally accepted limits. * n value and/or correlation coefficient limits are not officially part of the RESNET Multi -Point Test Standard. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 6/1/2015 Test File: 5863 Northern Lights Dr Multi Point Tectite Comments Connection to: Garage: -47.1 Mechanicals: -50 Pa