HomeMy WebLinkAbout251 Boardwalk Dr - Special Inspections/Field Verification - 05/19/2015251 Lawrence H. Finn & Associates, Inc. Nei ip 55 S. Elm Ave., Suite 220 — Eaton, CO 80615 ® Phone (970) 454-5351— Fax (970) 454-5391 2389 0"-�WaAW V CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 5/19/15 PROJECT Home Instead Plaza JFK Parkway and Boardwalk Fort Collins, CO ARCHITECT WG Architects P.O. Box 270788 Fort Collins, CO ENGINEER SRB Consulting Engineering 37127 Cullison Ridge Road Windsor, CO CONTRACTOR Poudre Valley Air 2416 Donella Ct. Fort Collins, CO DAVI�(CHEI V asas Exp.3131/18 Lawrence H. Finn & Associates, Inc. Fan Unit PROJECT: Home Instead Plaza LOCATION: Ft. Collins, CO SYSTEMNNIT: EF-5 AREA: Unit'Data Fan Manufacturer Twin City Fan Fan Model Number T080-A Rated CFM 87 CFM Fan Type Forward Curve Fan Size 4" ID Fan Class 1 Fan Arrangement SWSI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 50 CFM Total CFM Actual 83 CFM Fan RPM Design Direct Drive RPM Motor Volts 1 122 Volts Motor Amps 1 0.5 Amps SP In Actual -0.05 in. we SP Out Actual 0.1 in. we Total SP Actual 0.15 in. we * Notes DATE: 5/19/2015 CONTACT: Keith Finn N E jB _a 2389 Tested By: Keith Finn Test Date: May 14, 2015 Motor Data Motor Manufacturer Newtone Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 0.6 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Make Direct Drive L.H. Finn and Associates Final Report Page 12 of 14 Lawrence H. Finn & Associates, Inc. Roof Top Unit PROJECT: Home Instead Plaza LOCATION: Ft. Collins, CO SYSTEM/UNIT. RTU-1 AREA: Unit Data" ". Unit Manufacturer Carrier Unit Model Number 48TCDD12C3T5AOB2CO Unit Serial Number 1115P97368 Unit Discharge Vertical/Down RTU-1 / Supply Fan Fan Type Forward Curve Fan Size 13" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Vertical/Down RTU-1 / Filter Bank Filter Manufacturer Airguard Filter Type Disposable Filter Quantity 4 Filter Size 20x2Ox2 Starter Data RTU-1 / Supply Fan Installed Thermal Internal . Test Data, " Total CFM Design 3900 CFM Total CFM Actual 3912 CFM Outside Air CFM Design 490 CFM Outside Air CFM Actual 503 CFM Return Air CFM Design 3410 CFM Return Air CFM Actual 3422 CFM RTU-1 I Supply Fan Fan RPM Actual 1037 RPM Motor Volts 1 207 Volts Motor Volts 2 208 Volts Motor Volts 3 208 Volts Motor Amps 1 8.4 Amps Motor Amps 2 8.6 Amps Motor Amps 3 8.3 Amps DATE: 5/19/2015 CONTACT: Keith Finn diBBB 23899 Tested By: Keith Finn Test Date: May 15, 2015 Motor Data RTU-1 / Suooly Fan Motor Manufacturer Marathon Motor Frame 145TZ Motor RPM 1725 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 13.6-12.7/6.4 Amps Motor Service Factor 1.15 Sheave Data° RTU-1 / Supply Fan Motor Sheave Make Browning Motor Sheave Model 1 VP65 Motor Sheave Dlam. 6 1/2 in. Motor Sheave Bore 7/8 in. Motor Operating Diameter 5 in. Fan Sheave Make Fenner Fan Sheave Model AFD84 Fan Sheave Diam. 8 1/2 in. Fan Sheave Bore 1 