HomeMy WebLinkAbout2103 Yearling Dr - Disclosures/Blower Door Test - 12/03/2014BUILDING LEAKAGE TEST . L .0 i A 4 3 Date of Test: 12/3/2014 Test File: 2103 Yearling Dr Multi Point Tectite Customer: DR Horton Technician: Brad Smith - EnergyLogic Project Number: 33715 Building Address: 2103 Yearling Dr Fort Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 2206 CFM50 (+/- 0.7 %) (50 Pa = 0.2 w.c.) 2.95 ACH50 2. Leakage Area: 121.3 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 204.9 (+/- 16.9 %) Exponent (n) = 0.607 ( +/- 0.042 ) Correlation Coefficient = 0.99767 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 128.7 CFM 0.17ACH 25.7 CFM per person 2. Estimated Design Infiltration Rate: Winter: 242.0 CFM Summer: 151.8 CFM 0.32 ACH 0.20 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 84.1 CFM Base Rate: 84.1 CFM BUILDING LEAKAGE TEST Page 2 of }je -- '�✓�1 Date of Test: 12/3/2014 Test File: 2103 Yearling Dr Multi Point Tectite r !,� Building Information Location Climate Information Volume 44801 Surface Area 8607 Floor Area 4663 Height 20 # of Bedrooms 4 # of Occupants 5 Year of Construction 2014 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6128 Cooling Degree Days 297 Design Winter Wind Speed 7.3 mph Design Summer Wind Speed 9.4 mph Design Winter Temp Diff 73 deg F Design Summer Temp Diff 15 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 13013-7 6/17/2014 BUILDING LEAKAGE TEST Page 3-of 4 Date of Test: 12/3/2014 Test File: 2103 Yearling Dr Multi Point Tectite )) -J Depressurization Test: Environmental Data UJ :5 IIJJ � Indoor Temperature (A°F) Outdoor Temperature (A°F) Altitude (ft) 70.0 36.0 1 5003.0 Data Points Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration -2.6 n/a n/a -69.1 -65.5 30.5 2687 2605 0.2 Open -67.3 -63.7 29.0 2619 2539 -0.6 Open -63.1 -59.5 26.9 2527 2450 -0.0 Open -55.9 -52.2 170.6 2330 2259 -0.3 Ring A -56.1 -52.4 23.3 2353 2282 0.5 Open -51.8 -48.1 157.8 2243 2174 0.8 Ring A -49.8 -46.2 148.7 2179 2112 0.5 Ring A -47.3 -43.6 134.2 2072 2009 -1.1 Ring A -4.7 n/a n/a Time Averaging Period: 10 Deviations from Standard RESNET Multi -Point Test - Test Parameters None ' BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 12/3/2014 Test File: 2103 Yearling Dr Multi Point Tectite _...,_, Comments '� � �� � � �� � (%� �. Connection to: l� �� � � Garage: -45.0 Mechanicals: -50 Pa