in. Number of Belts 1 Belt Size AX54 Sheave Center Line 17 3/4 in. a, Test Pressures Fan SP In Actual -1.23 in. we Fan SP Out Actual 0.54 in. we External SP In Actual -0.89 in. we External SP Out Actual 0.54 in. we OA Damper Pas Actual 15 % RA Damper Pas Actual 85 % Unit External SP Actual 1.43 in. we Filter/Coil SP In -0.89 in. we Filter/Coil SP Out -1.23 in. we L.H. Finn and Associates Final Report Page 4 of 14 L�wr�ence H. Finn & As�ociates, Inc. N E t �� 2389 Roof Top Unit PROJECT:Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Collins,CO CONTACT: Keith Finn SYSTEM/UNIT:RTU-1(Conk) Tested By: Keith Finn AREA: Test Date: May 15, 2015 RTU-1 Supply Outlet Summary System,%Unit Area Sarved�� 'Outle#::,' .5ias�CzW/Fi. ;� AK <,`Maulmum ` Preltm _ Maximuin %Btel(m %llFinal � ' `d � ° �=F��'i'ype� 6�' v.Factor� ;�Design .; *Reading`� �Ftnal�� � `Devia}fon`. ,pe4iat�o�� ,� . t<,. � .< �.�, , � . . , : c. r � .,�� ., , �.. � OuUet-01 Office A 24x24 200 207 204 104 102 Outlet-02 See Print B 24x24 150 278 148 185 99 Outlet-03 Carridor A 24x24 200 236 206 118 103 OuUet-04 Reception A 24x24 300 391 303 130 101 Outlet-05 Office A 24x24 200 203 189 102 95 Outlet-OB Open Area A 24x24 200 205 202 103 101 Outlet-07 Open Area A 24x24 200 221 190 111 95 Outlet-OS Open Area A 24x24 200 211 207 106 104 Outlet-09 Open Area A 24x24 200 231 200 116 100 Outlet-10 Family Conf A 24x24 250 193 241 77 96 Outlet-11 Office A 24x24 200 137 206 69 103 OuUet-12 OpenArea A 24x24 200 199 204 100 102 Outlet-13 Office A 24x24 200 211 199 106 100 Outlet-14 Office A 24x24 200 183 212 92 106 OuUet-15 Office A 24x24 200 209 203 105 102 Outlet-16 Scheduling C 16x12 200 235 192 118 96 OuUet-17 Scheduling C 16x12 200 209 204 105 102 Outlet-18 Scheduling C 16x12 200 178 198 89 99 Outlet-19 Scheduling C 16x12 200 166 204 93 102 �'`- � Totals,:: <• ds � ' ' ,3.900� 4.1Z3`"- ` ' 3�972 °� ' 106„%� z r�`�100°/a �a * Notes L.H.Finn andAssociates FinalReport Page 5 of 14 � �w. N�E B B Lnwrence H. Finn & Associntes, Inc. -��-:.a e::_ 2389 Roof Top Unit PROJECT: Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Collins,CO CONTACT: Keith Finn SYSTEM/UNIT:RTU-2 Tested By: Emerson Moore AREA: Test Date: May 14, 2015 Unit Data Motor Data Unit Manufacturer Carrie� RTU-2/Supplv Fan Unit Model Number 48TCDD08C3T5AOB2C0 Motor Manufacturer Ma�athon Unit Serial Number 1015P97305 Motor Frame 145TZ Unit Dlscharge Vertical/Down Motor RPM 1725 RPM RTU-2!Suppiv Fan Mator Rated Volts 208-230/460 Volts Fan Type Forward Curve Motor Phase 3 Fan Slae 13"ID Motor Hertz 60 Hz Fan Class 1 Motor FL Amps 13.6-12.7I6.4 Amps Fan Arrangement DWDI Motor Service Factor 1.15 Fan Discharge VeRical/Down RTU-2/Filter Bank Sheave Data Filter Manufacturer Airguard Filtar Type Disposable RTU-2/Supplv Fan Fllter Quantlty 4 Motor Sheave Make Browning FilterSize 16x20x2 MotorSheaveModel 1VP65 Motor Sheave Diam. 6 1l2 in. Starter Data Motor sheave eore 7/8 in. Motor Oparating Dlameter 5 in. RTU-2/Supplv Fan Fan Sheave Make Browning Installed Thermal Intetnal Fan Sheave Diam. 9 1!4 in. Fan Sheave Bore 1 in. Test Data Number of Belts � .. ' se�t s�ze Ax5s Total CFM Deslgn 3000 CFM Sheave Center Line 18 in. Total CFM Actual 2958 CFM Outside Air CFM Design 370 CFM Outside Air CFM Actual 391 CFM Test Pressures Retum Alr CFM Design 2630 CFM Fan SP In Actual -0.90 in.wc Return Air CFM Actual 2567 CFM Fan SP Out Actual 0.35 in.wc RTU-2/Suoclv Fan Extemal SP In Actual -0.59 in.wc Fan RPM Actual 943 RPM Extemal SP Out Actual 0.35 in.wc Motor Volts 7 208 Volts OA Damper Pos Actual 15% Motor Volts 2 207 Volts RA Damper Pos Acfual 85% Motor Volts 3 208 Volts Unit Extemal SP Actual 0.94 in.wc Motor Amps 1 6.6 Amps Filter/Coi1 SP In -0.59 in.wc MotorAmps 2 6.7 Amps FiltedCoil SP Out -0.90 in.wc MotorAmps 3 6.8 Amps L.H.FinnandAssociates FinalRepon Page 6 of 14 . � Lawrence H. Finn & Associates, Inc. ��.� B� 2389 Roof Top iJnit PROJECT: Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Collins,CO CONTACT: Keith Finn SYSTEM/UNIT:RTU-2(Cont.) Tested By: Emerson Moore AREA: Test Date: May 14, 2015 RTU-2 Supply Outlet Summary System/Unit Area Served Outlet Slze LxW!D AK Maximum Prelim Maxlmum %Prelim: %Final Type a Factor �esign , Reading Final Deviatfon . Devtadort Outlet-01 VesGbule C 12x8 100 173 101 173 101 Outlet-02 Womans B 12x12 100 179 97 179 97 Outlet-03 Office A 24x24 200 117 188 59 94 Outlet-04 Corridar C 12x8 100 203 100 203 100 Outlet-05 Lobby C 16x12 300 333 289 111 96 Outlet-O6 Lobby C 16x12 300 312 303 104 101 Outlet-07 Mens B 12x12 100 184 102 184 102 Outlet-08' B 12x12 0 0 0 NaN NaN Outiet-09 Office A 24x24 200 120 185 60 93 Outlet-10 Office A 24x24 200 147 185 74 93 Oullet-11 Corridor A 24x24 100 194 96 194 96 Outlet-12 Files B 12x12 50 118 48 236 96 Outlet-13 O�ce A 24x24 150 179 152 119 101 Outlet-14 Kitchen A 24x24 150 154 147 103 98 Outlet-15 Restroom B 12u12 50 121 53 242 106 Outlet-16 Training Area A 24x24 150 174 153 116 102 OuUet-17 Training A 24x24 250 239 254 96 102 Room OuUet-18 Training A 24x24 250 222 250 89 100 Roam Outlet-19 Training A 24x24 250 229 255 92 102 Roam TOtals: - - 3�000 3�398 2�958 �13% 99% * Notes RTU-2/Outlet-08 14-May-15 Keith Finn Outlet deleted. L.H.Finn and Associates FinalReport Page 7 of 14 � Ln�vrence H. Finn � Associates, Inc. �E� B�� 2389 Fan Unit PROJECT: Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Collins,CO CONTACT: Keith Finn SYSTEM/UNIT:EF-1 Tested By: Keith Finn AREA: Test Date: May 14, 2015 Unit Data Motor Data Fan Manufacturer Twin City Fan Motor Manufacturer ANA Fan Model Numher T250 Motor Rated Volts 115 Volts Fan Type Forward Curve Motor Phase 1 Fan Size 5 1/2"ID Motor Hertz 60 Hz Fan Class 1 Motor FL Amps 2.1 Amps Fan Arrangement DWDI Motor Service Factor 1.0 Fan Discharge Horizontal Sheave Data Starter Data Motor Sheave Make Direct Drive Installed Thermal Intemal Test Data Total CFM Design 210 CFM Total CFM Adual 202 CFM Fan RPM Actual High RPM Motor Volts 1 123 Volts MotorAmps 7 1.8 Amps SP In Actual -0.1 in.wc SP Out Actual 0.1 in.wc Totai SP Actual 0.2 in.wc * Notes L.H.Finn andAssociates Fina/Report Page 8 of 14 . �u Lnwrence H. Finn & Associ�tes, Inc. N�� B B 2389 Fan Unit PROJECT: Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Collins,CO CONTACT: Keith Finn SYSTEM/UNIT:EF-2 Tested By: Keith Finn AREA: Test Date: May 14, 2015 ` Unit Data Motor Data " Fan Manufacturer Twin City Fan Motor Manufacturer ANA Fan Model Num6er T250 Motor Rated Volts 115 Volts Fan Type Fonvard Curve Motor Phase 1 Fan Slze 5 1/2"ID Motor Hertz 60 Hz Fan Class 1 Motor FL Amps 2.1 Amps Fan Arrangement DWDI Motor Service Factar 1.0 Fan Dlscharge Horizontal � � � � Sheave Data Starter Data Motor Sheave Make Direct Drive Installed Thermal Internal Test Data Total CFM Design 210 CFM Total CFM Actual 199 CFM Fan RPM Actual High RPM Motor Volts 1 123 Volts MotorAmps 1 1.7 Amps SP In Actual -0.15 in.wc SP Out Actual 0.1 in.wc Total SP Actual 0.25 in.wc ' Notes L.H.Finn andAssociates FinalReport Page 9 of 14 � � Lawrenee H. Finn & Associates, Inc. �E.� B� 2389 Fan Unit PROJECT: Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Coliins,CO CONTACT:Keith Finn SYSTEM/UNIT:EF-3 Tested By: Keith Finn AREA: Test Date: May 14, 2015 Unit'Data Motor Data Fan Manufacturer Twin City Fan Motor Manufacturer ANA Fan Model Number T150 Motor Rated Volts 115 Volts Fan Type Forvvard Curve Motor Phasa 1 Fan Slze 5 1l2"ID Motor Hertz 60 Hz Fan Class 1 Motor FL Amps 1.3 Amps Fan Arrangement DWDI Motor Service Factor 1.0 Fan Discharga Horizontal Sheave Data Starter Data Motor Sheave Make Direct Drive Installed Thermal Internal Test Data Total CFM Design 140 CFM Total CFM Actual 132 CFM Fan RPM Actual High RPM Motor Volts 1 122 Volts Motor Amps 1 1.0 Amps SP In Actual -0.1 in.wc SP OutActual 0.15 in.wc Total SP Actual 0.25 in.wc * Notes L.H.Finn andAssociates Fina/Report Page 10 of 14 • �,�m. Lawrence H. Finn & Associates, Inc. ��.= B B 2389 Fan Unif PROJECT: Home Instead Plaza DATE:5/19/2015 LOCATION: Ft.Collins, CO CONTACT: Keith Finn SYSTEM/UNIT:EF-4 Tested By: Keith Finn AREA: Test Date: May 14, 2015 Unit Data Motor Data Fan Manufacturer Twin City Fan Motor Manufacturer ANA Fan Model Number T250 Motor Rated Valts 115 Volts Fan Type Forward Curve Motor Phase 1 Fan Size 5 1/2"ID Motor Her� 60 Hz Fan Class. 1 Motor FL Amps 2.1 Amps Fan Arrangement DWDI Motor Service Factor 1.0 Fan Discharge Horizontal Sheave Data Starter Data Motor Sheave Make Direct Drive Installed Thermal Internal Test Data Total CFM Design 250 CFM Total CFM Actual 229 CFM Fan RPM Actual High RPM Mator Volts 1 123 Volts MotorAmps 1 1.8 Amps SP In Actual -0.15 in.wc SP OutActual 0.1 in.wc Total SP Actual 0.25 in.wc * Notes L.H.Finn andAssociates Fina/Report Page 11 of 14